| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER (NAVAL WORKS) MUMBAI Name of Work : CERTAIN REPAIR OF ELECTRIC SUPPLY DISTRIBUTION NETWORK OF NOFRA AND WNC(O) MESS AREA UNDER GE(NW) NOFRA. Contract No: 8690/CWE (NW) MUMBAI/E8 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Item Code / Make Quantity Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Material and labour for repairs / overhauling / servicing of existing LT electrical panels / meter panels (Indoor type) by obtaining shutdown from the competent authority and carrying out the following operations complete all as specified and directed by the Engineer-in-Charge:(i) Cleaning inside the panel including all incoming and outgoing feeders such as MCCB, SFU, changeover switches, contactors, ACB etc. thoroughly using vacuum cleaner.(ii) Checking all incoming and outgoing feeder connections and tightening loose connections including replacement of defective GI nuts, bolts and washers as required.(iii) Replacing burnt or damaged colour coded PVC sleeves of main and feeder bus bars with suitable size PVC heat shrinkable sleeves – 01 Job. |
| 3 | Material and labour for repairs / overhauling / servicing of existing LT Feeder Pillar Box (Outdoor type) connected to transformer by obtaining shutdown from the competent authority and carrying out the following operations complete all as specified and directed by the Engineer-in-Charge:(i) Cleaning inside and outside of the feeder pillar box including all incoming and outgoing feeders such as MCCB, SFU, changeover switches, contactors, ACB etc. thoroughly using vacuum cleaner.(ii) Checking all incoming and outgoing feeder connections and tightening loose connections including replacement of defective GI nuts, bolts and washers.(iii) Replacing damaged cable glands, thimbles and lugs as per size of existing cables and applying petroleum jelly on electrical contacts. |
| 4 | (iv) Replacing burnt or damaged colour coded PVC sleeves of main and feeder bus bars with suitable size PVC heat shrinkable sleeves – 01 Job.(v) Removing and replacing defective voltmeters, ammeters, indicating lamps and HRC fuses.(vi) Replacing burnt or damaged control wiring of ammeter, voltmeter, indicating lamps and CT circuits using 1.5/2.5 Sqmm single core copper conductor cable, 1100 Volt grade – 01 Job.(vii) Replacing burnt or damaged feeder bus bars with new bus bars of suitable size made of copper or aluminium – 01 Job.(viii) Replacing burnt or damaged feeder bus bar insulators with suitable size new insulators – 01 Job.(ix) Repairing damaged or hanging doors of feeder pillar box by welding or fixing new hinges to make the panel fully serviceable.(x) Surface preparation and spray painting / powder coating of the feeder pillar box after servicing.(xi) Testing and commissioning of the feeder pillar box after completion of servicing.(xii) Note: Replacement items mentioned at serial No. (v), (vii) and (viii) shall be measured and paid separately under relevant BOQ items. |
| 5 | Supply only Aluminium Bus Bar strips, of any size, for extention of MCCB terminals for cable terminations, inside the cable alley of LT panel board, duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size complete all as specified and as directed . Note :- (a) Size of the strip shall be determined depending upon the current carrying capacity of the individual outgoing MCCBs.(b) Overall length of the strip shall be measured and paid after necessary conversion into weight.(c) Cost of drilling / bending / Grinding of the strips at site as required shall be included in the unit rate quoted. No extra payment shall be admissible on that account.(d) Bolts, Nuts etc shall be measured and paid separately under respective items. |
| 6 | Supply only copper bus bar strips of suitable size for cable terminations inside the cable alley of LT panel board, to be mounted on existing FRP/DMC bus bar support insulators, including necessary cutting, drilling, bending and shaping to obtain required dimensions, complete all as specified and as directed by the Engineer-in-Charge.(a) Size of the bus bar strip shall be selected based on the current carrying capacity of the individual outgoing MCCBs.(b) Measurement shall be made based on the actual length of bus bar installed and converted into weight (kg) for payment.(c) The quoted rate shall be deemed to include cutting, drilling, bending, grinding and shaping of bus bars at site. No extra payment shall be admissible on this account.(d) Bolts, nuts, washers and other fixing hardware shall be measured and paid separately under relevant BOQ items. |
| 7 | Supply and fixing of FRP / DMC bus bar support insulator (Bridge type) of suitable size for supporting extended aluminium / copper bus bars for cable terminations inside LT panel board, fixed to the panel body including galvanized steel bolts, nuts, washers and necessary drilling in the panel body, complete all as specified and as directed by the Engineer-in-Charge. |
