| 1 | SITC of Factory made/ CHESCOM approved Tamper Proof Meter box confirming to CESC design and requirements for OUTDOOR metering purpose, made of suitable gauge MS sheet of size Minimum 800mm X 800mm X 250mm (HxBxD) having the following provisions, Top portion Sloped roof (double sheet), earthing terminal, with all hinged doors, provision of holes for cable entry at bottom, rubber gasket for doors with necessary fastners, painted with CESC approved colour paint, sign writing, danger notice display on Meter Box with vinyle type stickering, provision for an external double door with gaskets (to avoid rain water entry)is to be provisioned as per CESC specifications etc as reqd.i/c excavation of soil upto 2feet depth of required length & breadth to accommodate the MS stand legs and providing cement concrete to the legs of the stand for firm support complete etc as reqd. (Note: The Meter box shall Confirm to CESC Approved CESC design and requirements) | SITC of Factory made/ CHESCOM approved Tamper Proof Meter box confirming to CESC design and requirements for OUTDOOR metering purpose, made of suitable gauge MS sheet of size Minimum 800mm X 800mm X 250mm (HxBxD) having the following provisions, Top portion Sloped roof (double sheet), earthing terminal, with all hinged doors, provision of holes for cable entry at bottom, rubber gasket for doors with necessary fastners, painted with CESC approved colour paint, sign writing, danger notice display on Meter Box with vinyle type stickering, provision for an external double door with gaskets (to avoid rain water entry)is to be provisioned as per CESC specifications etc as reqd.i/c excavation of soil upto 2feet depth of required length & breadth to accommodate the MS stand legs and providing cement concrete to the legs of the stand for firm support complete etc as reqd. (Note: The Meter box shall Confirm to CESC Approved CESC design and requirements) |
| 2 | Supplying & Fixing of 4 Nos 50/5 Amps, 3.75VA, Class 0.5 or 0.5S accuracy Ring Type LT current transformers suitable for operation on single Phase, 50Hz AC supply in the existing TP meter box i/c providing CT test certificates, making wiring with 2.5Sqmm pvc insulated copper wires, ferrules, suitable size round lugs, providing insulating supports to the CTs inside the busbar chamber complete etc as reqd. (Make: Kalpa or as per the CESC requirements, the CTs have to be got tested at CESC O/o AEE, MT section, Jyothinagar, Mysore) | Supplying & Fixing of 4 Nos 50/5 Amps, 3.75VA, Class 0.5 or 0.5S accuracy Ring Type LT current transformers suitable for operation on single Phase, 50Hz AC supply in the existing TP meter box i/c providing CT test certificates, making wiring with 2.5Sqmm pvc insulated copper wires, ferrules, suitable size round lugs, providing insulating supports to the CTs inside the busbar chamber complete etc as reqd. (Make: Kalpa or as per the CESC requirements, the CTs have to be got tested at CESC O/o AEE, MT section, Jyothinagar, Mysore) |
| 3 | Supplying and Fixing of 3 Phase 4 Wire 50 Hz CT Operated Digital Energy meter suitable for measuring sanctioned load as per the CHESCOM specification, approved make & model, suitable to read Energy parameters i/c testing of meter as per CHESCOM requirements complete as reqd. (The meter shall be as per the CESC requirements, supplier has to produce all necessary documents to CESC for servicing the installation) | Supplying and Fixing of 3 Phase 4 Wire 50 Hz CT Operated Digital Energy meter suitable for measuring sanctioned load as per the CHESCOM specification, approved make & model, suitable to read Energy parameters i/c testing of meter as per CHESCOM requirements complete as reqd. (The meter shall be as per the CESC requirements, supplier has to produce all necessary documents to CESC for servicing the installation) |
| 4 | Taking LC from CESC, removal of Aerial fuses on CESC pole, disconnection, rearrangement of power cables from existing metering arrangement, excavation of soil approx up to 3 to 5 Mtrs for rerouting and laying the cable on surface / recess and connecting it to the new TP meter board/panel switch gears, making terminations etc as reqd. | Taking LC from CESC, removal of Aerial fuses on CESC pole, disconnection, rearrangement of power cables from existing metering arrangement, excavation of soil approx up to 3 to 5 Mtrs for rerouting and laying the cable on surface / recess and connecting it to the new TP meter board/panel switch gears, making terminations etc as reqd. |
| 5 | Laying of one number PVC Insulated PVC sheathed aluminium conductor single / three phase 1.1KV class 50Hz AC armoured UG cable of following size as per dept specification. | Laying of one number PVC Insulated PVC sheathed aluminium conductor single / three phase 1.1KV class 50Hz AC armoured UG cable of following size as per dept specification. |
