| 1 | Supply, installation, testing and commissioning of ABS plastic shut off nozzle for hose reel complete as required. |
| 2 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required.Single headed Stainless steel |
| 3 | Providing and fixing M.S. dead plate/blank flange cover for missing landing valve outlet of internal fire fighting system, fabricated from minimum 6 mm thick mild steel plate of suitable size conforming to landing valve outlet dimensions, including rubber insertion gasket, nuts, bolts, washers and necessary drilling/threading complete, duly painted with one coat of red oxide primer and two coats of synthetic enamel paint of approved fire red shade, properly fixed to prevent leakage and maintain integrity of the fire fighting line etc. complete as required. |
| 4 | Supplying and replacement of heavy duty rechargeable battery of 180 AH, 12 Volt suitable for DG set/UPS/fire alarm or other approved application, complete with all necessary connections, terminals, accessories, transportation, installation, testing and commissioning as required. The battery shall be of approved make and conform to relevant IS specifications, with warranty period of 36 months comprising 18 months free replacement warranty and further 18 months warranty on pro-rata basis, cetc. complete as required. |
| 5 | Supplying, installing, testing and commissioning automatic battery charger suitable for charging 180 AH, 12 Volt rechargeable battery, complete with input/output connections, charging indicators, protection against overload, short circuit and reverse polarity, housed in suitable powder coated metal enclosure, compatible for DG set/UPS/fire alarm or approved application, conforming to relevant specifications, including all accessories and wiring required for proper functioning etc. complete as required. |
| 6 | Supply, installation, testing and commissioning of 4 Pole, 1000 Amps electrically operated draw-out type Air Circuit Breaker (ACB), suitable for 415 Volts, 50 Hz, AC supply, having minimum breaking capacity of 50 kA at 415 Volts, complete with microprocessor based release with adjustable Over Load (O/L), Short Circuit (S/C), Instantaneous and Earth Fault protections, LED indications, ON/OFF/TRIP indications, shunt trip, under voltage release, motorized spring charging mechanism, auxiliary contacts and all standard accessories, conforming to relevant IS/IEC standards, including dismantling/removal of existing defective ACB, modification of panel if required, connection with existing bus bars/cables, complete wiring, testing, commissioning and making the system fully functional and complete as required at site with a minimum warranty of 12 months. Please Enable Macros to View BoQ information |