| 1 | NOTE: Contractor should rate with all taxes. |
| 2 | Fabrication, supply, erection, testing and commissioning of servo controlled automatic voltage regulator transformer with Buck boost transformerInput voltage 240-450 p-pOutput Voltage 400V p-p 230 N-POver load protectionSingle phase preventerUnder voltage protectionHigh voltage protectionDelay line outputMaterial CopperAll protections through micro controllerOil CooledUn-balanced typeThe stabilizer shall be provided with first filling of fresh transformer oil.Sheet gauge used for fabrication of stabilizer should not be less than 14 SWGSpeed of correction should not be less than 10-20 volt per second efficiency more than 90%40 KVA |
| 3 | Construction of RCC foundation for the Servo stabilizer in 1:2:4 grade with size of 10 ft.x10ft. Lxb and approximate depth of 600 mm and 300 mm foundation below ground level and300mm height should be above ground level |
| 4 | Construction of GC sheet roofing of suitable gauge, (24G) placed on MS angle simple truss structure of (50mmx50mmx6mmthick) having distance of 2 ft between Angle iron and MS pipe of size 4\\" with steel j hooks. The length and breadth of GC sheet roofing should be at least 2 Feet more than the size of the enclosure as per the drawing. The sides should be provided with iron wire mesh with Angle support on sides having double door on one side |
| 5 | Earthing.Supply Installation testing & commissioning of Maintenance free hot deep galvanized on 250 microns Gl earthing system with 10 ft long, 80 mm dia. & 3.0mm wall thickness. (Pipe-In-Pipe with Flat Terminal) Technology. With 2 Bag of Electron High Conductive & Anti Corrosive Compound Spec: 3 mtr Length x 80 mm dia. / 2.96 mm thick/250 micron Electrode Thickness: 3.0 mm / ISI Class - B, Hot Dip Galvanized 250 Microns Terminal size should be 40 x 10 mm thick and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. |
| 6 | PanelSupply, Installation, Testing and Commissioning of LT Motor FASD ControlPanel of appropriate size from CRCA sheet of 1.6mm thickness includingcleaning & finishing complete with powder coating in approved shade havingconnections, interconnections with adequate size copper wire, copper links,connectors and terminal blocks etc along with necessary nut & bolts, clampsetc mounted on wall duly painted Milestones/DVEPL/METFAB makes.Main Circuit Breaker:100A 4 Pole 36kA MCCB with Thermal magnetic Release Ics 100% of Icu,Spreader Terminals & Phase Barriers (LK Make)- 1 No.Bypass Switch 125A FP (Havells Make) - 1 No.Onload Changeover Switch 100A FP (Havells Make) - 1 No.Busbar:125A TPN Aluminium mounted on DMC Busbar Supports and Covered withheat Shrinkable Colour Coded Sleeves -1 SetMetering:Digital VAF, PF Meter Three Phase Class 1.0 (LK/Aiwaa Make) - 1NoDigital Voltmeter Three Phase Class 1.0 (LK Make) - INoRYB LED Indication Lamps - 2 SetsMotor Protection Circuit Breaker Units:63A 3 Pole 50kA MCCB with Thermal magnetic Release(LK Make) - 2 No.2 No.'s Motor Starters MU-G30 FASD 30 HP (With Wideband Coil) - 2 No.Auxiliary Load:MCCB 63A FP 10kA with Thermal magnetic Release Spreader Terminals &Phase Barriers (LK Make)1 NoPa consisting of the following panel board be greated 0.5 feet underground and 1.5 feet above ground level the foundation legs be covered by all sides |
| 7 | Steel Tubular PolesProviding and fixing of Road lighting on steel tubular pole swagged type conforming to IS 2713-(Part-III), pole designation 410-SP-12 complete with base plate, of 300mmx300mmx6mm (Lx BxW), drilling of 25mm dia hole at 2.74 Mtrs from bottom for entry of wire. The Pole to be painted with one coat of primer and two coats of silver white aluminium paint and underground section of the pole is to be painted with one coat of primer and two coats of black enamel paint both inner and outer side. The pole is to be erected by execution of 5 feet x2feet x2 feet pole[pit including making foundation incement concrete in the ratio of 1:2:4(1 cement: 3 coarse sand: 6 graded stone, 40 mm dia nominal), the foundation is to be continued upto 0.3 M above ground level around the pole tapered suitably into the collar in round shape of 0.5 M in dia. The exposed portion of the block is to be plastered properly and white washed. The job includes, excavation of pole pit refilling and canoval of excavated material from the site and properly disposed off complete job in all respect. |
