| 1 | FIRE RISER -Supplying, installation testing and commissioning of the following-: ‘C’ class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/JINDAL/SAIL 150 mm dia |
| 2 | 80 mm |
| 3 | Supply and installation, testing and commissioning of CI Butterfly valves ( control of each shaft) ) conforming to BS 5155 ,PN 1.6 tested to 1.5 times working pressure with necessary companion flanges, bolts, nuts, gasket packing and any other spares, including indicator for open and shut position as per fire practice etc complete.Make-Zoloto/Audco/Leader. 150 mm |
| 4 | Providing and fixing Single headed hydrant having outlet of 63 mm dia (2.1/2”) N.B. hydrant (IS:5290) landing valve in Stainless Steel Morris Pattern instanteous coupling type TAC / LFA approved & ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 5 | Providing & fixing 63mm dia RRL hose pipe a 15 mtr length per IS 636 TYPE A TAC/ LFA approved of standard length of approved pattern and size including gun metal male and female Coupling duly bound with copper wire etc. complete.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 6 | Providing and fixing TAC approved fire hose cabinet to house fire hydrant & hose, including all other related accerrories fabricated from M.S. sheet (2mm thick) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 nos. hoses. The hose box size is 750 mm x 600 mm x 300 mm |
| 7 | Supplying & fixing first aid fire hose reel of thermoplast braided suitably reinforced 20 mm size & 30 m standard length with 5 mm tapering branch nozzle, 25mm dia. Pipe to connect to riser with cut off ball valve attachment. Hose to be swinging type wall mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts (Including drum and swivel arrangement) etc complete..Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 8 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 9 | Providing and fixing Stainless Steel standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 10 | EXTERNAL HYDRANT SYSTEM-Supplying, installation testing and commissioning of the following-: ‘C’ class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/JINDAL/SAIL size 150 mm |
| 11 | 80 mm dia. |
| 12 | Providing and fixing hydrant stand posts of 80 mm dia. With flanges and accessories and supply, fixing 63 mm dia SS Single headed Hydrant Valve in the courtyard IS:5290 Including 2 coats of approved enamel paint (red) over a coat of primer, complete with 2.1/2” ‘Morris’ pattern instaneous couplings, etc. complete..Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 13 | Providing & fixing 63mm dia CP hose pipe as per IS 8423 TYPE A TAC/ LFA approved of 15 mtr. standard length of approved pattern and size including SS male and female Coupling duly bound with copper wire etc. complete.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 14 | Providing and fixing TAC approved fire hose cabinet to house fire hydrant & hose, including all other related accerrories fabricated from M.S. sheet (16 Gauge) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 nos. hoses. The hose box size is 750 mm x 600 mm x 300 mm . |
| 15 | Supplying and fixing 4 way Fire Brigade service inlet of size 150 mm dia. with 4 No. 63mm (2.1/2\\") size Stainless Steel male outlets ( Stainless Steel male coupling) including metallic cover of mild steel and glass front, indicator plates,150mm BFV, 150 mm NRV etc. complete.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 16 | Supply and installation, testing and commissioning of Isolation Sluice valves tested to ISI marked ,PN 1.6 with CI body, bonnet & brass trim parts, & having necessary companion flanges, bolts, nuts, gasket packing and any other spares, including indicator for open and shut position to be installed underground in valve chamber as per fire practice etc complete.Make-Leader/Audco/Zoloto.150 mm dia |
| 17 | Providing and fixing Stainless Steel standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:.Make-Minimax/Newage/Fireshield/Safex/Omex. |
| 18 | Supply, Installation, testing and commissioning of One cum Air Vessel ( Comprise with 100 NBCI sluice valve and 25NB Air release valve and ball valve ) with matching flanges as per direction of engineer in charge .Make-Leader/Audco/Zoloto. |
| 19 | TERRACE PIPING & ACCESSORIES -: Supply and installation, testing and commissioning of CI Butterfly valves ( heavy ) conforming to BS 5155 ,PN1.6 tested to 1.5 times working pressure with necessary companion flanges, bolts, nuts, gasket packing, support and any other spares, including indicator for open and shut position as per fire practice etc complete..Make-Zoloto/Audco/Leader.100 mm dia |
| 20 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader Size : 100 mm dia |
| 21 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru |
| 22 | Supplying, installation testing and commissioning of the following-: ‘C’ class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/JINDAL/SAIL Size- 100 mm Dia |
| 23 | Supply and Fixing of 1 Nos of 5000 ltr.doubble layer plastic water storage tank for fire fighting hydrant system to be placed at terace level.Make:- Sinttex/Plasto |
| 24 | Main Structure: Supply and Fixing of Structural steel like MS Beam (ISMB) 200 X 100, MS Channel (ISMC) 100 X 50 X 5, MS Angle ISA 65 X 65 X 6, MS Angle ISA 40 X 40 X 5, MS Sheet 2500 mm x 1250 mm x 2 mm & Plate 200 x 200 x 12 mm including one coats of primer and two coats of signal red colour with all accessories at terrace level for foundation of PVC tank. Make: SAIL/RINL/MSP as per direction of the Engineer-in-charge. |
| 25 | GI Shed over fire pump to protect the fire pump from rain water in terace level. |
| 26 | Supply and Installationof u pvc (32mm) Pipe & Solvent |
| 27 | Pvc ball valve 32 mm |
| 28 | Supply and Installation of GI hex nipple both side threaded for tank connection 100 mm |
| 29 | Supply and Installation of GI socket 100 mm |
| 30 | Supply and installation of float valve |
| 31 | SPRINKLER SYSTEM -: Supplying, installation testing and commissioning of the following-: ‘C’ class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/JINDAL/SAIL 25 mm |
| 32 | 32 mm dia |
| 33 | 40 mm dia |
| 34 | 50 mm dia |
| 35 | 65 mm dia |
| 36 | 80 mm dia |
| 37 | 100 mm dia |
| 38 | 150 mm dia |
| 39 | Supply,Providing & fixing OS&Y conforming to IS-13095, PN 1.6 (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required. Size-100 mm dia |
| 40 | 80 mm dia |
| 41 | 65 mm dia |
| 42 | 50 mm dia |
| 43 | Supplying, installing, testing and commissioning of Pendent/ Upright/ Side wall conventional Sprinkler quartzoid bulb type with 15mm screwed end connection of 68 deg. C. temperature rating, K 80 and orifice shall not be less than 12.7mm.Sprinklers shall be UL Listed / FM approved with Chrome finished.Make-Tyco/HD/Viaking |
| 44 | Supply,Installation, Testing & Commissioning Flexible sprinkler hose for connecting pendent sprinkler.Make-HD/Tyco/Viaking. |
| 45 | Supplying, installing, testing and commissioning of sight glass unit with required size orifice plate, test valve and complete accessories like tees,elbows flanges etc.as per the tender drawing .Butter fly valve for Drain (50 mm) |
| 46 | Supplying, installing, testing and commissioning of Drain Pipe of 50 mm dia.Make- TATA/SAIL/JINDAL |
| 47 | Supply & installation of approved make flow switch on sprinkler header on each floor, operating at 24-V with all accessories & hardwares.Make-Honeywell. |
| 48 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader Size : 100 mm dia |
| 49 | ANALOGUE ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM-:Supply, installing, testing and commissioning of of 8 Loop Network Panel Micro processor based 2 wire fault tolerant loop,with inbuilt network port (each loop accessing 99 or more detectors and 99 or more modules ) fire alarm/detection control panel. The Panel shall have 10000 or more event log history . Panel shall be capable of having 1600 or more configurable zones .The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module when ever any alarm is triggered. The panel shall have 7 Inch Touch Screen unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects.The Panel Shallbe Sheet Steel Painted, selaed to IP30. The Panel Shall have provision for 40 or more Zones with Individual LED Indicators expdable upto 200 Zones or higher. The panel shall have a built in power supply and battery charger along with maintenance free 7 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required.and as per specifications. conforming to BS5839 Standards and Duly Approved by EN54 The panel shall support detection logics like coincidence & verification detections for the false alarm management. The Panel shall adjust the sensitivity between day and night to maintain the better detection/reponse time. The Panel shall be capabale of programming through PC ; Touch Screen of USB .This panel having facility of MODBUS protocol over TCP/IP for BMS integration.The panel should have provision for inbuilt RJ45 connection terminal for connecting to the LAN with inbuilt BACNET Protocol.The price is inclusive of dual loop card. Make- Honeywell(MAX) /Siemens/ Bosch/ Edward/ NOTIFIER/ GST/ Schneider |
| 50 | Supplying, installing, testing and commissioning of OEM make Cloud based service through universal gateway, which shall be enabled through internet. Remote health monitoring solution shall utilize cloud-based software-as-a-service web application & supplementary network gateway hardware. System shall provide secure web access to cloud-based web application using any of the web browsers like Google Chrome (preferable), Internet Explorer etc. from any computer/ tablet/ smartphone connected over internet via defined credentials – username and password. It shall also have the facility to monitor the cloud service over the mobile apps. The cloud-based web application shall capture all fire alarm system data points as received from the system via supplementary gateway hardware of the same make as Fire Alarm Panel. The software shall display real time view of fire system effectiveness, multi-location unified view, custom dashboard, device level information, scheduled reporting, e-mail of critical alarms. The cloud service shall be capable of monitoring 250000 datapoints scattered across multiple install bases spread across multiple geographical locations. The Gateway Card shall be UL Listed.It should have 5 nos. or more user license. Internet/Wi-Fi Connectivity Required.The cost is inclusive of 2 years subscription charges.Software and panel shall be of same make. |
| 51 | Supplying, installing, testing and commissioning of adressable multi sense smoke detector with inbuilt isolator module/isolator base,base, junction box and other accessories.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 52 | Supplying, installing, testing and commissioning of Addressable Manual Call Point with inbuilt monitor module and back box.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 53 | Supplying, installing, testing and commissioning of addressable Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |
| 54 | Supplying, installing, testing and commissioning of addressable Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |