| 1 | INTELLIGENT FIRE ALARM SYSTEM |
| 2 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable multisensor detector IP 42 (VDS / EN / UL / FM / ULC approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors.(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 3 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS /EN / UL / FM / ULC approved) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required.(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 4 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 (VDS / EN/ UL / FM / ULC /EN approved).(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 5 | Supply, Installation, Testing & Commissioning of Addressable Input/Output Modules ( VDS / EN/ UL / FM / ULC approved ) for monitoring/controlling Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required.(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 6 | Supply & Laying of 2 Core sheathed 1.5 sq.mm FRLSH flexible copper Cable (For Loop) (Make. Finolex/RR Kabel/Polycab/Gloster) through 20mm dia PVC \\"FR\\" type Rigid Conduit pipe(Precision/Polycab/AKG as approved by EIC ) with necessary arrangement as per GS. |
| 7 | SITC of Power supply 230 V AC to 24V DC with all other accessories. ( Approved Make ) |
| 8 | Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / EN/ UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. ((Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 9 | Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS /EN/ UL / FM / ULC approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice.There should be LAN port(RJ 45 ) for communication with laptop for configuration the fire alarm system. |
| 10 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. |
| 11 | The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software.(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls) |
| 12 | NOTE :- 1) The Fire Alarm system shall comply with latest requirements of --(i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 ,(iii) NFPA 70 National Electric Code,(iv) NFPA 72 National Fire Alarm & Signaling Code ,(v) Local Statutory Regulations ,(vi) Manufacturer Recommendation.vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module etc. and all these components should be of same brand. |
| 13 | TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system.2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. |
| 14 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required |
| 15 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 16 | Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required A) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC Please Enable Macros to View BoQ information |