| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Make: Polycab/ Finolex/ L&K) |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (Make: Polycab/ Finolex/ L&K/KEI) |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 2 X6sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 4X4sq. mm + 2X 4 sq. mm earth wire |
| 9 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 10 | 4 X 10sq. mm + 2 X 6 sq. mm earth wire |
| 11 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required Make-L&K(Entice model)/LEGRAND-(Mylinc model)/ABB-(Tvisha white/IVIE model/ INDOASEAN) |
| 12 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required (Make:L & K/ABB/LEGRAND /INDOASEAN) |
| 13 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.Make-L&K(Entice model)/LEGRAND-(Mylinc model )/ABB-(Tvisha white/IVIE model) |
| 14 | Supplying & fixing suitable size GI/PVC box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. Make- L&K/LEGRAND/Havels /ABB/INDOASEAN |
| 15 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (Make:L & K/ABB/LEGRAND /INDOASEAN) |
| 16 | 5/6 A switch |
| 17 | 15/16 A switch |
| 18 | 3 pin 5/6 A socket outlet |
| 19 | 6 pin 15/16 A socket outlet |
| 20 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 21 | 1 or 2 Module |
| 22 | 3 Module |
| 23 | 4 Module |
| 24 | 6 Module |
| 25 | 8 Module |
| 26 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. (Make:L & K/ABB/LEGRAND /INDOASEAN) |
| 27 | 1 or 2 Module (75mmX75mm) |
| 28 | 3 Module (100mmX75mm) |
| 29 | 4 Module (125mmX75mm) |
| 30 | 6 Module (200mmX75mm) |
| 31 | 8 Module (125mmX125mm) |
| 32 | 12 Module (200mmX150mm) |
| 33 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Make- L&K/ABB/LEGRAND /INDOASEAN |
| 34 | 8 way , Double door |
| 35 | 12way , Double door |
| 36 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Make- L&K/ABB/LEGRAND |
| 37 | 4 way (4 + 12), Double door |
| 38 | 6 way (4 + 18), Double door |
| 39 | 8 way (4 + 24), Double door |
| 40 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 125 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCCBs and incomer) as required . (Note : Vertical type MCCB TPDB is normally used where 3 phase outlets are required.) Make- L&K/ABB/LEGRAND/INDOASEAN |
| 41 | 4 way (4 + 24), Double door Make- L&K/ABB/LEGRAND/INDOASEAN |
| 42 | 8 way (4 + 24), Double door Make- L&K/ABB/LEGRAND/INDOASEAN |
| 43 | 12 way (4 + 36), Double door Make- L&K/ABB/LEGRAND /INDOASEAN |
| 44 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required |
| 45 | 100 A, 30 kA,FP MCCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 46 | 125 A, 36 kA,FP MCCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 47 | 200 A, 36 kA,FP MCCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 48 | 250 A, 36 kA,FP MCCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 49 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.(Annual Repair and Maintenance of Electrical works in Academic Buildings in the campus of IIT(BHU) ) |
| 50 | 32 A TP&N |
| 51 | 63 A TP&N |
| 52 | 100 A TP&N |
| 53 | 125 A TP&N |
| 54 | 160 A TP&N |
| 55 | 200 A TP&N |
| 56 | Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses, connections, earthing etc. as required. |
| 57 | 63 A TP&N Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 58 | 100 A TP&N Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 59 | 200 A TP&N Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 60 | 315 A TP&N Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 61 | 400 A TP&N Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 62 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make L&K/ABB/C&S/Legrand/Hagger/Schneider |
| 63 | Single Pole MCB Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 64 | Double Pole MCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 65 | Triple Pole MCB Make-L&K/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 66 | FP MCB 40/63 A Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 67 | 4 Way Enclosure Metal Box |
| 68 | 2 Way Enclosure Metal Box |
| 69 | Supply & laying of 3.5CX50 Sqmm Aurmoured Aluminium cable XLPE Cable and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface or as per the site requirement . Make: KEI/ Gloster/ Universal./Polycab |
| 70 | Supply & laying of 3.5CX70 Sqmm Aurmoured Aluminium cable XLPE Cable and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface or as per the site requirement . Make: KEI/ Gloster/ Universal./Polycab |
| 71 | Supply & laying of 3.5CX95 Sqmm Aurmoured Aluminium cable XLPE Cable and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface or as per the site requirement . Make: KEI/ Gloster/ Universal./Polycab |
| 72 | Supply & laying of 3.5CX185 Sqmm Aurmoured Aluminium cable XLPE Cable and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface or as per the site requirement . Make: KEI/ Gloster/ Universal./Polycab |
| 73 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 74 | 3½ X 185 sq. mm (57 mm) |
| 75 | 3½ X 95 sq. mm (45 mm) |
| 76 | 3½ X 70 sq. mm (38 mm) |
| 77 | 3½ X 50 sq. mm (35 mm) |
| 78 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 79 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) |
