| 1 | SUB-HEAD 01 -- Supply & erection of poles |
| 2 | Supply of 8 Mtr height hot dip galvanized octagonal pole made of HT steel of grade S355 with 135 mm bottom A/F & 70 mm top A/F made up from 3 mm thick GI sheet along with base plate of size 225 x 225 x 12 mm thick with inbuilt sleek terminal box with required sizes studs for 4 core 16 sqmm A/Al cable termination as required and 10A porcelain fuse for each outgoing with proper pad locking arrangement (2 nos.)NOTE: Above 6 Mtr & 8 Mtr octagonal pole should contain terminal box capable for fixing of 3 phase connector box incl. S/F of 3 phase looping connector box with allied accessories as per requirement & as per direction of E.I.C. (Make: Utkorsh / Transrail/ Bansal / Skipper / Bajaj / Surya / CG) |
| 3 | Erection of single octagonal pole of length 6/8 Mtr with 4 no 20 mm dia, 600/700mm length “J” type bolt projected100 mm with nuts etc in CC foundation having 600 x 600 x 150 mm thick CC (4:2:1) base block with hard jhama metal including 1300 mm depth x 500 mm dia cylindrical type RCC (6:3:1) muffing & 0.5 Mtr above ground level incl. 3 mm thick neat cemented finish and required size hole for alkathene/ polythene pipe entry, for street light wiring, without loop box with GI earth bolt after making drilled hole etc. on base plate & carriage of pole upto 1.6 km from store to work site incl. filling up excavated earth pit with shifted soil & ramming properly. |
| 4 | S&F of Circular Ring Shaped (ISI-M) (40 mm dia) pole bracket (suitable for Top 70 /90 mm A/F poles to arrange maximum 4 Nos. Led Flood Light Lumineries) of 600 mm dia with 0.3 Mtr long Sleeves of 80 mm dia G.I pipe (ISI-M), incl. S/F of 3 nos ½” MS jam nut each with 1 no ½” dia through bolt, pole cap and painting as to GS of the entire assembly. |
| 5 | Supply & Erection of 1.5 m long pole 80mm dia GI pipe pole with base plate & pole cap Providing CC (6:3:1) muffing 450 x450 x 600 mm in size or equivalent size of cylindrical muffing above ground level /roof top around the pole base complete with 3 mm thick neatly finished cement plaster all round after dismantling the unserviceable muffing if any incl. Al painting and making earth bolt washer and G.I. earth bolt on plate as to G.S. with out loop box incl. fixing of LED street light as per direction of ther E.I.C |
| 6 | Supply and Fixing of single arm header assembly fabricated from 40mm dia. GI Pipe (ISI-M) of 1.5 mtr length rigidly welded with 80 mm dia. GI Pipe (ISI-M) of 0.3 Mtr. long at an angle of 110⁰ & suitable angle between the two arms including S/F 3 Nos ½” MS jam nut each with 1No. ½” dia. through bolt, pole cap incl. painting as to GS of the entire assembly. |
| 7 | Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 4 way stud type terminal etc. and housing the same in pole muffing incl. painting as per direction of E.I.C (200 x 150 x 100mm) |
| 8 | Supply & Drawing 1.1 KV grade 3 Core 22/0.3 (1.5 sqmm) XLPE insulated Un-armoured Cu Cable (Brand approved by EIC) for connection from loop box to fittings through the Pole including making connections as necessary. (Make: Finolex/ RR Kable/ Polycab/ Havells/ KEI/ Gloster) |
| 9 | SUB-HEAD 02 -- Supply & laying of cable & SITC of Timer DB |
| 10 | Supplying and delivery of following size Armoured cablesXLPE/PVC insulated are designed for 1.1 kV StrandedAluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1 / 2011 with Up To Date Amendments.) (Make: Finolex/ RR Kable/ Polycab/ Havells/ KEI/ Gloster) |
| 11 | 2 Core 10 Sqmm |
| 12 | 4 Core 16 Sqmm |
| 13 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 14 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 15 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below & Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 16 | 2 Core 10 Sqmm |
| 17 | 4 core 16 sq.mm |
| 18 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 19 | 2 Core 10 Sqmm |
| 20 | 4 Core 16 Sqmm |
| 21 | Supply & fixing 2+12 way, double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish as compound light timer Control Unit (Indoor type) assembled with following accessories and wiring with 2.5 sq.mm Cu wire (For MCB to Contractor/terminal block),1.5 sq.mm Cu wire (For control wiring) to accommodate the following accessories. |
| 22 | i) 32 A DP MCB (Make:L&T/Legrand/ABB)-1no as incommer |
| 23 | ii) Digital 24 hour time switch (modular type) (Make- L&T/ABB/Siemens)-1no. |
| 24 | iii) 25 A, 2NO, modular type Contractor with IP 20 protection (L&T/ABB/Siemens)-2no. |
| 25 | iv) Toggle Switch(ON-OFF-ON)-1No |
| 26 | v) Modular type Indicating lamp - 2 No. (one for incoming & 1 for outgoing) (Make- L&T/ABB/Siemens) |
| 27 | Supply & fixing compound light timer Control Unit (Indoor type) assembled with following accessories and wiring with 4sq.mm Cu wire (For MCB to Contractor / terminal block),1.5 sq.mm Cu wire (For control wiring). Suitable size 16 SWG CRCA sheet metal box having min depth 3.5\\" and should have adequate strength and space to accommodate the following accessories. |