| 8 | SITC of 70w street light fixture on existing street lighting pole made of Pressure die-cast aluminium alloy for housing (heat sink) for effective thermal management, sturdiness, excellent corrosion resistant.High efficiency polycarbonate UV stabilized cover with integrated Lens to ensure Asymmetrical batwing light distribution. fixture to have with built in autonomous sensor with Capabilities of switching ON and OFF with DAWN to DUSK operation. IR sensor to mitigate the effect of surrounding artificial light High efficiency long life LED module with SMD LED package mounted on MCPCB. Lumen efficacy of LED >140 lm/W.NABL lab in-house. Powered by Integral potted electronic driver with APFC, lower THD, Output Short/Open Circuit Protection, Protection upto 10kV (with external SPD), phase to phase (440V) / Over Voltage Protection. CCT 5700, CRI>70, THD<10%, PF>.95, IP66, IK07.Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +50 DEG.C; Input Supply Voltage Range:100V-300V, Driver safety standards :IS 15885-2-13, DRIVER Surge PERFORMANCE REQUIREMENTS: IS 16104, PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, CERTIFICATION: LM 79 FOR LUMINAIRELM 80 Make Phil Page 5s 8 approved by site engineer. |
| 9 | Pole BracketFabrication, supply, installation and fixing ofpole bracket made out of 32 mm dia G.I pipe medium class 1.Mtr long including accessories including bending the pipe to the required shape, 2 no.s 40mm x 3mm flat iron clamps with suitable size nuts, bolts and washer, painting the flat iron with primer and finish paint ete as required suitable for fixing of 36-70W LED luminary. |
| 10 | Connection WireSupply and fixing of 2x1.5 Sq. mm connection wire + 1x1.5 Sq. mm wire PVC insulated, copper conductor single core multi stranded cable from connection box up to light fixture in existing Poles and new Poles complete with connections etc. as required. |
| 11 | CableSupply, laying, Testing and commissioning of PVC insulated, PVC sheathed/XLPE Power cable of 1.1 KVA grade of following sizes 0.75M below ground including digging of trench 0.35M wide 0.75 M depth, protection with SN4 DWC HDPE PIPE 4 inch and refilling the trench, and having suitable 2ft x 2ft main holes after every 15 mtrs. of the cable including main hole covers etc. as required complete Job the cable should be joined with Aluminum Lugs as reqd.(complete job in all respect)10 Sq.mm 4 core cable |
| 12 | P/F of 185 Sq. mm 3.5 core XLPE armoured cable., steel armoured cable 0.75M below ground including digging of trench 0.35M wide 0.75 M depth, providing of Double Wall corrugated(DWC) 75 mm made of HDPE material pipe for cable protection. Including the required heat shrinkable kits, lugs etc. Complete job. |
| 13 | P/F of MCCB 400 Amp with single door type box incl. Amp. Mtr and volt amp. Mtr. and Al. bus bar 250 Amp with selector switches. (weather proof) complete job. |
| 14 | S/I/T/C of 2'x 2'x1' feeder pillar with 4 pole32amp MCB C curve 1 no. 4pole bus bar 100 amp, locking arrangement including 3 feet height angle iron stand above the ground level and I feet below the ground ete. connections as required. |
| 15 | MCB's Supply and fixing of B-series SP MCB 5A, 240V, miniature circuit breaker suitable for inductive load of single pole in existing connection box complete with connections, testing and commissioning etc. as required. |
| 16 | Cable Looping Box(Connection Box)Fabrication, supply, fixing and connectioning of dust and weather proof, gasketted, canopy type connection box in Poles made out of 16 SWG MS sheet 250mm x 250mm x 200mm in size. The connection box is to be fitted with 2 Nos. MS 2 strips 250mm x40mm x5mm on its back side with 2 No. hole on each strip for fixing of box with strip by suitable size nut and bolts. The MS strips shall have to be welded with pole at appropriate place around the existing hole on the pole. the box shall have to provide with hinged cover, locking arrangement, earth studs, neoprene gasket, terminal strip 60A four way, MCB carrier for two no. MCB's complete with connections, two no. 40mm dia. hole at bottom and 25mm dia. hole and centre of back side of the box. The box shall be painted with one coat of primer and two coats of silver white Aluminium paint, complete job in all respects. |
| 17 | Distribution boxFabrication, supply, fixing and connection of dust and weather proof, gasketted, canopy type connection box made out of 16SWG MS sheet 450mmx350mmx200mm (LBW) in size. The connection box is to be welded with 2 No's Angle Iron 25mmx25mm size 4 feet long which should be grouted at least 1 feet below ground level with 3 above ground and 2 feet underground in cement concrete, the box should have the provision for 4 pole aluminium Bus bar and also having the provision for fixing of 10 numbers of MCB's.The box shall be painted with one coat of primer and two coats of paint, locking arrangement etc., and items (Pb1, Pb2). Please Enable Macros to View BoQ information |