| 80 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 81 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 82 | LED Batten light (System lumen efficacy ≥105 85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 83 | Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 36 watt Make: Wipro/ Philipse/CG |
| 84 | LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 85 | Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 36 watt Make-Phillipse/Wipro/CG |
| 86 | Supplying Installation, testing and commisioning of following Energy Efficieny recess mounted LED Luminarie suitable for 36w,1X1 Grid Ceiling having flat diffuser & constant current electronic driver complete with all accessories & lamps including making hanging arrangement using chain etc. and connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc as reqd. (Make Philips Cat No-(Make Philips Cat No-RC375B LED 365 865/840 PSU W60L60 52 WH/ Equivaent in Wipro) Make-Phillipse/Wipro/CG/ |
| 87 | Supplying, Installation, Testing and commissioning of 24W Round surface mounted LED Light (Make: Crompton/Wipro/Philips) (Cat No: SM242C LED 24S PSU WH) |
| 88 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beamangle 30 deg-120deg as per the application and theproject requirement., suitable tilt able fitting, life time(LED, Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumenmaintained till life ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) ,SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not morethan the specified rating and Fixture shall of relevant BIS standard complete in all respect i/cexternal connections with 1.5 sqmmFRLS/HFFR, PVC insulated copper conductor singlecorcable and earthing etc. as required withMinimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 89 | 100 watt Make-Phillipse/Wipro/CG |
| 90 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70,under voltage and over voltage protection, EMI EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 91 | 90 watt Make-Phillipse/Wipro/CG |
| 92 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 93 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) (Make:Usha / Crompton / Orient) |
| 94 | Supplying and fixing of 230VAC 1Ph. 1400mm dia Ceiling Fan (High Speed). (Make: Usha / Crompton / Orient) |
| 95 | Supplying and fixing of 230VAC 1Ph. Stepped type Modular Fan regulator (2 module) |
| 96 | Supplying,Cutting of huck , painting and fixing of MS Down down conduit for installation of ceiling fan upto 5 to 8 feet |
| 97 | Supplying and fixing of 230VAC 1Ph. 250 mm exhaust Fan with sweep feature. Make: Usha / Crompton / Orient |
| 98 | Supplying and fixing of 230VAC 1Ph. 450 mm exhaust Fan with sweep feature. (Make: Usha / Crompton / Orient) |
| 99 | Supplying and fixing of 230VAC 1Ph. 300 mm exhaust Fan with sweep feature. Make: Usha / Crompton / Orient |
| 100 | Supplying and fixing of 230VAC 1Ph.400 mm ,900 rpm Wall Fan Make: Usha / Crompton / Orient |
| 101 | Supply and fixing of 170mm x57 mm Dado cable management trunking 2 compartment with suitable joint for each compartment ,internal & external corner, flat angles, flat tee, end cap & joint cover (coupler), cable retainer, separation partition as required.(Make: Honeybell) |
| 102 | Supply and fixing of 100 mm X 50 mm UPVC cable management trunking with suitable joint for each compartment ,internal & external corner, flat angles, flat tee, end cap & joint cover (coupler), cable retainer, separation partition as required.(Make: Honeybell) |
| 103 | Supplying .insalling on wall testing & commissioning of following capacity rising mains made Bus Bar of 1.6 thick IP 42 sheet steel encloser duly paited with powder coating bus havibg current rating 315 amp 415Volt 3 phase, 4 wire 50hz AC Supply extension joint fire proff jointed and earthing expansion joint, thrust.pads including with2 runs of G.I Strip |
| 104 | Supplying and laying of 1.1KV grade 4 core × 10sqmm AYFY Al cable single run PVC insulated and PVC sheathed / XLPE power cable in the pvc pipe in the surface including excavation and refilling the trench etc as required but excluding sand cushioning and protective covering Make: KEI/ Gloster/ Universal./Polycab |
| 105 | Supply and installation of 63-125 A HRC Fuse |
| 106 | Providing services for day to day maintenance, upkeep, Breakdown maintenace, Preventive maintenance and attending complaints of complete internal and external electrical installations including manpower and all work assigned by Engineer-Incharge of all residential and non residential buildings within Institute campus, pathway and parcel area lights, panels, feeder pillar etc, on all days including Sundays and holidays etc as required in general shift daily 365 Days. Duration of shift shall be of 8 hour) (Note : Material required for replacement of faulty fixture shall be measured and paid seprately.Cost of all tools, plants and consumables etc. required for above mentioned work is included in the scope of work.) |
| 107 | One Electrician |
| 108 | One Khallasi/Helpher Please Enable Macros to View BoQ information |