| 8 | Dismantling and repair / overhauling of Air Circuit Breaker (ACB), 3 pole / 4 pole, rating 630 Amps to 1200 Amps, 415 Volts, draw-out or fixed type, including the following operations complete all as specified and as directed by the Engineer-in-Charge:(i) Dismantling the ACB carefully from its installed position.(ii) Servicing and overhauling of spring charging mechanism, operating mechanism, coils and auxiliary switches.(iii) Checking, servicing and setting of overload coil, no-volt coil and tripping coil.(iv) Cleaning of male and female contacts and application of dry graphite conductive compound on contact surfaces.(v) Application of suitable multi-purpose grease on mechanical moving parts.(vi) Checking of internal electrical wiring system and tightening of connections.(vii) Re-assembling all components in correct position and refixing the ACB in the panel.(viii) Testing of ACB for proper operation and functional performance after completion of servicing.Complete all as specified and directed by the Engineer-in-Charge. |
| 9 | Supply only digital LT voltmeter with selector switch, panel mounting type, size 96 mm × 96 mm, suitable for 415 Volt LT system, measuring range 0–500 Volts, complete all as specified and as directed by the Engineer-in-Charge. |
| 10 | Supply only digital LT ammeter with selector switch, panel mounting type, size 96 mm × 96 mm, suitable for operation with CT secondary 5 Amp, measuring range 0–1000 Amps, programmable type, suitable for 415 V, 50 Hz LT system, complete all as specified and as directed by the Engineer-in-Charge. |
| 11 | Supply only LED indicating lamp complete with holder, panel mounting type, suitable for 230 Volts AC supply, available in Red, Yellow, Blue and Green colours for indication of incoming power supply in LT panels, complete all as specified and as directed by the Engineer-in-Charge. |
| 12 | Taking down unserviceable MCCB and Supply and fixing of MCCB, 4 pole, 400 Amps, breaking capacity 36 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge.. |
| 13 | Taking down unserviceable MCCB and Supply and fixing of MCCB, 4 pole, 320 Amps, breaking capacity 25 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge.. |
| 14 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 pole, 250 Amps, breaking capacity 25 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 15 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 pole, 200 Amps, breaking capacity 25 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 16 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 pole, 160 Amps, breaking capacity 25 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 17 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 Pole, 125 Amps, breaking capacity 25 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 18 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 Pole, 100 Amps, breaking capacity 16 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 19 | Taking down unserviceable MCCB and supply and fixing of MCCB, 4 Pole, 63 Amps, breaking capacity 16 kA, thermal magnetic adjustable trip type, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge.. |
| 20 | Taking down unserviceable Change Over Switch and supply and fixing of Change Over Switch, 4 Pole, 400 Amps, On-Load type, open execution, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 21 | Taking down unserviceable Change Over Switch and supply and fixing of Change Over Switch, 4 Pole, 250 Amps, On-Load type, open execution, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 22 | Taking down unserviceable Change Over Switch and supply and fixing of Change Over Switch, 4 Pole, 160 Amps, On-Load type, open execution, suitable for 415 Volts, 50 Hz AC LT system, including necessary additions / alterations in the existing LT panel, connection of incoming and outgoing cables/bus bars, tightening of terminals, testing and commissioning, complete all as specified and as directed by the Engineer-in-Charge. |
| 23 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 300 Sqmm to 240 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 24 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 185 Sqmm to 150 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 25 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 120 Sqmm to 95 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 26 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 70 Sqmm to 50 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 27 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 35 Sqmm to 25 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 28 | Taking down unserviceable cable lugs and supply and fixing of aluminium cable lugs suitable for 16 Sqmm to 10 Sqmm cable, including proper crimping, connection to bus bars / MCCB terminals and insulation with PVC insulation tape, complete all as specified and as directed by the Engineer-in-Charge. |
| 29 | Taking down unserviceable Current Transformer (CT) and supply only Current Transformer suitable for 415 Volt LT system, ratio 400/5 Amps, 15 VA burden, accuracy class 1, suitable for metering application in existing LT panel, complete all as specified and as directed by the Engineer-in-Charge. |
