| 1 | Supplying, Installing, Testing & Commissioning of Electric Driven Main Fire Pump suitable for automatic operation consisting of Horizontal, End Suction Centrifugal Fire pump with cast iron casing & cast-iron impeller, stainless steel shaft to deliver 1620 Ltrs/Min at 60 MWC (Meter of Water Column). Pump coupled to Squirrel cage type TEFC (totally Enclosed Fan Cooled) induction motor suitable for operation on 415 v, 3 phase 50hz system with Common base plate for pump and motor and coupling, coupling guard and other accessories accessories standard mounting accessories. (RCC foundation & Cabling shall be provided by others) |
| 2 | Supplying, Installing, Testing & Commissioning of Electric Driven Jockey Pump suitable for automatic operation consisting of Horizontal End Suction Centrifugal Fire pump with cast iron casing & cast- iron impeller, stainless steel shaft to deliver 180 Ltrs/Min at 60 MWC (Meter of Water Column). Pump coupled to Squirrel cage type TEFC (totally Enclosed Fan Cooled) induction motor suitable for operation on 415 v, 3 phase 50hz system of with Common base plate for pump and motor and coupling, coupling guard and other standard mounting accessories.(RCC foundation & Cabling shall be provided by others) |
| 3 | Supply, Installation, Testing and Commissioning of Diesel Engine Driven Fire Pump of approved make suitable for automatic/manual operations End suction type fire pump with CI impeller with CI body should be of grade F.G. 200 to IS : 210 casing shall be designed for 1.5 time of working pressure, capable of delivering of 1620 LPM against a total head of 60 Mtrs while running at minimum of 1600 R.P.M to ensure a minimum pressure of 3.5 Kg per Sq.cm at the farthest outlet; complete with common base plate, coupling, coupling guard and other accessories standard mounting accessories.(RCC foundation & Cabling shall be provided by others) |
| 4 | Supply, Installation, Testing and Commissioning of charges for automatic fire hydrant system panel for the main pump, standby pump, terrace pump and jockey pump. Incorporating automatic start delta starter for main and stand by fire pump & automatic direct online starter indications showing the power supply condition ammeter with clear indications of the motor full load current, volt meter with selector switch L&T 9(ISI) etc , the panel shall be duly painted with protective anticorrosive lacquer and be of floor mounted type. |
| 5 | Supply, erection, testing and commissioning of Electrical driven Monoblock Terrace pump 450 Lpm@ 3.5 Bar with all the necessary accessories. |
| 6 | Supply, installation, testing and commissioning of motor control panel with necessary indication lamps for ON or OFF. |
| 7 | Supply, Installation, Testing and Commissioning of 50mm GI 'C' Class Exhaust Pipe for diesel engine pump |
| 8 | S I T C of hydraulically operated Sprinkler control valve, with water motor gong bell and trims as required, pressure gauges, drain valves, ball valves, check valves, strainers etc. complete |
| 9 | Supplying, installing, testing and commissioning of Pressure gauges of suitable range for pump sets. Glycerin filled 150mm dia pressure gauges to use on pump discharge & test lines. |
| 10 | Supply, Installation, Testing and Commissioning of charges of Pressure switch arrangement for pump room and total system |
| 11 | Supply, Installation, Testing and Commissioning of charges of air cushion Vessel 200 mm dia with stand pressure of 15 kg /cm2 with automatic air release cock, bronze make 25 mm dia ball valve, drain pipe, bronze drain valve and shut off having a length of 120cm. |
| 12 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 150 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 13 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 100 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 14 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 80 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 15 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 65 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 16 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 40 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 17 | Supply, Installation, Testing and Commissioning of GI 'C' class medium pipe as per is medium grade of 25 mm dia, with necessary fittings such as nuts & bolts, bends, flanges, etc and Welded joints, The pipe shall be painted with two coats red colour enamel paint over primary coat of Primer. |
| 18 | Supply, Installation, Testing and Commissioning of underground piping GI pipe Class 'C' medium grade 150 mm dia ISI mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. and piping shall have anti corrosive wrapping treatment. |
| 19 | Supply, Installation, Testing and Commissioning of underground piping GI pipe Class 'C' medium grade 100 mm dia ISI mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. and piping shall have anti corrosive wrapping treatment. |
| 20 | Supply, Installation, Testing and Commissioning of underground piping GI pipe Class 'C' medium grade 80 mm dia ISI mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. and piping shall have anti corrosive wrapping treatment. |
| 21 | Supply, Installation, Testing and Commissioning of butterfly valve 150 mm wafer type Stainless steel/SG iron disc , lever operated in PN 1.0 , teflon or nylon bushing, nitrile O rings in standard mounting flanges with hand lever type. |
| 22 | Supply, Installation, Testing and Commissioning of butterfly valve 100 mm wafer type Stainless steel/SG iron disc , lever operated in PN 1.0 , teflon or nylon bushing, nitrile O rings in standard mounting flanges with hand lever type. |
| 23 | Supply, Installation, Testing and Commissioning of butterfly valve 80 mm wafer type Stainless steel/SG iron disc , lever operated in PN 1.0 , teflon or nylon bushing, nitrile O rings in standard mounting flanges with hand lever type. |
