| 1 | DSR item No.1.8 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group-C |
| 3 | DSR item No. 1.17 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 4 | 3 x 1.5 sq. mm |
| 5 | 3 x 2.5 sq. mm |
| 6 | DSR item No. 1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 25 mm |
| 8 | DSR 1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 9 | DSR item No.1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | DSR item No.2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 11 | 100 A,30KA,FPMCCB |
| 12 | 200 A,36KA,FPMCCB |
| 13 | DSR item No.8.7 LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt) (Recessed/ Surface type) (Please refer DNIT for complete specification of item no.7) |
| 14 | 36 watt |
| 15 | DSR item No.8.16 LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt). (Please refer DNIT for complete specification of item no.8) |
| 16 | 150 Watt. |
| 17 | DSR item No.9.2 Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. |
| 18 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 19 | Supply & erection of Exhaust Fan (heavy duty motor with copper wound metallic body) following size complete with motor, metallic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation, epoxy powder coating along with metallic louver to be installed in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of Engineer-in-charge. |
| 20 | Size 15 inch (380mm) Sweep, 900 RPM Heavy Duty Exhaust fan (Single Phase) with louver of Havells (Turbo Force SP) / Orient (Industrial Heavy Duty)/ Usha (Turbo HDEF)/ Crompton (EXHD380-6-1)/ Bajaj (Supreme Plus) make only. |
| 21 | S/E of on load change over switch of 200 Amp. 4 pole 415 Volt with enclosure. The changeover switch should be of Havells/ Lauritz Knudsen/ Siemens/ Schneider/ABB/ Hager make only. The Changeover switch should be installed in existing cubicle panel / angle iron board/ including drilling holes in cubicle panel / angle iron board, making connections with suitable rating of copper wire / copper strip etc. as required. The job includes the cost of all petty material and labour charge etc as required to complete the job to the entire satisfaction of Engineer-in-charge. |
| 22 | S/E of electronic fan regulator step type socket type in the existing bakelite sheet including cutting the sheet and making connection etc. The job includes all labour and petty material required to complete the job to the entire satisfaction of the Engineer-in-chaege of the work. The fan regulator should be of Anchor(Penta)/ Havells (Reo)/ SSK make only. Please Enable Macros to View BoQ information |