| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER BAREILLY Name of Work: SPECIAL REPAIR WKS FOR FUNCTIONAL OF INBUILD FIRE FIGHTING SYSTEM AT MH BAREILLY FOR THE YEAR FY 2025-26 UNDER GE (W) BAREILLY Contract No : CWE / BLY / GE(W) /25 OF 2026-27 Bidder Name : SCHEDULE A(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supplying ,installation testing and commissioning of the following C class MS ERW pipe as per IS 1239 or 3589 for below ground level pipe with flange welded and with as required including pipe of shorter lengths tappering connecting pieces,short and long bends ,Tee, reducers, plugs anchor fastner etc with anticorrosive treatment with 4mm thick polymer corrosion resistant tape as per IS 10221, over lap shall be 15mm minimum complete all as specified and directed. |
| 3 | 150 mm bore dia of pipe |
| 4 | 100 mm bore dia of pipe |
| 5 | 80 mm bore dia of pipe |
| 6 | 63 mm bore dia of pipe |
| 7 | 50 mm bore dia of pipe |
| 8 | 40 mm bore dia of pipe |
| 9 | 32 mm bore dia of pipe |
| 10 | 25 mm bore dia of pipe |
| 11 | M&L for relaying, installation testing and commissioning of the following old serviceable MS ERW pipe retrived from Item sl No 1 for below ground level pipe with flange welded and with as required including pipe of shorter lengths tappering connecting pieces,short and long bends ,Tee, reducers, plugs anchor fastner etc with anticorrosive treatment with 4mm thick polymer corrosion resistant tape as per IS 10221, over lap shall be 15mm minimum complete all as specified and directed. |
| 12 | 150 mm bore dia of pipe |
| 13 | 100 mm bore dia of pipe |
| 14 | 80 mm bore dia of pipe |
| 15 | 63 mm bore dia of pipe |
| 16 | 50 mm bore dia of pipe |
| 17 | 40 mm bore dia of pipe |
| 18 | 32 mm bore dia of pipe |
| 19 | 25 mm bore dia of pipe |
| 20 | Taking downg of the following C class MS ERW pipe below ground level pipe with flange welded and with as required including pipe of shorter lengths tappering connecting pieces,short and long bends ,Tee, reducers, plugs anchor fastner etc with anticorrosive treatment with 4mm thick polymer corrosion resistant tape as per IS 10221, overlap shall be 15mm minimum complete all as specified and directed. |
| 21 | 150 mm bore dia of pipe |
| 22 | 100 mm bore dia of pipe |
| 23 | 80 mm bore dia of pipe |
| 24 | 63 mm bore dia of pipe |
| 25 | 50 mm bore dia of pipe |
| 26 | 40 mm bore dia of pipe |
| 27 | 32 mm bore dia of pipe |
| 28 | 25 mm bore dia of pipe |
| 29 | Supply, fixing and testing cast iron sluice valve class PN 1.6 heavy duty ISI marked, both ends flanged with brass spindle of size 150 mm including taking down complete all as specified and directed. |
| 30 | Supply, fixing and testing cast iron sluice valve class PN 1.6 heavy duty ISI marked, both ends flanged with brass spindle of size 100 mm including taking down complete all as specified and directed. |
| 31 | Supply, fixing and testing cast iron sluice valve class PN 1.6 heavy duty ISI marked, both ends flanged with brass spindle of size 80 mm including taking down complete all as specified and directed. |
| 32 | Supply, fixing & testing cast iron Non return valve class heavy duty ISI marked, both ends flanged of size 150 mm including fitting for connecting the line with jointing material including taking down complete all as specified and directed. |
| 33 | Supply, fixing & testing cast iron Non return valve class heavy duty ISI marked, both ends flanged of size 100 mm including fitting for connecting the line with jointing material including taking down complete all as specified and directed. |
| 34 | Supply, fixing & testing cast iron Non return valve class heavy duty ISI marked, both ends flanged of size 80 mm including fitting for connecting the line with jointing material including taking down complete all as specified and directed. |
| 35 | S&F Gun metal gate valave 50mm ISI marked with iron wheel head, screwed both ends for iron pipe with union, including removing old unserviceable gate valves complete all as specified and directed. |
| 36 | S&F Gun metal fire brigade 4 way inlet connection for connecting to external fire hydrant ring main consisting of four nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories complete all as specified and directed. |
| 37 | M&L for repair, testing of Air Vessel tank/ Air Cushioning tank including replacement of PRV (Pressure release Valve) and unserviceable differential pressure switch complete all as specified and directed. |
| 38 | S&F fire hydrant landing valve type A (single head outlet) of 63 mm dia conforming to IS 5290 complete all as specified and directed. |
| 39 | M&L for yard hydrant Post / Stand Post 80mm dia GI / MS both flanged type 1.5m height complete all as specified and directed. |
| 40 | S&F 63 mm dia, 15 mtr long rubberised fabric reinforced rubber lined hose including gun metal male & female instataneous coupling, hose confirming to IS : 636 type II and coupling confirming to IS 903-1975 complete all as specified and directed. |
| 41 | S&F stantaneous inlet, made threaded outlet, 63 mm dia gun metal branch pipe with 12.5 mm short nozzle conforming to IS 903 complete all as specified and directed. |
| 42 | S&F hose reel drum with hose reel of 20 mm size of 30 meter length complete with stainless steel nozzle ,conforming to IS 884 complete all as specified and directed. |
| 43 | M&L for hose box made of 18 gauge MS sheet 800mm x 600mm x 250mm with Double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet set painted fire red out side and brilliant white inside yard complete all as specified and directed. |
| 44 | M&L for checking, servicing, and testing of sprinkler control valve and making valve functional in each respect for all the Zones complete all as specified and directed. |
| 45 | M&L for Checking, servicing, testing of sprinklers and making sprinklers functional in each aspect complete all as specified and directed. |
| 46 | S&F sprinklers glass bulb type (Standard response) as Per IS:15105/TAC guidelines 79 degree temperature rating pendent type complete all as specified and directed. |
| 47 | S&F pressure guages 4\\"dial 0-14 kgs rating complete all as specified and directed. |
| 48 | S&F pressure switch universal type complete all as specified and directed. |
| 49 | S&F flow switch 150mm dia complete all as specified and directed. |
| 50 | M&L for pipe support for all types of pipes including hangars/fastners/elbows/ supports/ tees complete all as specified and directed. |
| 51 | Repair of Hydrant Point hose cabinet including cleaning of the cabinet ,replacement of lock and Key and replacement of broken glass, repair of damaged PCC stand if any and painting complete hose cabinet Box with fire Red Colour and marking of Fire Hydrant Point No with White colour complete all as specified and directed. |
| 52 | Repair of Hydrant Valves including oiling in the opening wheel and checking and testing of hose reel drum including hose pipe and and its opening valves and testing of leakage and repair in situ and painting the Fire pipeline of hose cabinet box with fire red colour complete all as specified and directed. |
| 53 | M&L for fire alarm control panel complying with PR-10Z+SSA-45M+TBM-16Z-SPX+AS-416-PA 18 ZONE panel Capacity from UPTO 360 detectors complete all as specified and directed. |
| 54 | M&L for detectors complying with and type certified to EN-45 ADDRESSABLEL type multisensor detector with heat and smoke combination with base with self built intelligence as per IS-11360 complete all as specified and directed. |
| 55 | S&F addressable type Flame detectors with UV/IR detection Capacity (add up cost of module to be a complete set, the type of module shall be relay type module) complete all as specified and directed. |
| 56 | M&L for addressable manual call point resettable type complete all as specified and directed. |
| 57 | S&F addressable sounder complete all as specified and directed. |
| 58 | M&L for 4 watt ceiling speaker complete all as specified and directed. |
| 59 | M&L for 250 watt Amplifier complete all as specified and directed. |
| 60 | M&L for fire alarm sounders/sirens electronic type horizontal single stage continuous Normal operation for at least 50 minutes with sound level 65 DB to 120 measured at 1.5 Mtr with sound output variation of 65 DB 1000 mtr range complete all as specified and directed. |
