| 1 | Total amount of Sch 'A' Sec-I ( BUILDING WORKS ) Lump sum price worked out by the contractor for \\" BUILDING WORKS \\" as listed in schedule 'A' Part-I |
| 2 | Total amount of Sch 'A' Sec II (SITE CLEARANCE, SITE DEVELOPEMENT & MISC. EARTH WORKS) Lump sum price worked out by the contractor for \\" SITE CLEARANCE & Earth Works \\" as listed in schedule 'A' Part-II |
| 3 | Total amount of Sch 'A' Sec III ( INTERNAL WATER SUPPLY WORKS ) Lump sum price worked out by the contractor for \\" BUILDING WORKS \\" as listed in schedule 'A' Part-III |
| 4 | Total amount of Sch 'A' Sec IV (INTERNAL ELECTRIFICATION WORKS) Lump sum price worked out by the contractor for \\" BUILDING WORKS \\" as listed in schedule 'A' Part-IV |
| 5 | Total amount of Sch 'A' Sec V (SEWAGE DISPOSAL WORKS) Lump sum price worked out by the contractor for \\" SEWAGE DISPOSAL WORKS \\" as listed in schedule 'A' Part-V |
| 6 | Total amount of Sch 'A' Sec VI (AREA DRAINAGE WORKS) Lump sum price worked out by the contractor for \\" AREA DRAINAGE WORKS \\" as listed in schedule 'A' Part-VI |
| 7 | Total amount of Sch 'A' Sec VII (ROAD, PATH, CULVERTS AND HARDSTANDING WORKS) Lump sum price worked out by the contractor for \\" ROAD/PATH/CULVERT WORKS \\" as listed in schedule 'A' Part-VII |
| 8 | Total amount of Sch 'A' Sec VIII (EXTERNAL WATER SUPPLY WORKS) Lump sum price worked out by the contractor for \\" EXTERNAL WATER SUPPLY WORKS \\" as listed in schedule 'A' Part-VIII. |
| 9 | Total amount of Sch 'A' Sec IX ( EXTERNAL ELECTRIC SUPPLY WORKS) Lump sum price worked out by the contractor for \\" EXTERNAL ELECTRIFICATION WORKS \\" as listed in schedule 'A' Part-IX. |
| 10 | Total amount of Sch 'A' Sec X (FENCING & GATE WORKS) Lump sum price worked out by the contractor for \\" FENCING & GATE WORKS \\" as listed in schedule 'A' Part-X |
| 11 | Schedule 'A'Section-XI(Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col. 5 siginifies this fact only. |
| 12 | FENCING & GATE WORKSM&L for Construction of Steel Gate 5.5m wide 2.5m height made out of angle iron square bars gun set plate incl RCC pillars channel wheel track painting steel work with two coats synthetic enamel paint over a coat of primer and two coat of snowcem to RCC pillaars necessary excavation etc complete all as specified and shown on drg. |
| 13 | SEWAGE DISPOSAL WORKSM&L for Construction of Septic tank designed to carry sewage and sullage water, excavation in any type of soil for 100 users of conventional type ,as per Drg no. 1320(c) Sh 1/3 to 3/3 complete all as specified and directed . |
| 14 | M&L for Construction of Soakage wells excavation, in any type of soil,for 2.4 meters Dia with 3 meters effective Depth of foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats complete all as specified and directed . |
| 15 | INTERNAL ELECTRIFICATION WORKSM&L for modular fan step regulator 2 module, 120 W suitable for BLDC fans complete all as specified and directed. |
| 16 | M&L for vertical loadline DB TPN 4 ways double door 415 volts suitable for MCCB TPN as incommer and standard insulated bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type including drilling holes for incoming and outgoing cables complete all as specified and directed . |
| 17 | Supply & Fixing electric water storage heater (vertical type geysers) 25 Ltr, 2.0 KW, BEE 5 star 230 volts AC single Phase, including MS glass lined inner tank, glass coated heating element , high density PUF insulation Anode rod protection heavy duty fastner not less than 100mm with suitable size of nut & washer grouted in wall with complete mason work for proper mounting of geyser fastner bolt, such as safety value, NRV thermostat , plug top & wire fabric at pressure 6Kg/cm2 both side, CP brass 15mm bore coupling or nuts etc as directed as per site requirement , making necessary inlet/outlet water connection and electric connection, testing on load for full satisfaction of Engineer-In Charge. Note: Portable residual current device (16 Amps, 30 mA) shall be provided with each Geysers in lieu of Plug Top. Cost of which is included in overall coated cost by contractor. Any item left out for completion of job is deemed to be included in overall rates quoted. |
| 18 | Supply & Fixing new generation energy saving and environmental friendly long life LED building security light 1x35 watts made up of pressure die cast alluinium housing with high power LED as light source and lense embedded PC Cover having top opening separate driver compartment with IP65 protection and impact resistance of IK07, with all accessories including suitable bracket with 32mm bore light grade GI pipe bend to shape , including MS clamp of size of required size and PVC cable 1.5 sqmm twincore from ceiling rose to light fittings , complete all as specfied and directed. |
| 19 | M&L for RCBO-A Type (SPN-2 M) 63 Amps 30 mA (in accordance with IS 12640-2 & IEC 61009-1) 240 V/415V, 50 Hz with 10 kA short circuit capacity, RCBO designed for use in domestic, commercial and industrial distribution systems at the most downstream circuit for ensuring protection from leakage current, short circuit & over load to the user for a particular circuit. In normal use, it is safe to use and free of threat to user as well as to environment complete and all as directed and specified. |
| 20 | M&L for MCCB TPN, 160 A, 415 V, 16 kA confirms to IEC 60947-II adjustable thermal setting type suitable for TPN vertical loadline DB complete all as specified and directed . |
| 21 | M&L for LED bulb 12 Watt, Inverter type, 230 volts AC 50 Hz Retrofit B22 base complete all as specified and directed . Please Enable Macros to View BoQ information |
| 22 | M&L for LED bulb 12 Watt, Inverter type, 230 volts AC 50 Hz Retrofit B22 base complete all as specified and directed . Please Enable Macros to View BoQ information |