| 1 | Fire Alram and Detection System Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. 2 LOOP. |
| 2 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 3 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 4 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 5 | Supplying, installation, testing & commissioning of addressable Manual Call Point complete as required. |
| 6 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 7 | Supplying & laying of 2Cx1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 8 | S/F of 25mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 9 | Supplying & laying of 2x1.5 sqmm unarmoured cable, 600/1000V rated with annealed copper conductor having Pvc/ XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 10 | Dismentling of old/unusable fire alram and detection system detector & devices complete in all respect as required. |
| 11 | Dismentling of old/unusable wire including pipe fire alram and detection system detector & devices complete in all respect as required. |
| 12 | Fire Hydrant systemProviding laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia. |
| 13 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paintof required shade complete as required : |
| 14 | 80 mm dia. |
| 15 | 100 mm dia. |
| 16 | 150 mm dia. |
| 17 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required Single headed Stainless steel |
| 18 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required Single headed Stainless steel |
| 19 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 20 | 80 mm dia |
| 21 | 100 mm dia |
| 22 | 150 mm dia |
| 23 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 80 mm dia |
| 24 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 150 mm dia |
| 25 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304) |
| 26 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.20 mm nominal internal dia water hose thermoplastic(Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle.Drum and brackets for fixing the equipmets on wall.Connections from riser with 25 mm dia stop gun metalvalve & M.S. Pipe and socket. 30mm |
| 27 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS 4 way - 150 mm dia M.S. Pipe |
| 28 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 29 | Providing & fixing in position the industrial type pressure gauges with gun metal/ brass valves complete as required. |
| 30 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304) |
| 31 | S/F of MS double door hose box made of 16 gauge ( mini) MS sheet with size of 750mmx600mmx250mm including handle and lock red colour powder coated paint suitable for 2 no.RRL pipe and 1 no. short branch pipe complete in all respect as required. |
| 32 | Dismentling and shifting (within 500m horizontal distance) of old/unusable surface mounted fire hydrant 80mm/100mm/150mm/200mm size pipe including internal/ hydrant valve/hose reel complete in all respect as required. |
| 33 | Dismentling and shifting (within 500m horizontal distance) of old/unusable/defective surface mounted fire hydrant valve/nrv/panel/hose reel/hose box complete in all respect as required. |
| 34 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories,mountings and internal wiring, earth terminals, numbering etc. complete in all respect,suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWDspecification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :A MaterialsINCOMING 250A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switchDigital Ammeter (0-250 A) with selector swtich &CTs etc.LED type RYB phase indicating lamps, ON,OFF, trip indicating lamps Set of Copper Bus Bar 300AOUTGOING ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches,and LED type ON, OFF, trip indicating lamps)Main Fire Pump 125 A, 50kA TPN MCCB, Ics=100% Icu, withfully automatic Star/Delta starter suitable for 60HP pump with overload protection, currentsensing type single phase preventor completewith all acceessories and internal wiring requiredfor automatic operation, selector switch forlocal/remote, auto/manual/OFF operation. |
| 35 | Jockey Pump 63 A, 50kA TPN MCCB, Ics=100% Icu, withsuitable HP fully automatic Star/Delta starterwith overload protection, current sensing typesingle phase preventor complete with allacceessories and internal wiring required forautomatic operation, selector switch forlocal/remote, auto/manual/OFF operation.DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window forfault indication, complete as per specification Please Enable Macros to View BoQ information |