| 61 | M&L for submain wiring with two run of single core PVC insulated unsheathed multi stranded copper conductor FRLS cable of size 1.5 Sqmm 1100 Volts grade and one run of PVC insulated unsheathed stranded copper conductor FRLS cable of size 1.5 Sqmm 100 Volts grade as earth continuity conductor drawn through in and including rigid non metallec PVC conduit of size 15mm dia concealed including making good the disturbed surfaces of wall etc including complete all as specified and directed. (Note :- Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories is deemed to be included in the unit rate). |
| 62 | S&F fire fighting pump house sign board at Pump House Glow sign board with PVC letters of height 10\\" including LED 15 watts module light of each letter, alcopanel of 5mm both side about 100 Sqft with 10 kg iron Frame complete all as specified and directed. |
| 63 | Dismantling and Wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/ blankets, any thickness, including cover fillets complete all as specified and directed. |
| 64 | M&L for horizontal boring below pavement/road, in soft/loose soil for crossing 100mm to 25mm size GI pipe lines complete all as specified and directed. |
| 65 | Excavation in trenches in soft / loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for getting out / taking out / laying of GI / CI pipe line from bottom surfaces of excavation to required level / gradient etc complete all as specified and directed. |
| 66 | Returning, filling in trenches with excavated soil including spreading, eveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed. |
| 67 | Removing excavated material exc. 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 68 | M&L for brick work with sub class B old size brick straight or curved on plan n.exc 6m mean radius built in cement mortor 1:4 complete all as specified and directed. |
| 69 | M&L for rendering 10 mm thick on brick works surfaces of concrete surface of supporting pillar in 1:4 complete all as specified and directed. |
| 70 | M&L for PCC in foundation, filling and mass concrete type D2 1:4:8, using 40mm graded crush stone aggregate complete all as specified and directed. |
| 71 | Demolition of brick or stone /bolder masonary or pipe supporting pillars,kerbs,apron laid in any mortor complete |
| 72 | M&L for cement concrete 1:2:4 type B1 using 20 mm graded stone aggregates for floor/ foundation filling and mass concrete complete all as specified and directed. |
| 73 | S&F suspended false ceiling using Desiner E-grid 2430, 180 GSM (exposed ceiling suspension system ) of grid size 600mmx600 mm with main runner 38 mm x 24 mm and wall angle 24mm x 24mm using 4mm thick High Pressure stean Crude Everest Non Asbestos Fiber Cement plain Board (E-Board Classic) in & including a grid of GI system duly suspended with 4mm dia GI wire hanger fixed with providing positions for light fixtures,air conditioning diffuser and ducts ,sprinkler ,smoke detectors etc.The main runners to be secured to structural soffits by hanger @ 1220 mm maximum c/c. the last hanger at the end of each main runner should not be placed at more than 450mm from the adjucent wall,Flush fitting 1220 mm cross tee to be interlocked between main runners @ 610mm c/c,so as to form 600mm x 600 mm grid incl taking down old ceiling with frame and making good disturbed surface complete all as specified and directed. |
| 74 | M&L POP (Plaster of Paris) false ceiling applying 10 to 12 mm thick POP finish over ceiling surfaces with wall care putty mixed with POP powder in ratio of 1:10(a) PGI sheet of 26 gauge in angle shape of size 25 x 25 mm all around the wall complete.(b) Main runners of 26 gauge PGI sheet in angle shape of size 35 x 25 mm at the interval of 90 cm centre to centre complete. complete including one dome not less than 1 metre dia and frame work complete all as described below : (c) Cross runners of 26 gauge PGI sheet in angle shape of size 35 x 25 mm at 40 cm center to center complete.(d) Suspender/ hanger of 26 gauge of PGI sheets in angle shape of size 25 x 25 mm fixed to soffits of roof by steel fastener complete.Including Dismantling of plaster of paris ceiling (Gypsum anhydrous) to flat surface including framework and G.I. wire mesh complete all as specified and directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |