| 1 | BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER, UDHAMPUR Name of Work: PROVN OF TROLLEY MOUNTED TRANSFORMER FOR AREA OF CPH AND MPH UNDER GE (UTILITIES) UDHAMPUR Contract No: CWE/U(U)-28/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply install , testing and commissioning out door type , Trolley mounted step down transformer 11 kv / 433 volts ( at no load ) AC 3 Each 1 phase 50 Hz , of 750 KVA capacity (or next heigher rating aviilable in the market ) double copper wound , oil immersed , naturally cooled , ( ON AN ) , with external cooling tubes / fins , vector group DYN 11 with neutral brought out on ( LV side ) and having tapings at ± 2.5 % to be changed by means of hand operated OFF load tap changer confirm to IS - 1180 Part - I . 2014 level - 3 & shall comprise of the following:-( a ) one cable box on HT side ( Primery side consisting of 3 No procelain bushings with copper rods complete with nuts & bolts.( b ) one cable box on LT side ( secondary) side consisting of 4 nos porcelain bushing with copper rods complete with nuts & washer ( c ) oil conservator oil level gauge, ( d ) dehydrating breather with first fill of dehydrating agent ( silica gel )( e ) explosion vent thermometer pocket on tank cover oil drain filter valve , lifting lugs oil filling hole with cap / plug air release valve plug & 4 Nos plain soild cast steel detachable rollers ( f ) 1 No 100 mm dia dial type thermometer , vapor pressure type , having range 0-120 degree celsius having maximum temperature reading indicator with resetting. |
| 3 | Srl Item No. 1 Contd/----- ( g ) 2 earthing terminals on tank cover to facilitate fixing of 50X6 mm galvanised iron earth strip for earthing of body ( h ) rating plate & terminal marking plate ( i ) extra bushing for neutral , in the LT cable box for providing independent set of earthing for neutral( j ) first filling of new & unused transformer oil , IS - 335 Marked within filter & tested upto 40 KV di electric strength at 2:5 mm air gap between testing electrodes.The transformer oil shall be fresh and approval certificate from manufacturer shall be obtained by contractor and furnished to GE. the copper shall be 99.97% purity and approval certificate from manufaturer shall be obtained by contractor and furnished to GE. (k) Distribution transformer to be incorporated in the work must necessarily have BIS certification, BEE star labeling and valid Type Test Report duly issued by NABL accredited BlS approved lab. Note: Pre -commisioning, inspection of transformer shall be carried out by rep of Accepting offr and T&P for the inspection shall be arrange by contractor, cost of the T&P etc for testing shall deemed to be included in the unit rate. |
| 4 | Supply install , testing and commissioning out door type , Trolley mounted step down transformer 11 kv / 433 volts ( at no load ) AC 3 Each 1 phase 50 Hz , of 500 KVA capacity (or next heigher rating aviilable in the market ) double copper wound , oil immersed , naturally cooled , ( ON AN ) , with external cooling tubes / fins , vector group DYN 11 with neutral brought out on ( LV side ) and having tapings at ± 2.5 % to be changed by means of hand operated OFF load tap changer confirm to IS - 1180 Part - I . 2014 level - 3 & shall comprise of the following:- ( a ) one cable box on HT side ( Primery side consisting of 3 No procelain bushings with copper rods complete with nuts & bolts.( b ) one cable box on LT side ( secondary) side consisting of 4 nos porcelain bushing with copper rods complete with nuts & washer ( c ) oil conservator oil level gauge, ( d ) dehydrating breather with first fill of dehydrating agent ( silica gel )( e ) explosion vent thermometer pocket on tank cover oil drain filter valve , lifting lugs oil filling hole with cap / plug air release valve plug & 4 Nos plain soild cast steel detachable rollers ( f ) 1 No 100mm dia dial type thermometer , vapor pressure type , having range 0-120 degree celsius having maximum temperature reading indicator with resetting |
| 5 | Srl Item No. 2 Contd/----- ( g ) 2 earthing terminals on tank cover to facilitate fixing of 50X6 mm galvanised iron earth strip for earthing of body (h) rating plate & terminal marking plate. (i) extra bushing for neutral , in the LT cable box for providing independent set of earthing for neutral (j) first filling of new & unused transformer oil , IS - 335 Marked within filter & tested upto 40 KV di electric strength at 2 : 5 mm air gap between testing electrodes.The transformer oil shall be fresh and approval certificate from manufacturer shall be obtained by contractor and furnished to GE. the copper shall be 99.97% purity and approval certificate from manufaturer shall be obtained by contractor and furnished to GE.(k) Distribution transformer to be incorporated in the work must necessarily have BIS certification, BEE star labeling and valid Type Test Report duly issued by NABL accredited BlS approved lab. Note: Pre -commisioning, inspection of transformer shall be carried out by rep of Accepting offr and T&P for the inspection shall be arrange by contractor, cost of the T&P etc for testing shall deemed to be included in the unit rate. |
| 6 | Supply, laying, jointing & testing XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 11000 volts grade cross sectional area 120 Sqmm 3 core laind in trenches or passing through pipe or fixed on poles complete all as specefied and directed. |
| 7 | Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete, all as specified and directed. |
| 8 | Supply, laying and testing HT cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 300 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles complete all as specified and directed. |
| 9 | Design Supply and Commisioning of four wheel platform type trailor size 2500 (L) X 2000 (W) X 600 (H) mm with hook for mounting of Transformer having hydraulic system arrangement in four wheel alongwith supporting bar with following specificaitons:-(a) Trailor will provide with chasis with the main base chasis made of MS channel 150 x 75 x 10 mm thick sheet having dimension of 3600 x 1600 x 6 mm duly welded and supported from the bottom with cross MS channel width wise and 100 x 50 x 6 mm angle length wise.(b) One set per trailor of leaf spring steel primed 14 layers 80 x 10 mm and assy span 950 mm (02 Nos leaf spring).(c) One no square axles of the size 62 x 62 mm.(d) Mechanical parking brake system operated through hand leaver in front of the trailor 03 Jacks.(e) Four Nos new tyres and tubes alongwith heavy duty rim of size 9:50-16 (New) fitted in the trailor.(f) Tringular toe bar made of 80 x 50 mm channel with 36 mm eye hook spring loaded. |
| 10 | Srl Item No.6 Contd/----- (g) All other parameters to meet the suitability of the equipment which is not covered in the above point but is design requirement.(h) The complete structure of the trailor/tyres rims will be painted black after two coats of red oxide primer.Note : Design/drawing shall be submitted for approval before placing the order. The minimum parameter are mentioned however the trolley is to be suitable to carry minimum weight for 750 KVA Transformer all as specified and directed by Engr-in-Charge. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |