| 1 | Exavation in trenches, 1.5m wide and n. exc. 1.5m in depth , fo foundation etc.n.exc 10 sqm on plan and n. exc 1.5 m in depth and gatting out in soft / loose soil for laying of cables all as specified and directed by Engr-in-charge. |
| 2 | Returnig , filling in, including spreading, leveling , watering and well ramming in layers not exc 25 cm in soft / loose soil complete all as specified and directed by Engr-in-charge. |
| 3 | Removing excavated material n. exc 50m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed by Engr-in-charge. |
| 4 | Material and labour for sand cushioning / sand covering for underground cable protection and consolidated and compected with clean dry sand complete all as specified and directed by Engr-in-charge. |
| 5 | Supply and lay in trenches brick, common burnt in clay, building brick, sub class 'B' designation 75 for cable protection all as specified and directed by the Engr-in-Charge. |
| 6 | Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm all as specified and directed by the Engr-in-Charge. |
| 7 | Supply, laying, jointing and testing of electric cable, heavy duty 11KV (E) grade of size 95 Sqmm 3 core, XLPE insulated, screened with sound compacted aluminium conductor, conductor screening with extruded semi-conducting layers insulation screening with copper tape covers laid up with PVC (ST-2) extruded inner sheathing galvanised steel strip armoured PVC (ST-2) outer sheathed cable conforming to IS-7098(Part-II) amended, laid in trenches/cable duct complete all as specified and as directed. |
| 8 | Supply &Laying only in trenches,fix on pole or passing through pipe and testing LT , XLPE insulated (heavy duty) PVC elecric cable with aluminium conductor , 1100 volte grade , cross-sectional area including taking out U/S LT cable and and aluminium cable lugs of suitable size and cable gland of suitable size and ratings for the following sizes:-. |
| 9 | (a) 400 Sqmm 3.5 core |
| 10 | (c) 95 sqmm 3.5 core complete |
| 11 | (d) 50 sq mm 3.5 Core cmplete |
| 12 | (e) 35 sq mm 3.5 Core cmplete |
| 13 | Supply and laying in replacement GI pipe 80 mm dia light grade for UG cable protection complete all as specified and as directed by Engr-in - charge. |
| 14 | Supply and laying in replacement GI pipe 50 mm dia light grade for UG cable protection complete all as specified and as directed by Engr-in - charge. |
| 15 | Labour only for road boaring (manual) for cable crossing using manual boring prosses all as specified and directed . |
| 16 | Supply and Fixing CPRI approved LT Bus bar chamber Outdoor /wall mounted suitable for 415V 3phase 4 wire 50 Hz AC Supply system of capacity 400A as specified .The panel should be powder coated paint for better environmental protection,made of CRCA sheet steel 3.15mm ,specification should be CPRI approved including making of foundation of the panel ,lugs and glang of suitable size ,Fixing and connection Included all as specified and as directed.The rate also inclusive of all material mentioned from sl no (A) to (F) complete.Note:CPRI approved LT Bus bar chamber shall be provided as per listed in Tender Documents. |
| 17 | Design, Fabrication, Testing & Commissioning of Varmin dust proof CPRI approved LT Feerder Pillar board outdoor type of suitable size made out of MS sheet 3.15 mm thick, CPRI approved & tested , powder coated , rear and front operated door with locking arrangement , suitable aluminium busbar and fixed on angle iron base suitable for pedastal mounting of size 50x50x5 mm at least 2 feet above GL to accomodating the following :- INCOMING :-(A) MCCB 400 Amps, 4 pole, 36 KA - 01(in coming)OUTGOING :-(B) MCCB 200 Amps, 4 pole, 25KA - 02 Nos (out going)(C) MCCB 125 Amps, 4 pole, 25KA - 04 Nos (out going)(D) MCCB 63 Amps, 4 pole, 25KA - 04 Nos (out going) (E) MCB 32 Amps,DP, 15KA - 02 Nos (out going) (F) Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class Note : The rate also inclusive of all material mentioned from sl no (A) to (F) complete.CPRI approved LT Feerder Pillar board shall be provided as per listed manufacturer in Tender Documents. |
| 18 | Design, Fabrication, Testing & Commissioning of Varmin dust proof CPRI approved LT Feerder Pillar board outdoor type of suitable size made out of MS sheet 3.15 mm thick, CPRI approved & tested , powder coated , rear and front operated door with locking arrangement , suitable aluminium busbar and fixed on angle iron base suitable for pedastal mounting of size 50x50x5 mm at least 2 feet above GL to accomodating the following :- INCOMING :-(A) MCCB 200 Amps, 4 pole, 36 KA - 01(in coming)OUTGOING :-(B) MCCB 63 Amps, 4 pole, 25KA - 07 Nos (out going) (C) MCB 32 Amps,DP, 15KA - 02 Nos (out going) (D)Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class Note : The rate also inclusive of all material mentioned from sl no (A) to (D) complete.CPRI approved LT Feerder Pillar board shall be provided as per listed manufacturer in Tender Documents. |
| 19 | M&L for PCC 1:2:4 type C2 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement. |
| 20 | M&L Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground( earth pit not less than 2.25 mtrs deep below normal ground level )with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI strip of size 32 x 6mm by means of GI nuts, bolts check nuts and washers earth lead protected by 15mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion. Notes:-The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GI watering pipe 20mm dia med grade ,wire mesh, protection pipe 40mm dia GI pipe light gde for earth lead upto 7.50m long complete . |
| 21 | M&L for earthing with copper earth plate electrode 600 x 600 x 3.15 mm thick burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to copper strip of size 20 x 3 mm as earthing lead means of nut, bolts and washers made out of galvanised ireon mild steel and 40 mm dia GI pipe \\"light grade\\" for protection of earth lead and connected to contoll board or main switch or as directed by Engr -in-Charge including earthing pit in PCC (1:3:6) type C1 pre-cast cover RCC cover lab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work complete shown in electrical plated No 3 and tesing complete. NOTE : (i) Copper strip of size 20 x 3 mm upto 7.5 mtr length shall be deemed to include in this items rate. Please Enable Macros to View BoQ information |
| 22 | M&L for earthing with copper earth plate electrode 600 x 600 x 3.15 mm thick burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to copper strip of size 20 x 3 mm as earthing lead means of nut, bolts and washers made out of galvanised ireon mild steel and 40 mm dia GI pipe \\"light grade\\" for protection of earth lead and connected to contoll board or main switch or as directed by Engr -in-Charge including earthing pit in PCC (1:3:6) type C1 pre-cast cover RCC cover lab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work complete shown in electrical plated No 3 and tesing complete. NOTE : (i) Copper strip of size 20 x 3 mm upto 7.5 mtr length shall be deemed to include in this items rate. Please Enable Macros to View BoQ information |