| 1 | Taking down carefully copper/aluminum point wiring (light, fan,socket or power) complete,including fixture and fitting such as as switches, ceiling roses, pendants, regulators, sockets,etc excluing light fittings etc,removing materials to store for keeping in safe custudy or for taking credit ( credit for above items should be made as per conditions separately) and making good disturbed surface of walls, ceiling, floor etc to match with the existing surface complete all as specified and directed. |
| 2 | M & L for servicing of ceiling fans/wall mounted 1200/1400mm sweep of any make/model, including removal of existing winding carefully from the slots,cleaning the slots thoroughly with necessary cleaning agent, applying slot insulation with super enmelled copper number of turns as that of existing and connecting the coils suitable to operate on 230 volts single-phase AC supply permanent capacitor type, tying the windings and applying air dry insulating varnish and drying the windings including complete all as specified and directed. |
| 3 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire including multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and modular sunken boxes, its accessories,modular plate 4,6,8,10,12 & including with multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision sunken concealed terminal boxes complete all as specified and directed for One light/fan/bell/exhaust point controlled by one switch Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 4 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire including multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and sunken for boxes, its accessories,modular plate 4,6,8,10,12 & including with multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision sunken concealed terminal boxes complete all as specified and directed for One 5 amp same board controlled by one switch Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 5 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire including multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and sinkings for boxes, its accessories modular plate 4,6,8,10,12& including with multi stranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision sunken concealed terminal boxes complete all as specified and directed for One 5 amp Indepedent board controlled by one switch Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 6 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire and including multi stranded copper conductor 2.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and sinkings for boxes, its accessories modular plate 4,6,8,10,12 & including with multi stranded copper conductor 2.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision of sunken concealed terminal boxes complete all as specified and directed for the following :-Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 7 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire and including multi stranded copper conductor 4 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and sinkings for boxes, its accessories modular plate 4,6,8,10,12 & including with multi stranded copper conductor 4 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision of sunken concealed terminal boxes complete all as specified and directed for the following :-Note: per point lenght of cable should be 7 to 15 mtr . |
| 8 | M&L for drawing of wire RYB for phase,black for neutral,green for earth wire and including multistranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed FRLSH cable 1100 Volts grade, ISI marked with valied CML number drawn in and including medium grade non flamble heavy duty with decorative casing & caping including elbow,tee,junction boxes double lock type 32mm in size,sunken boxes,plate 4,6,8,10,12 modulare plate, fire resistant, ISI marked including with its fittings and fixtures such as tees, bends, elbows, junction boxes, etc. including multistranded copper conductor 1.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed FRLSH cable 1100 Volts grade, ISI marked with valied CML number as continuity earth wire and including pressed steel sunken concealed terminal box with 3mm thick industrial laminated sheet cover for mounting switches, sockets and fan regulators etc. complete all as specified and directed for the following :--Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 9 | (a) One light/fan point controlled by one switch |
| 10 | (b) One 5 Amps socket on Independent board. |
| 11 | (c) One 5 Amps socket on the same board. |
| 12 | M&L for wiring with and including multi stranded copper conductor 2.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number, drawing through in and including, rigid non metallic, PVC concealed conduit of 25 mm OD and including cutting chases for conduits and sunken box,4,6,8,10,12 modular plate for boxes, its accessories & including with multi stranded copper conductor 2.5 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with valid CML number as continuity earth wire terminating with provision of sunken concealed terminal boxes complete all as specified and directed for the following :--Note: per point lenght of cable should be 7 to 15 mtr . 2.light circuit will be laid seperate conduit not including 5amp, 15 amp coduit complete all as specified and directed. |
