| 1 | [20.71.1]Supply, erection, testing of Ceiling fans IS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge 1. 48\\" (1200mm) |
| 2 | [20.72]Supplying, errection, testing of Exhaust fan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structure confirming to latest IS specifications complete in all respect to satisfaction of Engineer-in-charge. |
| 3 | [23.22.1.9]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.9. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 6 amp to 100 amp , 25 KA |
| 4 | [23.22.3.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 3.2. Supply and erection of sheet steel enclosures 1pole/2 pole/4 pole on wall/on existing pedestal complete as required. S.P.N. or DP enclosure suitable for DP MCB |
| 5 | [23.22.4.6]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.6. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DB Horizontal type Double Door 6 way ( 8 incoming 3phase*6 outgoing) |
| 6 | [23.22.4.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.8. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DB Horizontal type Double Door 12 way ( 8 incoming 3phase*12 outgoing) |
| 7 | [23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole |
| 8 | [23.23.1.3]MISCELLANEOUS 1.3. Supply and fixing Galvanised Iron flexible pipe complete with socket nipples and check nuts etc. at both ends (Up to length of one metre):- Size 25 mm dia |
| 9 | [23.24.3.5]MS STAND, BUS BAR CHAMBER AND PANELS 3.5. Supply and erection of metal clad bus bar chamber made from 1.6 mm thick M.S. sheet and fixing with rag bolts on wall or on existing pedestal/angle iron frame including bonding, detachable top and bottom including painting and necessary connection etc. (Aluminium bars). 200 amp 4 bars of 55 cm each (cross section 38 mm x 6 mm) chamber over all size 60 cm x 45 cm x 18cm |
| 10 | [23.3.6.4]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.4. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 6 Sqmm(1/2.80mm) |
| 11 | [23.3.6.5]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.5. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 10 Sqmm(1/3.50 mm) |
| 12 | [23.3.6.7]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.7. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 2 run of Size 2.50 Sqmm(1.1.80mm) |
| 13 | [23.3.6.8]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.8. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 2 run of Size 4 Sqmm(1/2.24mm) |
| 14 | [23.3.6.9]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.9. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 3 run of Size 1.50 Sqmm(1/1.40mm) |
| 15 | [23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. |
| 16 | [23.7.6.3]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.3. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 32 mm dia. |
| 17 | [23.8.11.7]FITTING AND ACCESSORIES 11.7. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. step type Fan Regulator 2 modules 300 watt |
| 18 | [24.1.10]EARTHING AND LIGHTENING ARRESTOR 10. Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material. |
| 19 | [24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. |
| 20 | [24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required. |
| 21 | [24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. |
| 22 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. |
| 23 | [24.13.24]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 24. 16 Sq mm 4 core (Arm.) |
| 24 | Supply and Erection of wall Fan of Crompton Greeves or other equivalent make of USHA/Orient/Khatan/Bajaj heavy duty with electronic regulator complete in all respect to satisfaction of Engineer-in-charge. |
| 25 | Supply/Installation/Testing/Commissioning of LED T8 Batten Tube Light fitting with wattage range of 20 Watt or other equivalent make and model of Phillip’s/GE/ Bajaj/LT /Panasonic with lense with high power LED T8 Batten light with complete assembly with LED driver and accessories required to complete the job in all respect including erection and fixing including connection and other petty material for the same upto the entire satisfaction of Engineer-in-Charge of the work. (Warranty- 3 Years Including Driver against any manufacturing defect Separate letter head to be given by the quoting agency). The logo of company should be embossed on the fixture. Please Enable Macros to View BoQ information |