| 1 | DSR Item 1.10 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2 | Group C |
| 3 | DSR Item 1.15 Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel /PVC conduit including dismantling as required. |
| 4 | Group C |
| 5 | DSR Item No 1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 6 | 3 x 1.5 sq. mm |
| 7 | 3 x 2.5 sq. mm |
| 8 | 3 x 4 sq. mm |
| 9 | DSR Item 1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 25 mm |
| 11 | DSR item 1.24 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 5/6 amps switch |
| 13 | 3 Pin 5/6 A. socket outlet |
| 14 | Telephone socket outlet |
| 15 | TV antenna socket outlet |
| 16 | DSR item 1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 17 | DSR item 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 18 | 1 or 2 Module (75 mmX75 mm) |
| 19 | 4 Module (125 mmX75 mm) |
| 20 | 6 Module (200 mmX75 mm) |
| 21 | 8 Module (125 mmX125 mm) |
| 22 | 12 Module (200 mmX150 mm) |
| 23 | DSR item 1.28 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 24 | 12 Module |
| 25 | DSR item 1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 26 | DSR item 1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 27 | DSR Item 1.33 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 28 | DSR Item 1.38 Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 29 | DSR item 1.57 Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 30 | DSR Item 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB/ RCCB/ Isolator). |
| 31 | 4 way (4 + 12) Double door |
| 32 | DSR Item 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 33 | Single pole |
| 34 | Double pole |
| 35 | Triple pole and neutral |
| 36 | DSR item 4.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 37 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 38 | DSR item 39.17.1 Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, (As per Complete Item 17 of the DNIT). |
| 39 | 1 Run of cable |
| 40 | DSR item 8.1.3LED Down lighter (SMD Type) (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed /surface Down lighter (Round / square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, (As per Complete Item 18 of the DNIT). |
| 41 | 12 -15 watt |
| 42 | DSR item 8.7.10LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, (As per Complete Item 19 of the DNIT). |
| 43 | 36 watt |
| 44 | DSR item 9.2Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, (As per Complete Item 20 of the DNIT). |
| 45 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 46 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 47 | Supply and fixing extra down rod of 15 mm dia G.I. pipe length to fix the ceiling fan. The job includes cost of cutting, making holes and cutting groove in pipe for proper tightening of rod to the fan motor. (As per Complete Item 21 of the DNIT). |
| 48 | Supply and Erection of fan hook for erection of ceiling fan. The hook shall be made out of ½” dia M.S. bar in ‘U’ shape formation. It shall be fixed after chasing the RCC Slab and making necessary repair, plastering to site in original position. The job includes the labour & petty material reqd. to complete the job. |
| 49 | Supply and fixing of 12 modules (200 mm x 150 mm) G.I box suitable for accommodate the following accessories along with modular base and cover plate for modular switches in recess / surface etc as required for Computer Point with 4 Nos. 5/6 Amp. modular switch and 4 Nos. 3 pin 5/6 Amp. modular socket outlet. (As per Complete Item 23 of the DNIT). |
| 50 | Supply & erection of fresh air fan high speed motor with copper wound 10” sweep with louver and plastic body complete with high speed motor, blades, epoxy powder coated of Havells make Ventiliar DX White / Orient make Ventilator / Crompton make Brisk Air/ Bajaj make 70049 250mm sweep only. (As per Complete Item 24 of the DNIT). |
| 51 | Supply & erection of Cabin Fan 16” sweep (metal body) oscillating type complete with aluminium blades & regulator. (As per Complete Item 25 of the DNIT). |
| 52 | Supply & fixing of Computer jack & contact one module RJ45 of Molex/ R&M/ Panduit make including making connection etc. as required to complete the job to the entire satisfaction of Engineer-in-charge. |
| 53 | DSR item 2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required |
| 54 | 100A,30KA,FPMCCB |
| 55 | S/E of enclosure for MCCB 125 Amp 4 pole made out of 16 Gauge M.S. sheet. The enclosure is to be painted after one coat of primer including its erection in existing angle iron board with nut bolts/ screws etc. to complete the job to the entire satisfaction of Engineer In Charge. |
| 56 | Supply and erection of 63/100 Amp. 415 Volt. 4 pole ON Load Change over switch with MS enclosure of following ratings installed in existing switch board/ LT Panel with nuts & bolts of requisite size after making holes etc. (As per Complete Item 29 of the DNIT). Please Enable Macros to View BoQ information |