| 28 | i) 32 A TP MCB (Make: L&T / Legrand / ABB)-1no as incommer |
| 29 | ii) Digital 24 hour time switch (Make-GIC)-1no. |
| 30 | iii) 32A 3-Pole Power Contractor 1 NO + 1 NC (L&T:Cat No-CS94980)-1no. |
| 31 | iv) 25 A TP MCB \\"C\\" curve (Make: L&T / Legrand /ABB) -1no as out going |
| 32 | v) Toggle Switch (ON-OFF-ON)-1No |
| 33 | vi) Out going terminal stud with nut--4sets. |
| 34 | vii) Indication lamp (R,Y,B)- 1 Set. |
| 35 | viii) EI Danger Board (6”X4”) – 1No. |
| 36 | Metal Box should have gasket arrangement inside the door and entry and exit points of IN-OUT power, which protect the dust insertion and two locking arrangement with allen key. The panel box should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing |
| 37 | SUB-HEAD 03 -- SITC of Outdoor type Light Fittings |
| 38 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, |
| 39 | Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours, |
| 40 | (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy ≥135 lm/Watt (Make: Philips Signify/ Crompton/ Havells/ Bajaj/ Wipro) |
| 41 | 120 Watt |
| 42 | Supplying, installation, Testing & Commissioning of Flood light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, |
| 43 | Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, undervoltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours |
| 44 | (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM- 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy ≥135 <135 lm/Watt (Make: Philips Signify/ Crompton/ Havells/ Bajaj/ Wipro) |
| 45 | 70 Watt |
| 46 | Supplying, installation, Testing & Commissioning of LEDhighbay fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, |
| 47 | Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours, |
| 48 | (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevantBIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy ≥135 lm/Watt (Make: Philips Signify/ Crompton/ Havells/ Bajaj/ Wipro) |
| 49 | 150 Watt |
| 50 | SUB-HEAD 04 -- EARTHING INSTALLATION |
| 51 | Excavation of soil for installation of Earth Electrode and filling & ramming. (for soft Soil) |
| 52 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: |
| 53 | By ISI-Medium GI pipe |
| 54 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. |
| 55 | Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S. |
| 56 | Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 57 | Insulating the 65x8 mm MS flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar) |
| 58 | Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. |
| 59 | SUB-HEAD 05 --SITC of LED SIGN BOARD |
| 60 | SITC of Glowsign Board ( Router cutting) with liquid Acrlyic letters with adhesive on ACP Board of 3 mm Thick (Make – Aludecor / Alstone) of suitable size to accommodate all the matters / contains as approved by the authority to be made with 25 x 25 x 4 mm M.S angle Iron, 18 S.W. G square /Round Hollow bar, Base plate (10 mm Thickness) requires for fixing the necessary Nuts, Bolts, Washers, supporting angle Iron, Clamp etc. and ACP Sheet on Front sides & edges only & back side to be covered by GI Sheet (with proper ventilation arrangement), All side to be moulded uniformly, Side fabricated by Aluminium ‘L’Channel, upon which elevated or box type letter made from imported liquid acrylic will be fixed. The Thickness of Acrylic will be 5 mm (for small letters), 8 mm (for Big letters) and 10 mm (for very big letters). The Back Side of the letters is covered by 3 mm thick ACP (Make – Aludecor / Alstone). The inside of the letter of the letter Supplying and Fixing of best Quality LED Lighting arrangement of fully water proof 10 nos. LED light fittings of 20 watt (100 lumen / watt). The letters are sealed by exterior grade Silicon. The back side of the Board Covered by 22 S.W.G G.I sheet with Nuts & Bolts. (1 no Signage- 72 Sq Ft/ 12 Ft x 6 Ft each) |
| 61 | Intensity: Same & smooth uniform throughout without any dark patch. |
| 62 | Visibility: Up to 250 meters for normal eyes. |
| 63 | The complete sign board would be fixed on roof of the building with providing necessary CC muffing, 1 no CI water proof 200 x 150 x 100 mm loop Box, 50 x 50 x 6 mm MS angel for supporting the board of required length by nuts, bolts, washers etc. After drilling holes on the frame front facia. GSB would have 2 nos. hinge type doors in back side to have the inside access including mending goods the damages to original finish. |
| 64 | Painting of any steel / iron surface of the above Glow sign board with no. of coats of paints as given below with ready mixed paint / primer of approved make and brand incl. preparation of surface by sand paper / emery paper, cleaning etc. for receiving fresh coat of paint. |
| 65 | 1st coat of aluminium paint over one coat of RO priming. |
| 66 | 2nd coat of aluminium paint over one coat of RO priming. |
| 67 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint Please Enable Macros to View BoQ information |