| 13 | S&F in repair socket outlet multipurpose, 3 pin, 6 Amps with swith switch flush type complete all as specified and directed. |
| 14 | S&F in repair socket outlet multipurpose, 5 pin, 15 Amps socket with switch flush type complete all as specified and directed. |
| 15 | S &F fix in repair Distribution Board SPN 12 way, 240 volts, factory made powder coated, double door with neutral and earth link, suitable for fixing MCB,s complete including connecting all as specified and directed. |
| 16 | S &F fix in repair Distribution Board SPN 8 way, 240 volts, factory made powder coated, double door with neutral and earth link, suitable for fixing MCB,s complete including connecting all as specified and directed. |
| 17 | S &F fix in repair Distribution Board SPN 4 way, 240 volts, factory made powder coated, double door with neutral and earth link, suitable for fixing MCB,s complete including connecting all as specified and directed. |
| 18 | S &F fix in repair Distribution Board SPN 2 way, 240 volts, factory made powder coated, single door with neutral and earth link, suitable for fixing MCB,s complete including connecting all as specified and directed. |
| 19 | S&F Distribution Board Power Line, VTPN, 4 way, 415 volts, factory made powder coated, double door with neutral and earth link, including 3 pole MCCB 63 Amps rating, 16KA breaking capacity for incoming supply and provision of MCBs 6 to 32 A for out going supply complete all as specified and directed. |
| 20 | S&F in repair lamp holder modular, insulated body with back plate for batten fittings complete all as specified and directed . |
| 21 | S&F in repair modular socket outlet multipurpose, 3 pin, 5 Amps flush type complete all as specified and directed. |
| 22 | S & F Switch Modular (piano) flush button single pole one way 6 amps 1 module with suitable plate and cover complete all as specified and directed. |
| 23 | Supply & fix modular switch 1 way, 16 Amps, 1 module (ISI marked).complete all as specified and as directed. |
| 24 | Supply & fix modular socket 16 Amps, 2 module (ISI marked).complete all as specified and as directed. |
| 25 | S & F Electronic Modular Fan regulator step type not less than 100/120 watt with suitable plate and cover complete all as specified and directed. |
| 26 | Supply and fixing in repair LED lights fitting 1x 20W, 220V,AC decorative type with driver, including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 27 | Supply & Fix in repair decorative wall light fittings compatable for LED Bulb B22 base upto 9W, toughned glass with secondary optics including taking out old unsv fitting of any type complete all specified and directed. |
| 28 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 29 | M&L for Sub main wiring complete with 4 single core, 6 sqmm PVC insulated, unsheathed, 1100 Volts grade, FRLS Hcopper multi stranded conductor drawn in and including PVC conduit not less than 25mm size including drawing 2 run of PVC insulated, unsheathed, 100 Volts grade, FRLSH, copper conductor multi stranded, 6 Sqmm size as continuous earth wire drawn through and connected to main switch/DB and testing on completion complete all as specified and directed. Note : (i). 4 runs of main conductor and one run of earth conductor and one run of PVC conduit shall be measured as one length. |
| 30 | M & L in replacement sub-main wiring with 2 single core 6 Sqmm PVC insulated, unsheathed, 1100Volts grade, copper multi stranded conductor drawn in PVC Concealed conduit ISI marked including with its fittings and fixtures such as tees, bends, elbows, junction boxes, etc. including multistranded copper conductor 6.0 Sqmm (nominal cross sectional area) single core, PVC insulated, unsheathed FRLS cable 1100 Volts grade, ISI marked with valied CML number as continuity earth wire drawn through and connected to main switch/ DB and testing on completion.Note: (i). 2 run of main conductor and one run of earth conductor shall be measured as one length. |
| 31 | M & L for earthing complete with galvanized steel earth plate electrode 60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth lead galvanised iron 4mm dia wire by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvd iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009. Note : RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. |
| 32 | Taking down carefully tube light fitting and refixing after proper cleaning and making good disturbed surfaces of walls etc. complete all as specified and directed. |
| 33 | Taking down carefully cealing fan fitting and refixing after proper cleaning and making good disturbed surfaces of walls etc. complete all as specified and directed. Please Enable Macros to View BoQ information |
| 34 | Taking down carefully cealing fan fitting and refixing after proper cleaning and making good disturbed surfaces of walls etc. complete all as specified and directed. Please Enable Macros to View BoQ information |