| 30 | Taking down unserviceable Current Transformer (CT) and supply only Current Transformer suitable for 415 Volt LT system, ratio 250/5 Amps, 15 VA burden, accuracy class 1, suitable for metering application in existing LT panel, complete all as specified and as directed by the Engineer-in-Charge. |
| 31 | Taking down unserviceable Current Transformer (CT) and supply only Current Transformer suitable for 415 Volt LT system, ratio 200/5 Amps, 15 VA burden, accuracy class 1, suitable for metering application in existing LT panel, complete all as specified and as directed by the Engineer-in-Charge. |
| 32 | Supply only following spare parts suitable for Air Circuit Breaker (ACB), 415 Volts, rating 630 Amps to 1200 Amps, indoor type, suitable, complete all as specified and as directed by the Engineer-in-Charge. |
| 33 | Shunt Trip Device/Electronic trip relay |
| 34 | Closing coil assembly |
| 35 | Mismatch Prevention Device |
| 36 | Moving contacts assembly |
| 37 | Fixed Contact assembly |
| 38 | Auxialary Switch |
| 39 | Arc chute with hardware |
| 40 | Material and labour for fault locating in LT underground cables of any size and length using cable fault locating equipment such as TDR / Thumper method, including identification of fault point, excavation as required for testing, and marking of fault location, complete all as specified and as directed by the Engineer-in-Charge. |
| 41 | Material labour for LT Cable Jointing work by Cutting the faulty cable and making new STRAIGHT THROUGH JOINT for 1100V grade cable complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 16 to 25 sq mm and all as directed by Engineer-In-Charge. |
| 42 | Material labour for LT Cable Jointing work by Cutting the faulty cable and making new STRAIGHT THROUGH JOINT for 1100V grade cable complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 35 to 50 sq mm and all as directed by Engineer-In-Charge. |
| 43 | Material labour for LT Cable Jointing work by Cutting the faulty cable and making new STRAIGHT THROUGH JOINT for 1100V grade cable complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 70 to 185 sq mm and all as directed by Engineer-In-Charge. |
| 44 | Material labour for LT Cable Jointing work by Cutting the faulty cable and making new STRAIGHT THROUGH JOINT for 1100V grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 240 to 400 sq mm and all as directed by Engineer-In-Charge. |
| 45 | Material and Labour for Attending Faults/Trippings and rectifying /repairing the faults in LT Panels Boards/FPB/ MCCB's/ACB's /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut bolts and all as specified and directed by Engineer-In-Charge. Note : Damaged/Burnt MCCB/ACB'S/Changeover switc/Lugs.will be measured and paid separately) |
| 46 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 400Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 47 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 300Sqmm 3.5 core and all as directed by Engineer-In-Charge |
| 48 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 240Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 49 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 185Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 50 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 150Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 51 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 120Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 52 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 95Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 53 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 70Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 54 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 50Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 55 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 35Sqmm 3.5 core and all as directed by Engineer-In-Charge. |
| 56 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 25Sqmm 3..5core and all as directed by Engineer-In-Charge. |
| 57 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 16Sqmm 4core and all as directed by Engineer-In-Charge. |
| 58 | Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 10Sqmm 4core and all as directed by Engineer-In-Charge. |
| 59 | Taking down and removing existing XLPE insulated LT cable of any size, including disconnection from both ends, careful removal from trench / duct / panel as applicable, and stacking at site or handing over to the Engineer-in-Charge as directed, complete all as specified and directed by the Engineer-in-Charge. |
| 60 | Material and labour for providing chequered plate, 5 mm thick, of required size as per site conditions, including cutting, drilling and shaping to required dimensions and applying one coat of red oxide primer and two coats of synthetic enamel paint, complete all as specified and as directed by the Engineer-in-Charge. |
| 61 | Supply and fixing of electrical insulating rubber mat, conforming to IS 15652:2006 (superseding IS:5424-1969), BIS approved and tested by CPRI / NTH / ERDA, Class ‘C’, dielectric strength 65 kV, sheet thickness not less than 3.0 mm, suitable for use in LT panels / power houses, including cutting to required size and fixing / pasting with approved adhesive compound, complete all as specified and directed by the Engineer-in-Charge. |
| 62 | Material and labour for attending faults / tripping and rectification in DG Sets and AMF Panels, including checking and rectification of control wiring, connections, terminals, contactors, relays, and replacement of minor consumables such as PVC insulation tape, nuts, bolts and washers, complete all as specified and as directed by the Engineer-in-Charge.Note:(i) Spare parts such as contactors, relays, MCCB, ACB, fuses, etc. shall be measured and paid separately under relevant BOQ items.(ii) Fault shall be attended and power supply restored within 4 hours from the time of reporting. |
| 63 | Supply and fixing of Air Circuit Breaker (ACB), 630 Amps, Four Pole, draw-out type, single frame, manual operated, suitable for 415 Volts, 50 Hz LT system, with breaking capacity Icu = Ics = Icw (1 sec) = 50 kA, complete with advanced self-powered electronic protection unit (MP2 / MP4 type), LCD display with current metering, minimum 10 trip history records and 10 alarms, logical selectivity, inbuilt temperature protection, complete with all mounting accessories, connections, testing and commissioning, complete all as specified and directed by the Engineer-in-Charge. |
| 64 | Supply, installation, testing and commissioning of LT panel, CPRI approved, cubicle outdoor type, suitable for 415 V, 3 phase, 50 Hz system, fabricated from 3.15 mm thick CRCA sheet, weather and vermin proof construction, powder coated finish, mounted on 40×40×5 mm MS angle iron frame grouted on PCC foundation, complete with front hinged door with locking arrangement, suitable cable entry from top and bottom, with individual compartments for breakers, complete with bus bars, control wiring, accessories and connections, including disconnecting existing cables and reconnecting in the new panel with suitable lugs/thimbles, shifting of existing LT panel if required, making good disturbed surfaces and all civil works necessary for proper installation, complete all as specified and directed by the Engineer-in-Charge.The panel shall comprise the following components:(a) MCCB 250 Amps, 25 kA, 4 Pole (Incoming) – 01 No(b) MCCB 160 Amps, 25 kA, 4 Pole (Outgoing) – 02 Nos(c) MCCB 100 Amps, 16 kA, 4 Pole (Outgoing) – 02 Nos(d) MCB DP, 40 Amps (Outgoing) – 03 Nos(e) Control panel wiring with 2.5 sq mm multi-stranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and selector switches, complete with: |
| 65 | • Current Transformers (CTs) –250/5A – 01 No160/5A – 02 Nos100/5A – 02 Nos• Voltmeter flush mounting type 96×96 mm – 01 No• Ammeter digital CT operated 96×96 mm flush mounting type – 07 Nos• Indication lamps for 3 phase and control fuses – 03 Nos(f) Copper bus bars rated for 400 Amps for phase and 250 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(g) Internal power wiring between bus bars and MCCBs using single core PVC insulated multistranded copper conductor cable, 1100 V grade, of suitable size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 66 | \\"Supply, installation, testing and commissioning of LT Feeder Pillar, CPRI approved, cubicle outdoor type suitable for 415 V, 3 phase, 50 Hz system, fabricated from 3.15 mm thick CRCA sheet, weather and vermin proof construction with powder coated finish, mounted on MS angle iron frame and grouted on PCC foundation, with front hinged door and locking arrangement, suitable for top and bottom cable entry, with individual compartments for breakers and controls.The work shall include disconnecting existing cable connections, fixing and connecting cables in the new feeder pillar with suitable thimbles/lugs, necessary civil works including PCC foundation and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The feeder pillar shall comprise the following components: (a) On-Load Changeover Switch, 4 Pole, 400 Amps – 01 No(b) MCCB, 4 Pole, 400 Amps, breaking capacity 36 kA (Incoming) – 02 Nos(c) MCCB, 4 Pole, 250 Amps, breaking capacity 25 kA (Outgoing) – 02 Nos(d) MCCB, 4 Pole, 200 Amps, breaking capacity 25 kA (Outgoing) – 01 No(e) MCCB, 4 Pole, 160 Amps, breaking capacity 25 kA (Outgoing) – 02 Nos(f) MCCB, 4 Pole, 63 Amps, breaking capacity 16 kA (Outgoing) – 02 Nos(g) MCB, 4 Pole, 63 Amps (Outgoing) – 04 Nos |
| 67 | (h) Control panel wiring with 2.5 sq mm multistranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and selector switches complete with:• CTs:400/5A – 02 Nos250/5A – 02 Nos200/5A – 01 No160/5A – 02 Nos• Voltmeter 96 × 96 mm flush mounting type – 01 No• Ammeter digital CT operated 96 × 96 mm flush mounting type – 10 Nos• Indication lamps for three phases and control fuses – 03 Nos(i) Copper bus bars rated 800 Amps for phase and 600 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(j) Internal power wiring between bus bars and MCCBs using single core PVC insulated multistranded copper conductor cable, 1100 V grade, of appropriate size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 68 | Supply, installation, testing and commissioning of LT Feeder Pillar, CPRI approved, wall mounted indoor type, with single side opening suitable for site conditions, complete with fixing of all breakers and controls suitable for 415 V, 3 phase, 50 Hz system, fabricated from 2 mm thick CRCA sheet, weather and vermin proof, factory fabricated, powder coated finish, with front hinged door and locking arrangement.The feeder pillar shall have individual compartments for MCCBs and 600 Amps rated bus bar, suitable for top and bottom cable entry, including disconnecting existing cable connections and fixing/connecting cables in the new panel with suitable thimbles/lugs, necessary framework and PCC foundation, including taking down of existing LT panel if required, making necessary arrangements for fixing of the panel and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The feeder pillar shall comprise the following:(b) MCCB, 4 Pole, 250 Amps, breaking capacity 36 kA (Incoming) – 01 No(c) MCCB, 4 Pole, 160 Amps, breaking capacity 25 kA (Outgoing) – 02 Nos(d) MCCB, 4 Pole, 125 Amps, breaking capacity 16 kA (Outgoing) – 02 Nos(e) Control panel wiring with 2.5 sq mm multistranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and their selector switches complete with: |
| 69 | • Current Transformers (CTs):400/5A – 02 Nos320/5A – 02 Nos250/5A – 02 Nos200/5A – 02 Nos160/5A – 02 Nos• Voltmeter flush mounting type 96 × 96 mm – 01 No• Ammeter digital CT operated 96 × 96 mm flush mounting type – 10 Nos• Indication lamps for three phase and control fuses – 03 Nos(f) Copper bus bars rated 400 Amps for phase and 250 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(g) Internal power wiring between bus bars and MCCBs using single core PVC insulated multistranded copper conductor cable, 1100 V grade, of suitable size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 70 | Supply, installation, testing and commissioning of LT Panel, CPRI approved, cubicle indoor type, mounted on 40 × 40 × 5 mm MS angle iron frame grouted on PCC foundation, suitable for 415 V, 3 phase, 50 Hz system, fabricated from 2 mm thick CRCA sheet, weather and vermin proof factory fabricated construction with powder coated finish.The panel shall be provided with front hinged door with locking arrangement, suitable for top and bottom cable entry, with individual compartments for MCCBs and 800 Amps rated copper bus bar.The scope shall include disconnecting existing cable connections, fixing and connecting cables in the new panel with suitable thimbles/lugs, shifting of existing LT panel if required, necessary framework and civil works including PCC foundation and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The panel shall comprise the following components:(a) MCCB, 4 Pole, 400 Amps, breaking capacity 36 kA (Incoming) – 02 Nos(b) On-Load LT Changeover Switch, 4 Pole, 400 Amps – 01 No |
| 71 | (c) MCCB, 3 Pole, 250 Amps, breaking capacity 25 kA (Outgoing) – 02 Nos(d) MCCB, 3 Pole, 160 Amps, breaking capacity 25 kA (Outgoing) – 01 No(e) MCCB, 3 Pole, 100 Amps, breaking capacity 16 kA (Outgoing) – 02 Nos(f) Control panel wiring using 2.5 sq mm multistranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and selector switches complete with: • Current Transformers (CTs):630/5 A – 02 Nos400/5 A – 03 Nos320/5 A – 04 Nos250/5 A – 03 Nos200/5 A – 03 Nos160/5 A – 02 Nos• Voltmeter flush mounting type 96 × 96 mm – 01 No• Ammeter digital CT operated 96 × 96 mm flush mounting type – 17 Nos• Indication lamps for three phase and control fuses – 03 Nos(g) Copper bus bars rated 800 Amps for phase and 400 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(h) Internal power wiring between bus bars and MCCBs using single core PVC insulated multistranded copper conductor cable, 1100 V grade, of suitable size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 72 | Supply, installation, testing and commissioning of LT Panel, CPRI approved, cubicle indoor type, mounted on 40 × 40 × 5 mm MS angle iron frame grouted on floor, suitable for 415 V, 3 phase system, fabricated from 2 mm thick CRCA sheet, weather and vermin proof factory fabricated construction with powder coated finish, provided with front hinged door with locking arrangement and suitable for top and bottom cable entry.The panel shall have individual compartments for MCCBs and copper bus bars rated for 1000 Amps, including disconnecting existing cable connections and reconnecting cables in the new panel with suitable thimbles/lugs, necessary framework and PCC foundation, including shifting of existing LT panel if required, fixing of panel and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The panel shall comprise the following components:(a) Air Circuit Breaker (ACB), 4 Pole, 800 Amps, draw-out type, manual operation, breaking capacity Icu = Ics = Icw (1 sec) = 50 kA, with electronic protection unit, LCD display with current metering, trip history, alarm indication, logical selectivity and inbuilt temperature protection – 01 No (Incoming).(b) MCCB, 4 Pole, 630 Amps, 36 kA (Outgoing) – 02 Nos.(c) MCCB, 4 Pole, 400 Amps, 36 kA (Outgoing) – 02 Nos.(d) MCCB, 3 Pole, 250 Amps, 25 kA (Outgoing) – 03 Nos.(e) MCCB, 4 Pole, 160 Amps, 25 kA (Outgoing) – 01 No.(f) MCB, 3 Pole, 63 Amps (Outgoing) – 03 Nos. |
| 73 | (g) Control panel wiring using 2.5 sq mm multi-stranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and selector switches complete with:• Current Transformers (CTs):630/5 A – 02 Nos400/5 A – 02 Nos250/5 A – 03 Nos160/5 A – 01 No• Voltmeter, flush mounting type 96 × 96 mm – 01 No• Ammeter, digital CT operated, flush mounting type 96 × 96 mm – 11 Nos• Indicating lamps for three phase supply and control fuses – 03 Nos.(h) Copper bus bars rated 1000 Amps for phase and 600 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(i) Internal power wiring between bus bars and MCCBs using single core PVC insulated multi-stranded copper conductor cable, 1100 V grade, of suitable size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 74 | Material and labour for earthing with galvanised steel earth plate electrode 600 × 600 × 6 mm thick, buried directly in ground (earth pit not less than 2.5 m below ground level) with the top edge of the plate not less than 1.5 m below normal ground level, connected to 32 × 6 mm galvanised iron strip by means of galvanised iron or steel bolts, nuts, check nuts and washers.The work shall include necessary excavation, providing PCC 1:3:6 (Type D2) for foundation and PCC cover 1:2:4 (Type B1), watering arrangement with GI pipe, funnel and wire mesh (jali), complete all as specified and shown in Electrical Plate No. 3, including connection to the earthing test point and testing of earth resistance on completion, complete all as specified and directed by the Engineer-in-Charge. |
| 75 | Material and labour for earth continuity conductor or main earthing lead, fixed to wall on batten or in recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated position for loop earthing etc., using 32 × 6 mm galvanised iron strip, complete all as specified and directed by the Engineer-in-Charge. |
| 76 | Supply, installation, testing and commissioning of meter cabin panel, mounted on MS angle iron frame and grouted on PCC foundation, cubicle indoor type, suitable for 415 V, 3 phase, 50 Hz system, fabricated from 2 mm thick CRCA sheet, weather and vermin proof factory fabricated construction with powder coated finish.The panel shall be provided with front hinged door with locking arrangement, suitable for top and bottom cable entry, with individual compartments for MCCBs and copper bus bars rated 300 Amps.The work shall include disconnecting existing cable connections and electronic energy meters from the old meter cabin panel and fixing/reconnecting the same in the new panel with suitable lugs/thimbles, providing necessary framework and PCC foundation (1:2:4 mix with 20 mm graded stone aggregate), shifting of existing panel if required, fixing the new panel in position and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The panel shall comprise the following components:(a) MCCB, 4 Pole, 200 Amps, breaking capacity 25 kA – 02 Nos(b) MCB, 63 Amps, 10 kA, C-curve – 12 Nos(c) Sheet metal enclosure, 2-way without bus bar – 12 Nos (c) MCCB, 4 Pole, 320 Amps, breaking capacity 36 kA – 01 No |
| 77 | (d) Copper bus bars rated 400 Amps for R, Y, B phases and neutral, complete with bus bar supports/insulators, nuts and bolts(e) Digital ammeter – 01 No(f) Digital voltmeter – 01 No(g) Phase indication lamps for R, Y and B phases – 03 Nos(h) Provision for mounting of digital electronic energy meters removed from the existing panel including suitable fixing arrangement and vision glass for meter display – 12 Nos(i) Material and labour for wiring using 2 core 10 sq mm multistranded copper conductor cable, 1100 V grade, from bus bar to electronic energy meters including suitable size copper lugs/thimbles and glands(j) Connection of sub-main cable using 2 core 10 sq mm copper conductor cable from outgoing of energy meters, complete all as specified and directed by the Engineer-in-Charge. |
