| 1 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [D-11/15] |
| 2 | a) 12 way Up to 160A [Make:-Legrand /L&T/Siemens/ ABB as approved by E.I.C] |
| 3 | Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nutsbolts etc. [D-2/3(a)] 200A |
| 4 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [D-10/14] |
| 5 | b) 8 Way Enclosure [Make: Legrand /L&T/Siemens/ABB as approved by E.I.C] |
| 6 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.[ D-9/13] |
| 7 | a) 2+14 way Enclosure [Make: Legrand/Siemens/L&T/ABB as approved by E.I.C] |
| 8 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as per GS.[D-5/6] |
| 9 | 63 A FP (Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 10 | 40 A DP (Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 11 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS.[D-6/7] |
| 12 | 6-32 A SP (Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 13 | 40 A SP (Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 14 | 63 A TP ( Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 15 | 6-32 A DP ( Make: Legrand/Siemens/L&T/ABB as approved by E.I.C) |
| 16 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. [D-8/10] |
| 17 | 160 A FP MCCB (Make- Legrand/L&T/Siemens/ABB as approved by E.I.C) |
| 18 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment. [D-12/16] ( Make as approved by EIC) |
| 19 | 12 way |
| 20 | S&F sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works.[E-4/11] |
| 21 | 175 mm x 100 mm x 65 mm |
| 22 | 200 mm x 150 mm x 65 mm |
| 23 | 240 mm x 200 mm x 65 mm |
| 24 | Supply & Fixing bakelite / perspex top cover on existing switch board by Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required.[E-4/12] |
| 25 | 175 mm x 100 mm x 65 mm |
| 26 | 200 mm x 150 mm x 65 mm |
| 27 | 240 mm x 200 mm x 65 mm |
| 28 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make- Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C) of the following sizes in the prelaid polythene / PVC rigid pipe and by the prelaid GI fish wire and making necy. connection as required [E-9/1] |
| 29 | 3 x 22/0.3 (1.5 sqmm) |
| 30 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC |
| 31 | 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC |
| 32 | 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC |
| 33 | 4x126/0.4 (16 sqmm) + 2x80/0.4 (10 sqmm) as ECC |
| 34 | Distribution wiring in 1.1 kV single core stranded 'FR' PVC insulated & unsheathed copper wire ( Make- Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.[E-14/1(a)] |
| 35 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 36 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 37 | 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC |
| 38 | 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC |
| 39 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-5/9] |
| 40 | i) 2.5sqmm |
| 41 | ii) 4 sqmm |
| 42 | iii) 6 sqmm |
| 43 | iv)10 sqmm |
| 44 | v)16 sqmm |
| 45 | vi)1.5 sqmm |
| 46 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Make: Legrand: Myrius/Arterior/ L&T/ABB as approved by E.I.C), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/5(a)] |
| 47 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Make: Legrand: Myrius/Arterior/ L&T/ABB as approved by E.I.C) & necy. Connections. [E-17/5(b)] |
| 48 | Supply & Fixing 240 V, 25 A, Modular type starter (Make: Legrand: Myrius/Arterior/ L&T/ABB as approved by E.I.C) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-19/17] |
| 49 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Make: Legrand/Anchor/Havells as approved by E.I.C) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.[E-7/26] |
| 50 | Supply & Fixing 240 V 6 A Piano key type switch (Make: Legrand/Anchor/Havells as approved by E.I.C) on existing sheet metal switch board having bakelite/perspex top cover by screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required [E-5/14(a)] |
| 51 | Supply & Fixing 240 V, 6A plug socket (Make: Legrand/Anchor/Havells as approved by E.I.C), without switch & plug top, on existing sheet metal switch board with bakelite/perspex top cover by screws after making housing for plug by cutting bakelite/perspex top cover and making necy. connections with PVC wire and earth continuity wire etc.[E-5/15(a)] |
| 52 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make- Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch(Make: Anchor/Havells as approved by E.I.C) fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish.[E-14/2] |
| 53 | Average run 8 mtr |
| 54 | Average run 9 mtr |
| 55 | Average run 10 mtr |
| 56 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make-Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch (Make: Anchor/Havells as approved by E.I.C) fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. |
| 57 | On Board |
| 58 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make-Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch (Make: Anchor/Havells as approved by E.I.C) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] [E-15/5] |
| 59 | Average run 8 mtr |
| 60 | Average run 9 mtr |
| 61 | Average run 10 mtr |
| 62 | Average run 11 mtr |
| 63 | Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles. [E-3/6] |
| 64 | 19 mm dia 3 mm thick polythene pipe without earth continuity wire |
| 65 | Cutting Channel of size (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles.[E-3/7] |
| 66 | 25 mm dia 3 mm thick polythene pipe without earth continuity wire. |
| 67 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.[ F-2/1(b)] |
| 68 | Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core [F-1/3(b)] |
| 69 | Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [F-1/2(b)] |
| 70 | Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [F-1/2(d)] |
| 71 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [F-1/2(e)] |
| 72 | Supplying and fixing compression type gland and finishing the ends of following XLPE / PVC armoured AL. cable (2/4 / 3.5)Core as per GS. [F-4 /7c] |
| 73 | 4 Core 95 Sq. mm [F-4/7(c)] |
| 74 | 4 Core 50 Sq. mm [[F-4/7(c)] |
| 75 | 4 Core 6 Sq. mm [[F-4/7(c)] |
| 76 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.[F-5/8(b)] |
| 77 | 4 Core 95 Sq. mm |
| 78 | 4 Core 50 Sq. mm |
| 79 | 4 Core 6 Sq. mm |
| 80 | Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable ben S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.[C-3/18] |
| 81 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required [C-3/20(b)] |
| 82 | Supplying and Fixing GI water proof looping cable box havinghinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. where necy. incl. painting.(a) 200 x 150 x 100mm [I-2/16] |
| 83 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials. [F-6/11] |
| 84 | 65 mm dia |
| 85 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment (Make- Legrand /L&T/Siemens/ ABB as approved by E.I.C)- (2way) [D-9/11] |
| 86 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:[G-1/2] |
| 87 | By ISI-Medium GI pipe |
| 88 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe. [G-2/3(a)] |
| 89 | Excavation of soil for installation of Earth Electrode and filling & ramming (For Soft Soil) as per GS.[G-1/1] |
| 90 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.[G-2/4(b)] |
| 91 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode. [G-2/3(b)] |
| 92 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc..[G-3/5(c)] |
| 93 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [C-2/17] |
| 94 | Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. as required. [C-2/14(d)] |
| 95 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.[C-2/16] |
| 96 | Engraving the deptt. number with 10 mm lettering on the body of fan upto 10 letters incl. hifen, stroke or stop. [C-3/24(a)] |
| 97 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.[C-3/21(a)] |
| 98 | Painting upto 10 letters of the engraved number with approved black /red paint as required.[C-3/26a] |
| 99 | S&F MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting.[D-14/29] |
| 100 | Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) [D-14/30] |
| 101 | Supply & Fixing Socket type fan regulator (Step type) (Anchor/Havells as approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc. [E-6/18(a)] |
| 102 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust [C-4/28] |
| 103 | 30 cm (12\\") |
| 104 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) [D-14/32(a)] |
| 105 | For Al 30 cm Exhaust fan (12\\") |
| 106 | Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make. Polycab/Gloster/Finolex/KEI/Havells/RR Cable as approved by E.I.C] |
| 107 | 4 Core 95 Al cable [ Sub Station to LT Panel] |
| 108 | 4 Core 50 Al cable [ LT Panel to VTPNDB] |
| 109 | 4 Core 6 Al cable [ LT panel to 3 phase Timer & timer to loop box] |
| 110 | Supply of 1.1 KV PVC insulated 3 core 1.5 sqmmRound Sheathed Cu cable ( Make Polycab/Gloster/Finolex/KEI/Havells/RR Cable/MESCAB) [ from loop box to fittings] |
| 111 | Supply of 4'ft LED Twin batten/Metal frame fittings incl. 2nos. 18W Polycarbonate/Aluminium LED tube having luminoius efficacy of 100lm/W & in built SPD protection [Make- Philips/Crompton/ Wipro or manufacturer with own NABL accredited Lab with valid Test certificate as approved by E.I.C] |
| 112 | Supply of 4'ft LED single batten/Metal frame fittings incl. 1no 18W Polycarbonate/Aluminium LED tube having luminoius efficacy of 100lm/W & in built SPD protection [Make- Philips/Crompton/ Wipro or manufacturer with own NABL accredited Lab with valid Test certificate as approved by E.I.C] |
