| 1 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 2 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 3 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 4 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required on surface including heavy duty saddles with base at spacing of 0.60 mtr. etc as required. |
| 5 | 20 mm |
| 6 | 25 mm |
| 7 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 8 | On board |
| 9 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 10 | Single pole MCB (With B / C curve tripping characteristics) |
| 11 | 6 A to 32 A rating |
| 12 | Double pole MCB (With B / C curve tripping characteristics) |
| 13 | 40 A rating |
| 14 | Triple pole MCB (With B / C curve tripping characteristics) |
| 15 | 50/63 A rating |
| 16 | Four pole MCB (With B / C curve tripping characteristics) |
| 17 | 50/63 A rating |
| 18 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. |
| 19 | Suitable for Two / Three / Four module for MCB |
| 20 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 21 | 3 pole MCCB With Thermal Magnetic release |
| 22 | up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting |
| 23 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 24 | 16.0 Sq. mm |
| 25 | 4 core |
| 26 | 25.0 Sq. mm |
| 27 | 3.5 core |
| 28 | 35.0 Sq. mm |
| 29 | 3.5 core |
| 30 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 31 | Metal door (Three phase) IK-09 and IP-43 with Metal end box |
| 32 | 4 Way (8 incomer + 12 Outgoing) |
| 33 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB/ RCBO up to 63 Amp and SP / TP MCB upto 32 Amp. as outgoing ,made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with insulated 100 A rating copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 34 | Double door IK-09 & IP-43 with Metal end box |
| 35 | 4 Way (8 Incomer +12 Outgoing) |
| 36 | P & F ISI marked 32 A D.P. switch with fuse and indicating lamp including making connection testing etc. as required. |
| 37 | Providing & Fixing of IK07 IP65 protected Top/Bottom mounted LED Post top Luminarie top & bottom made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with powder quoted reflector. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED Driving output current <750mA as required. |
| 38 | Minimum lumen output 2800 lm Post top Luminarie Please Enable Macros to View BoQ information |