| 1 | SUB-HEAD 1--Distribution Wiring |
| 2 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish |
| 3 | Average run 8 mtr |
| 4 | Average run 9 mtr |
| 5 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required |
| 6 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 7 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 8 | 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC |
| 9 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 10 | 2.5sqmm |
| 11 | 4 sqmm |
| 12 | 6 sqmm |
| 13 | SUB-HEAD 2-- PLUGS & SOCKETS |
| 14 | Supply & Fixing 240 V 6 A Piano key type switch (Brand approved by EIC) on existing sheet metal switch board having bakelite/perspex top cover by screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 15 | Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc. |
| 16 | Supply & Fixing of 440V, 2.25 mF metal body capacoior having copper terminal in existing ceiling fan. |
| 17 | Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 18 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 19 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 20 | Supplying & Fixing CRC sheet metal (16 SWG) JB-cum-Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. bakelite/Perspex/coloured Perspex (wall matching colour) top cover 3 mm thick flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works |
| 21 | 300 mm x 200 mm x 65 mm |
| 22 | Supply & Fixing bakelite / perspex top cover on existing switch board by Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required |
| 23 | 300 mm x 200 mm x 65 mm |
| 24 | SUB-HEAD 3--BDB,PDB,VTPN, Changeover ETC |
| 25 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make: Legrand/ABB/SIEMENS/Schneider/L&T] |
| 26 | 2+12 way |
| 27 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [Make: Legrand/ABB/SIEMENS/Schneider/L&T] |
| 28 | 4 way |
| 29 | 6 way |
| 30 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [Make: Legrand/ABB/SIEMENS/Schneider/L&T] |
| 31 | 12 way- Up to 160A |
| 32 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. [Make: Legrand/ABB/SIEMENS/Schneider/L&T] |
| 33 | 415V, 63 A FP |
| 34 | 240V, 40 A DP |
| 35 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. [Make: Legrand / ABB /SIEMENS/Schneider/L&T] |
| 36 | 160 A |
| 37 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make: Legrand / ABB /SIEMENS/Schneider/L&T] |
| 38 | 6-32 SP MCB |
| 39 | 32 A TP MCB |
| 40 | 63 A TP MCB |
| 41 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical / SPNDB enclosure with IP-42/43 protection as per GS. |
| 42 | 4/6/8/12 Way (Vertical) |
| 43 | 4/6 Way (Horizontal) |
| 44 | Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc [Make: Legrand / ABB / SIEMENS / Schneider/L&T] |
| 45 | SUB-HEAD 4---SUPPLY OF LIGHT FITTINGS |
| 46 | Supply & Delivery of 240V, 18/ 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 47 | Supply and Delivery of 4 feet Industrial box type twin LED tube fitting incl. Supply & Delivery of 2 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 105 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 48 | Supply and Delivery of 4 feet Industrial box type single LED tube fitting incl. Supply & Delivery of 1 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 49 | Supply & Delivery of 240V LED lamps of following wattage with glare free light distribution having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 50 | 9W LED Bulb B22/E27 Base |
| 51 | SUB-HEAD 5-- FIXING OF LIGHT FITTINGS |
| 52 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 53 | Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener. |
| 54 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 55 | Fixing only lamp |
| 56 | SUB-HEAD 6 -- SUPPLY OF FANS |
| 57 | Supply & Delivery of 230V, 1-Ph, AC ceiling fan of follwing size incl. all accessories. (Make- Crompton / Usha / Orient/ Polar) [BEE star rated] |
| 58 | Sweep Size- 1200 mm (48\\"), Wattage ≤ 55 Watt, R.PM ≤ 350, Air Delivery ≥ 220 C.M.M |
| 59 | Supply & Delivery of 230V, 50Hz, 450 mm sweep heavy duty full metal body wall bracket fan having wattage ≤ 90 Watt, RPM ≤ 1325, Air Displacement (In CFM) ≥ 3550 complete with all accessories. (Make - Orient/Crompton/ EPC/Cinni) [BEE star rated] |
| 60 | Supply & Delivery of 220V, Single Phase, 50 Hz A.C heavy duty exhaust fan of following sizes having complete metal body. (Make- EPC/ USHA/Orient CROMTON) [BEE star rated] |
| 61 | 300 mm (12\\"), 4 Blade, RPM ≤ 920 , Wattage ≤ 45 Watt, Sound level ≤ 46 dB, Air Displacement (In CFM) ≥ 750 |
| 62 | SUB-HEAD 7-- FIXING OF FANS |
| 63 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS |
| 64 | Engraving the deptt. number with 10 mm lettering on the body as per GS. |
| 65 | Extra for additional one letter incl. hifen, stroke and stop |
| 66 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length |
| 67 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter |
| 68 | 30 cm (12\\") |
| 69 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) |
| 70 | 30 cm Exhaust fan (12\\") |
| 71 | SUB-HEAD 8--Supplying & Laying of Cable |
| 72 | Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells as approved by E.I.C] |
| 73 | 4 core 95 Sq. mm |
| 74 | 4 core 50 Sq. mm |
| 75 | 4 core 25 Sq. mm |
| 76 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting (For 4 core 95 Sq. mm Cable) |
| 77 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting (For 4 core 50 Sq. mm Cable) |
| 78 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire. |
| 79 | Up to 50 sqmm (For 4 core 25 Sq. mm Cable) |
| 80 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed (For 4 core 25 Sq. mm Cable) |
| 81 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 82 | 4 core 95 Sq. mm |
| 83 | 4 core 50 Sq. mm |
| 84 | 4 core 25 Sq. mm |
| 85 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 86 | 4 core 95 Sq. mm |
| 87 | 4 core 50 Sq. mm |
| 88 | 4 core 25 Sq. mm |
| 89 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. |
| 90 | 200x50x1.25mm (18SWG) (With 25x25x3mm angle iron support) |
| 91 | Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. |
| 92 | 200x50x1.25mm |
| 93 | Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. |
| 94 | 200x50x1.25mm |
| 95 | SUB-HEAD 9--Compound light |
| 96 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required |
| 97 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint |
| 98 | Supply & Delivery of 240V, LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 99 | 70 Watt |
| 100 | Supply & Erection of GI mini pole of size 2 mtr long approx 50 mm dia seamless pipe class-B (Thickness 3mm) on the roof of the building by Supply & Providing MS plate incl. necy arrangement near base plate for smooth cable entry by pipes and making C.C muffing by size 600x600x760 mm height with cement mortor mixer (6:3:1) neat cement finish before cheaping properly the existing roof incl. S & providing earth bolt after drilling hole etc as per as per direction EIC. |
| 101 | Fixing only Street light Fitting on Pole/Tower or similar structure. |
| 102 | Supply & Delivary LED Decorative Post Top light fitting in Pressure die cast Aluminum base with Prismatic polycarbonate diffuser having following wattage, with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 40,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 103 | Supply & Fixing of 80/40mm dia GI pipe (ISI-M) of 1.5M long on the existing piller of GATE including making arrangement for CC construction upon the piller for fixing of GATE light and making necessary connection. |
| 104 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint |
| 105 | Supply & Drawing 1.1 KV grade 3Core 22/0.3 (1.5 sqmm) XLPE insulated Un-armoured Cu Cable (Brand approved by EIC) for connection from loop box to fittings through the Pole including making connections as necessary. |
| 106 | Weatherproof cabinets - IP 65 - IK 09 - Class II Door and cabinet faceplates from 2-row versions up 2-position rail for modular products and moulded cases. (for 4 pole MCB) [Make- Syntex] |
| 107 | 200x150x100 mm |
| 108 | SUB-HEAD 10 -- EARTHING INSTALLATION :- |
| 109 | Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil) |
| 110 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: |
| 111 | By ISI-Medium GI pipe |
| 112 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. |
| 113 | Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S. |
| 114 | Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 115 | Insulating the 65x8 mm MS flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar) |
| 116 | Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. |
| 117 | SUB-HEAD 11-- SITC of LT panel |
| 118 | Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel. |
| 119 | Construction Details : |
| 120 | All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side. |
| 121 | Incoming Arrangement : |
| 122 | a) 415V, 250 Amps Four Pole MCCB of Breaking capacity 50 kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 1 No. |
| 123 | b) 415 Volts, 250 Amps, on load front operated TPN changeover switch (open execution type) (Make: L&T/Legrand/ Schenider/ABB/Siemens)- 1No. |
| 124 | Bus bar section : |
| 125 | 415 V, 315 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification- 1 set. |
| 126 | The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications. |
| 127 | Outgoing Arrangement : |
| 128 | a) 415V, 160 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No. |
| 129 | b) 415V, 125 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No. |
| 130 | c) 415V, 100 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No. |
| 131 | d) E.I. Danger Board of suitable size ------- 1 no. |
| 132 | Metering Panel:- |
| 133 | a) Digital multifunction meter with selector push button switch (up/down) with Voltage, Current, Frequency, Total Harmonic Distortion, PF, KW, KVA, Kwh, KVAh and Preloaded Max & Min Demand with Date & Time Stamping display (Make-Schneider Electric/ Cat No- EM6400NG Class accuracy CIo.5S, POP of Accuracy Class 0.5S or equivalent model of Legrand/ Siemens/ L&T) - 1 No. |
| 134 | b) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent cat of L&T/ABB/ SCHNEIDER) - 1 No. |
| 135 | c) 500/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos. |
| 136 | d)S & F 2 Amp SPMCB for auxiliary supply to meters (Make- SIEMENS/L&T/Legrand) - 1 no. |
| 137 | Interconnection :- |
| 138 | All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads. |
| 139 | Earthing Arrangement :- |
| 140 | A separate continuous aluminum earth busbar of appropriate size is to be painted at the inside bottom of the panel and run across the full load of the panel board. All electrical equipment are to be properly earthed with suitable size G.I. strip. |
| 141 | The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating. |
| 142 | Installation :- |
| 143 | The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. |
| 144 | Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees. Please Enable Macros to View BoQ information |