| 24 | Supply, Installation, Testing and Commissioning of butterfly valve 50 mm wafer type Stainless steel/SG iron disc , lever operated in PN 1.0 , teflon or nylon bushing, nitrile O rings in standard mounting flanges with hand lever type. |
| 25 | Supply, Installation, testing and commissioning of 150 mm dia Non Return Valve Dual plate wafer type slim seal check valve, short pattern type with integral hinge pin disc , nitrile rubber O - ring seat and face sealing as per IS: 5312 . |
| 26 | Supply installation testing and commissioning charges of 150 mm Y Type Strainer cast iron body with leather gasket. |
| 27 | Supply,Installation,Testing and Commissioning of 25 mm Ball Valve |
| 28 | Supply,Installation,Testing and Commissioning of ISI marked single headed Hydrant valve 63 mm dia, oblique type, with SS body & working parts, with instantaneous hose coupling adaptor and PVC blank cap & chain. |
| 29 | Supply,Installation,Testing and Commissioning of branch pipe made out of SS short male instant. Inlet male threaded outlet, fitting with 15 mm bore nozzle ISI |
| 30 | Supply,Installation,Testing and Commissioning of ISI marked Fire Fighting Hose , all synthetic fiber circular woven jacketed,control perculated delevery hose , 38kg/cm2 burst pressure, 22kg/cm2 proof pressure, 14 kg/cm2 working pressure, bearing IS:636-88 type B , in 15 mtrs length, 63 mm dia, duly bounded with SS body coupling 63 mm dia pair of male & female parts, instantaneous type . |
| 31 | Supply,Installation,Testing and Commissioning of Hose reel drum made of Mild Steel, with mounting brackets 19 mm dia nylon braded smooth surface rubber thermo plast hose 30 mtrs length with shut off nozzle |
| 32 | Supply,Installation,Testing and Commissioning of Double Hose Box (Fire Hose cabinet) to accommodate one piece of 63 mm dia fire hose along with one pair of 63 mm dia male & female couplings and one branch pipe. The cabinet is made of Fiber with glass fronted hinged doors and lock. |
| 33 | Supply,Installation,Testing and Commissioning of 25 mm Air release valve gun metal body |
| 34 | Supply,Installation,Testing and Commissioning of 4 way Fire brigade Inlet connection fabricated from 100 mm dia MS Class B medium grade pipe comprising of two 63 mm dia S.S male threaded non return valve. |
| 35 | Supply,Installation,Testing and Commissioning of Tank filling Inlet fabricated from 100 mm dia MS Class B medium grade pipe comprising of two 63 mm dia S.S male threaded non return valve. |
| 36 | Supply,Installation,Testing and Commissioning of Sprinkler 15 mm size , 1/2\\" BSPT end connection having temp. rating 68 deg. C made out of forged brass and SS decorative finish with supports. UL listed |
| 37 | Supply, installation, testing & commissioning of flow switch on sprinkler distribution header on each floor shall be connected to fire alarm panel through cable |
| 38 | Supply, installation, testing and commissioning of Stainless steel corrugated flexible pipe(hose) for dropping sprinklers below false ceiling, pipe shall be 16 bar pressure rating and 25 mm dia with union |
| 39 | S I T C of chrome plated Rosette plates (Dome type, in one-piece) for Sprinklers below false ceiling area. |
| 40 | Supply and Fabricating of Structural Support such as An glair, Angle bar,C-Channel, Square Tube etc, including, cutting welding with nut, bolt & Anchor fastners etc… |
| 41 | Supply, Installation of Fire Extinguisher ABC type fire extinguisher ISI mark ,6 kg capacity with initial charger and installation brackets. |
| 42 | Supply, Installation, Testing and Commissioning of 2 Loop Fire Alarm Control Panel, 60-watt Addressable type microprocessor-based control panel of MS cabinet powder coated audio and visual display with all necessary attachments. Panel should have resettable power output 24 volt D UL/FM Approved |
| 43 | PUBLIC ADDRESS SYSTEM - Supply, installation, testing and commissioning of public address and talk back system consisting of 6 zone public address cum talkback console with mike and selector. 6 channel talk back master control panel with 2x16 character LCD display,power supply, battery charger, battery housing, 80 W PA & mic, 6 channel selector with all call and mic on. The console shall be provided with suitbale capacity amplifier (min 80W) and suitable capacity battery (min 12V) all assembled in a cabinet and meeting the technical specifications. The rate shall include the cost of all the necessary accessories as required for the operation of the system, complete as required as per the technical specification |
| 44 | Supply, Installation, Testing and Commissioning of Manual Call Point break glass type powder coated MS box, 24/12 Volt DC operated, and with necessary attachments. |
| 45 | Supply, Installation, Testing and Commissioning of Audio alarm hooter (sounder) powder coated MS box, 24/12 Volt DC operated, and with necessary attachments. |
| 46 | Supply, Installation, Testing and Commissioning of 6W wall mounted type Speakers with talk back facility, in CRCA sheet fabricated housing, complete with switch. |
| 47 | Supply, installation, testing and commissioning of wall/ceiling mounted 6W speaker including all necessary accessories complete as required as per the technical specification |
| 48 | Supply, Installation, Testing and Commissioning of Smoke detectors with all standard accessories like base etc to be installed under or above false ceiling, UL Approved |
| 49 | Conventional type reflected beam smoke detector with protection range upto 50 m complete with transmitter, receiver, reflector, brackets and all other necessary accessories. The product must be UL listed complete as required as per the technical specification. |
| 50 | CABLING and WIRING : Supplying and laying of 2x1.5 sq mm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring and LSZH outer sheath complete as required. |
| 51 | Supply, installation, testing & commissioning of addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected |
| 52 | Supply, installation, testing & commissioning of addressable Control module shall be capable of providing SPDT/DPDT contact rated at 24v DC, 2A (for hooter/strobe). |
| 53 | Supply, installation, testing & commissioning of addressable monitor module for monitoring the field devices and shall be capable of providing SPDT/DPDT contact rated at 24v DC,2A |
| 54 | 1 x 6W, 240 V, 1 ph, 50 Hz indoor type emergency exit light fixture with 1.3 AH 4hrs battery backup unit, LED Lamps, indicating Fire Exit, recess mounted type. 24 hrs x 7 days working conditional. |
| 55 | Supply Installation of in position the signages of \\"Fire boards approved by Kerala state fire service - size 1ft x 4ft made out of PVC rigid sheet 3mm thick with computer cut PVC non-reflective self adhesive imported vinyl painted on the front of PVC rigid sheet complete with wall mounting arrangements with mirror screws\\". with lettering ASSEMBLY AREA |
| 56 | Supplying Installing of in position the following type of sign boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, luminescent self-adhesive vinyl painted foam board, complete with mirror fasteners; FIRE DUCT |
| 57 | Supplying Installing of in position the following type of sign boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, luminescent self-adhesive vinyl painted foam board, complete with mirror fasteners; EXIT |
| 58 | Supplying Installing of in position the following type of sign boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, luminescent self-adhesive vinyl painted foam board, complete with mirror fasteners; FIRE EXIT |
| 59 | Supplying Installing of in position the following type of sign boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, luminescent self-adhesive vinyl painted foam board, complete with mirror fasteners; NO SMOKING |
| 60 | Supplying Installing of in position the following type of sign boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, luminescent self-adhesive vinyl painted foam board, complete with mirror fasteners; EVACUATION PLAN |
| 61 | Preparation of all drawings and Documents, arranging inspection from the State Fire & Rescue Services Dept. |
| 62 | 2.7.1 Earth work in Excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dresses, Ordinary rock |
| 63 | 4.1.5 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 64 | 5.9.1 Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 65 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works upto plinth level |
| 66 | 5.22.6 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 67 | 5.3 Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 68 | 5.9.6 Centering and shuttering including strutting etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 69 | 5.5 Reinforced cement concrete work in arches, archribs, domes, vaults, shells, folded plate and roofs having slope more than 15 up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 70 | 13.9.2 Cement plaster 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement. 20 mm cement plaster |
| 71 | 22.23.1 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50 mm. The work shall be carried out all complete as per specification and the direction of the engineering charge. The product performance shall carry guarantee for 10 years against any leakage. For vertical surface two coats @ 0.70 kg per sqm. |
| 72 | 13.46.1 Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm). |
| 73 | 13.52.2 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On concrete work |
| 74 | 18.17.3 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 40 mm nominal bore |
| 75 | 18.17.4 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 50 mm nominal bore |
| 76 | 18.9.4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement trenching, refilling and testing of joints complete as per direction of Engineer in Charge. : External work : 32 mm nominal dia pipes |
| 77 | 18.9.6 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement trenching, refilling and testing of joints complete as per direction of Engineer in Charge. : External work : 50 mm nominal dia pipes |
| 78 | 10.26.3 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. GI pipe |
| 79 | 10.16.2 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished seamless type tubes |
| 80 | 2.7.1 Earth work in Excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dresses, Ordinary rock |
| 81 | 4.1.5 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 82 | 5.9.1 Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 83 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works upto plinth level |
| 84 | 5.22.6 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 85 | 5.2.2 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 86 | 5.9.6 Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 87 | 13.9.2 Cement plaster 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement. 20 mm cement plaster |
| 88 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., The work shall be carried out all complete as per specification and the direction of the engineering charge. The product performance shall carry guarantee for 10 years against any leakage. |
| 89 | 13.46.1 Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm). |
| 90 | 13.52.2 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On concrete work |
| 91 | 18.17.4 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 50 mm nominal bore |
| 92 | 18.9.4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. : External work : 32 mm nominal dia pipes |
| 93 | 10.16.2 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished seamless type tubes |
| 94 | 10.26.3 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. GI pipe Please Enable Macros to View BoQ information |