| 78 | Supply, installation, testing and commissioning of LT Panel, CPRI approved, cubicle indoor type, mounted on 40 × 40 × 5 mm MS angle iron frame grouted on PCC foundation, suitable for 415 V, 3 phase, 50 Hz system, fabricated from 2 mm thick CRCA sheet, weather and vermin proof factory fabricated construction with powder coated finish.The panel shall be provided with front hinged door with locking arrangement, suitable for top and bottom cable entry, with individual compartments for MCCBs and copper bus bars rated 800 Amps.The scope shall include disconnecting existing cable connections, fixing and reconnecting cables in the new panel with suitable thimbles/lugs, necessary framework and PCC foundation, shifting of existing LT panel if required, fixing of panel and making good disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge.The panel shall comprise the following components:(a) MCCB, 4 Pole, 400 Amps, breaking capacity 36 kA (Incoming) – 02 Nos(b) On-Load Changeover Switch, 4 Pole, 400 Amps – 01 No(c) MCCB, 4 Pole, 320 Amps, breaking capacity 36 kA – 01 No(d) MCCB, 3 Pole, 250 Amps, breaking capacity 25 kA (Outgoing) – 02 Nos(e) MCCB, 3 Pole, 160 Amps, breaking capacity 25 kA (Outgoing) – 01 No(f) MCCB, 3 Pole, 100 Amps, breaking capacity 16 kA (Outgoing) – 02 Nos |
| 79 | (g) Control panel wiring using 2.5 sq mm multistranded PVC insulated copper conductor cable, including wiring between voltmeter, ammeter and selector switches complete with:• Current Transformers (CTs):630/5 A – 02 Nos400/5 A – 03 Nos320/5 A – 04 Nos250/5 A – 03 Nos200/5 A – 03 Nos160/5 A – 02 Nos• Voltmeter flush mounting type 96 × 96 mm – 01 No• Ammeter digital CT operated 96 × 96 mm flush mounting type – 17 Nos• Indication lamps for three phase supply and control fuses – 03 Nos(h) Copper bus bars rated 800 Amps for phase and 400 Amps for neutral, complete with bus bar supports/insulators, nuts and bolts.(i) Internal power wiring between bus bars and MCCBs using single core PVC insulated multistranded copper conductor cable, 1100 V grade, of suitable size complete with copper lugs.Complete all as specified and directed by the Engineer-in-Charge. |
| 80 | Material and labour for servicing of DG set of capacity 125 kVA, including carrying out routine maintenance, checking of engine and alternator parameters, tightening of electrical connections, cleaning of filters and radiator, checking of battery, lubrication system and fuel system, and testing on completion for satisfactory performance for a period of 2 hours at connected load, complete all as specified and directed by the Engineer-in-Charge.Note: Spare parts, engine oil and coolant shall be measured and paid separately under relevant “Supply Only” items.) |
| 81 | Supply only of engine oil SAE 20W-40 suitable for DG sets of capacity 62.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 82 | Supply only of coolant suitable for DG sets of capacity 62.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 83 | Supply only of distilled water suitable for DG set batteries of capacity 62.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 84 | Supply only of battery acid suitable for DG set batteries of capacity 62.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 85 | Material and labour for repair/overhauling of dynamo of DG set capacity 62.5 kVA, including replacement of carbon brushes, brush holders, springs, commutator servicing, bearing replacement, regulator servicing and associated components, complete all as specified and directed by the Engineer-in-Charge. |
| 86 | Material and labour for repair/overhauling of dynamo of DG set capacity 82.5 kVA to 125 kVA, including replacement of carbon brushes, brush holders, springs, commutator servicing, bearing replacement, regulator servicing and associated components, complete all as specified and directed by the Engineer-in-Charge. |
| 87 | Supply and fixing in replacement battery charger, 24 Volts, suitable for 12 Volt, 180 Ah batteries, float-cum-boost type, complete all as specified and directed by the Engineer-in-Charge. |
| 88 | Material and labour for dismantling and servicing/repairing of radiator assembly of DG set capacity 62.5 kVA, including flushing, testing for water tightness, soldering leakage points, replacement of defective radiator cap and rubber hoses, re-installation and testing of radiator assembly complete all as specified and directed by the Engineer-in-Charge. |
| 89 | Material and labour for dismantling and servicing/repairing of radiator assembly of DG set capacity 82.5 kVA to 125 kVA, including flushing, testing for water tightness, soldering leakage points, replacement of defective radiator cap and rubber hoses, re-installation and testing complete all as specified and directed by the Engineer-in-Charg |
| 90 | Material and labour for servicing of alternator of DG set capacity 62.5 kVA, including cleaning of field and armature windings, varnishing and baking, polishing of slip rings, checking and correction of excitation system, complete all as specified and directed by the Engineer-in-Charge. |
| 91 | Material and labour for servicing of alternator of DG set capacity 82.5 kVA to 125 kVA, including cleaning of field and armature windings, varnishing and baking, polishing of slip rings, checking and correction of excitation system, complete all as specified and directed by the Engineer-in-Charge. |
| 92 | Supply and replacement of Automatic Voltage Regulator (AVR) suitable for DG set, complete all as specified and directed by the Engineer-in-Charge. |
| 93 | (i) For DG Set 125 kVA |