| 113 | Supply of 1200mm Normal Speed Ceiling Fan of 65W, 400 RPM, 200 Cmm BEE star rated with complete accessories like blades, canopy, fork, rubber bush etc with all accessories without regulator having Double Ball Bearing & Low Noise.[Make: Orient/ Crompton/Polar BEE star rated as per choice of EIC] |
| 114 | Supply of 300 mm 1400 RPM ( heavy Duty) full metal body Exhaust Fan with ISI marked as per IS 3103(1975) with all necessary accessories. [Make: EPC/ Crompton/ Orient or as per approved by EIC] |
| 115 | Supply of Street light fiiting with light Wattage: Max. 110W Lumen output: -- Min. 120 lm/W,die cast aluminium housing, Driver rating should be higher than the bfittings rating & bult in 10 KV SPD. (Make: Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate.) |
| 116 | Supply of Floodlight fiiting with light Wattage: Max. 250W Lumen output: -- Min. 120 lm/W,die cast aluminium housing, Driver rating should be higher than the bfittings rating & bult in 10 KV SPD. (Make: Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate.) |
| 117 | Supply and fixing of LED post top 40 Watt for 360° indirect light fittings Pure polyester UV resistant powder coated die cast aluminium housing with PMMA clear diffuser for uniform illumination. and THD<10%, bult in 2.5KV SPD, IP-65 protection (for gate light) (Make Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate.) The scope of work also includes the S & F of 400 mm long 50mm dia GI pipe, reducer, nuts, etc on top of the gate pillar after making hole & mending good the damages with cement morter mixture as per direction of EIC. |
| 118 | Disconnection & dismantling existing old Electrical installation, Switch-board, wiring, SFU, Electrical fitting/fixtures etc with owns tools & takles incl. mending good damages as per GS and clearing/removing from the site. |
| 119 | S&F Timer Control Unit for compound lighting assembled with following accessories: - i) 12-way double-door(Metal door) SPNDB Box (L & T cat no.-DESPN012DDS or equivalent model of Legrand/ Siemens as approved by E.I.C)-1 no. ii) 25A FP 30mA RCBO (Make: L&T Cat no.- AUF3C403203 or equivalent model of Legrand /Siemens ) - 1 noiii) 22A 3-pole power contactor (L&T: Type- MNX22 ; Cat no.-CS94980 or equivalent model of Siemens/ABB)-1no. iv) Digital 24 hour time switch (Make-L&T Cat no.-67DDT0 or equivalent model of GIC/Siemens) -1no. v) Melamine terminal block-4 nos. vi) LED indicating lamp RYB (L&T: SIL R 240V)-3 no. vii) ON/OFF Push(L&T: emn R/G fd-1) = 2 nos All control circuit wiring would be made by 1x2.5 sqmm FRLS stranded Cu wire(Brand approved by E.I.C) and the I/C & O/G circuit with 4x4sqmm copper wire of suitable length maintaining colour code incl taping, socketing to complete the work. |
| 120 | Dismantling of flexible pavements and disposal of dismantled materials upto a lead of 100 m, stacking serviceable and unserviceable materials separately as per Technical Specifications Clause 202 for Rural Roads of MORD By Manual Means.a) Bituminous Courses.[ PWD Road S.O.R 2018 Item No- 2.14 page 235] |
| 121 | Ordinary Cement concrete (mix 1:1.5:3) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement if any, in ground floor as per relevant IS codes. |
| 122 | (i) Pakur Variety [PWD Civil S.O.R 2017 Building Page 26 Item No- 10] |
| 123 | Single Brick Flat Soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand [PWD Civil S.O.R 2017 Building Page 14 Item No- 1] |
| 124 | Submission of details SLD ( both hard & soft copy ) by AUTO CAD of the above job with indicating all the items of Power Distribution system with position of existing and also new cubical panel, feeder piller box, HT gear, Main LT panel , Sub-Station related wiring, VTPN's, PBDBs, LBDBs, Power Plugs, Lights, Fans, Switch Boards etc. Moreover marking all the main switches, DBs including the MCBs by Paint.Testing of whole distribution system( panel to switch board, LC, Earthing, cable etc) with instruments(Meggar,Earth tester, Thermal scanner, etc) and in addition to earthing testing of existing & new EI & Provision of LC testing arrangement, test certificate and test report for earthing arrangement, down conductor, horizontal conductor to ensure proper grounding etc. and also autocad drawing of total installation incl. compound lighting system as per direction of EIC. with detail data sheet regarding the whole installed electrical system to complete the installation as per direction of EIC. |
| 125 | Add. G.S.T.@ 18% on total of item |
| 126 | Add. LWC.@ 1% on total of item Please Enable Macros to View BoQ information |