| 6 | Supply & Making end termination suitable for following size AL conductor cable with brass compression gland etc., as reqd. | Supply & Making end termination suitable for following size AL conductor cable with brass compression gland etc., as reqd. |
| 7 | Laying of Existing rigid HDPE/PLB/PVC/UPVC pipe with necessary acessories for the protection of armoured UG cable in the following ways as per dept specification etc as reqd. (Note: Pipe will be issued from Department Stores) | Laying of Existing rigid HDPE/PLB/PVC/UPVC pipe with necessary acessories for the protection of armoured UG cable in the following ways as per dept specification etc as reqd. (Note: Pipe will be issued from Department Stores) |
| 8 | S&F of Aerial fuse Cutouts Porcelain type 100Ax3Nos with 63A Nuetral link, fixed on a suitable size hylum sheet board ,with suitable thickness , mounting all above on the EB Pole for Service Cable terminations i/c connections, testing complete as reqd. (On CESC Pole) | S&F of Aerial fuse Cutouts Porcelain type 100Ax3Nos with 63A Nuetral link, fixed on a suitable size hylum sheet board ,with suitable thickness , mounting all above on the EB Pole for Service Cable terminations i/c connections, testing complete as reqd. (On CESC Pole) |
| 9 | Supplying & Providing electrical grade Alkathene tubes/ PVC sleeves (LT Insulation grade ONLY) 15/18 mm dia for jump cables on the pole for protection as reqd. | Supplying & Providing electrical grade Alkathene tubes/ PVC sleeves (LT Insulation grade ONLY) 15/18 mm dia for jump cables on the pole for protection as reqd. |
| 10 | Supply & fixing Cable Pot head of Cast Iron suitable for the following size Power Cable i/c filling bitumen compound, to avoid water entry in to the Cable complete etc as reqd. | Supply & fixing Cable Pot head of Cast Iron suitable for the following size Power Cable i/c filling bitumen compound, to avoid water entry in to the Cable complete etc as reqd. |
| 11 | Transportation of Existing PLB pipe of length approx 25 to 30 Mtrs or as required at site from Belawadi BSNL Stores to Roopanagar BTS by hiring a suitable transport vehicle approx 10 Kms to 12 Kms to & from i/c loading and unloading etc as reqd. | Transportation of Existing PLB pipe of length approx 25 to 30 Mtrs or as required at site from Belawadi BSNL Stores to Roopanagar BTS by hiring a suitable transport vehicle approx 10 Kms to 12 Kms to & from i/c loading and unloading etc as reqd. |
| 12 | Supplying and fixing 63 Amps rating TPN Load limiter MCB, 240/415 volts, 10kA, 'C' Curve suitable for inductive load in the existing Meter Box/ DB complete with connections, testing and commissioning etc. as required. (Standard/ Havells OR SS) | Supplying and fixing 63 Amps rating TPN Load limiter MCB, 240/415 volts, 10kA, 'C' Curve suitable for inductive load in the existing Meter Box/ DB complete with connections, testing and commissioning etc. as required. (Standard/ Havells OR SS) |
| 13 | Supply and Laying of following size FRLS PVC insulated Sheathed Multistrand Copper Conductor wire in existing panel/ meterbox for interconnection wiring etc as reqd. (Make: Polycab/ Havells OR SS) | Supply and Laying of following size FRLS PVC insulated Sheathed Multistrand Copper Conductor wire in existing panel/ meterbox for interconnection wiring etc as reqd. (Make: Polycab/ Havells OR SS) |
| 14 | Supplying & Making MS frame arrangement with MS angle iron/ Flat for Out Door Meter Board supporting stand/ Rain proof shelter i/c cutting, welding, fabricating i/c excavation of soil upto 2feet depth of required length & breadth to accommodate the MS stand legs and providing cement concrete to the legs of the stand for firm support complete etc as reqd. | Supplying & Making MS frame arrangement with MS angle iron/ Flat for Out Door Meter Board supporting stand/ Rain proof shelter i/c cutting, welding, fabricating i/c excavation of soil upto 2feet depth of required length & breadth to accommodate the MS stand legs and providing cement concrete to the legs of the stand for firm support complete etc as reqd. |
| 15 | Supplying and Fixing of colour coated corrugated GI sheet of standard gauge factory made with curved inclination at either ends fixing above meter board in sloped roof i/c providing overlap capping on adjoining sheets with similar sheet material for protection against direct rain water fall and suitable fastners etc as reqd. (Make: JSW/ TATA or Similar Superior Make) | Supplying and Fixing of colour coated corrugated GI sheet of standard gauge factory made with curved inclination at either ends fixing above meter board in sloped roof i/c providing overlap capping on adjoining sheets with similar sheet material for protection against direct rain water fall and suitable fastners etc as reqd. (Make: JSW/ TATA or Similar Superior Make) |