| 94 | (ii) For DG Set 62.5 kVA to 82.5 kVA |
| 95 | Material and labour for cleaning of fuel tank of DG sets of capacity 62.5 kVA to 125 kVA, including decanting of diesel, internal cleaning of tank, painting with one coat of approved synthetic enamel paint after surface preparation, marking of fuel level gauge, fuel tank cap and writing of tank capacity on the tank, complete all as specified and directed by the Engineer-in-Charge. |
| 96 | Material and labour for servicing of self starter (12/24 Volts DC) of DG set including dismantling, replacement of solenoid and field coils, cleaning of commutator strips, replacement of bearings, servicing of Bendix pinion assembly, reassembly, connection and testing, complete all as specified and directed by the Engineer-in-Charge. |
| 97 | Material and labour for calibration of fuel injector of DG set capacity 62.5 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 98 | Material and labour for calibration of fuel injector of DG set capacity 82.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 99 | Supply and fixing of exhaust silencer suitable for diesel engine of capacity 62.5 kVA DG set, complete all as specified and directed by the Engineer-in-Charge. |
| 100 | Supply and fixing of exhaust silencer suitable for diesel engine of capacity 82.5 kVA to 125 kVA DG set, complete all as specified and directed by the Engineer-in-Charge. |
| 101 | Supply and fixing of self starter suitable for DG set of capacity 62.5 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 102 | Supply and fixing of self starter suitable for DG set of capacity 82.5 kVA to 125 kVA, complete all as specified and directed by the Engineer-in-Charge. |
| 103 | Supply and fixing in replacement of starting battery 12 Volts, 180 Ah suitable for DG set starting system, including testing and commissioning complete all as specified and directed by the Engineer-in-Charge. |
| 104 | Supply and fixing in replacement of unserviceable pre-lubrication hydraulic lift pump suitable for 62.5 kVA DG set, including taking down the existing pump, complete all as specified and directed by the Engineer-in-Charge. |
| 105 | Supply and fixing in replacement of unserviceable pre-lubrication hydraulic lift pump suitable for DG set capacity 82.5 kVA to 125 kVA, including taking down the existing pump, complete all as specified and directed by the Engineer-in-Charge. |
| 106 | Material and labour for taking down unserviceable water body of DG set of capacity 62.5 kVA, dismantling fan, fan belt, hoses and accessories, removing the existing unit and replacing with new water body as per sample, complete all as specified and directed by the Engineer-in-Charge. |
| 107 | Material and labour for taking down unserviceable water body of DG set of capacity 82.5 kVA to 125 kVA, dismantling fan, fan belt and hoses, replacing with new water body as per sample, complete all as specified and directed by the Engineer-in-Charge. |
| 108 | Supply only power contactor 80 Amps, 4 Pole with 2NO + 2NC, suitable for 62.5 kVA DG set AMF panel, complete all as specified and directed. |
| 109 | Supply only power contactor 100 Amps, 4 Pole with 2NO + 2NC, suitable for 82.5 kVA DG set AMF panel, complete all as specified and directed. |
| 110 | Supply only power contactor 160 Amps, 4 Pole with 2NO + 2NC, suitable for 125 kVA DG set AMF panel, complete all as specified and directed. |
| 111 | Supply only LED indicating lamps (Red / Green / Yellow / Blue) suitable for 24/230 V AC/DC operation for AMF panel, complete all as specified and directed by the Engineer-in-Charge. |
| 112 | Excavation in trenches not exceeding 1.5 m wide and 1.5 m depth in hard/dense soil for laying of cables / GI pipes including getting out excavated soil, complete all as specified and directed. |
| 113 | Returning, filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thickness, complete all as specified and directed. |
| 114 | Removing surplus soil outside MoD land and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed. |
| 115 | Material and labour for dry clean river sand cushioning for cables in trenches, including spreading, levelling and hand punning complete all as specified in SSR Part-I and as directed. |
| 116 | Supplying and laying unreinforced precast concrete cable cover, Class LV Type-I, flat, size 250 × 150 × 40 mm, laid in trenches complete all as specified and directed. |
| 117 | Material & Labour for cutting metal road / hard standing for laying of cable and making good the surface to match the existing finish, complete all as directed. |
| 118 | Material and labour for GI pipe, light grade, 80 mm diameter for cable protection during road crossing or above ground cable protection including removal of existing pipe if required, complete all as specified and directed. |
| 119 | Supply and fixing HDPE pipe of pressure rating 6 kgf/cm², 50 mm diameter, laid in trenches for cable protection complete all as specified and directed by the Engineer-in-Charge. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail