| 1 | Wiring for light point/exhaust fan point with (P+N) 2x1.5 Sq.mm FRLS-H (Polycab/Havells/Finolex/Apar/ Grandlay/ Eq.make as approved by site engineer ) PVC insulated copper conductor single core cable in surface/recessed conduits (Anchor/Polycab/Ravindra/Equivalent make as approved site engineer), with 6 Amp modular switch (Anchor Roma Urban/Legrand/SSK NV/ABB/Equivalent make), modular plate, cover in front and suitable GI Box of approved quality and makeISO/IEC (Quality of wire shall be apprroved before execution of work by site in charge engineer strictly as required) plus/ABB/Eq.Make & job including cost of circuit wire 2.5 Sqmm multistrand copper wire from switch board to distribution board complete including cost of conduit. |
| 2 | Wiring for Celling fan point with P+N] 2X 1.5 sq mm FRLSH Polycab/Havells/Finolex/Apar/ Grandlay/ eqt make as approved by site engineer, PVC Insulated Copper conductor single core cable in surface/recessed Conduits, 1 No. 6Amp modular switch(Anchor rama urban/legrand/SSK NV/ABB/equivalent make as approved by site engineer), modular plate, and suitable GI box , Two Module Steppeid Type Electronic fan Regulator of approved quality and make ISO/IEC Certified (wire shall be approved before execution of wok by SITE In-charge Engineer strictly as required) including cost of Circuit Wire in 2.5 Sq.mm Multi-strand copper wire complete |
| 3 | Wiring for Power Plug with (P+N+E) 3x4 sq.mm FRLS-H ( Polycab/Havells/Finolex/Apar/ Grandlay/ eqt make as approved by site engineer)PVCinsulated Multi strand Copper Conductor single core cable in surface/Recessed Condult (Anchor/polycab/Ravindra/equivalent make as approved by site engineer) along with 1 x 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop Earthing of approved quality and ISI marked as required. With. 1NO. 16Amp Modular switch(Anchor roma urban/legrand/55X NV/ABB/equivalent make as approved by site engineer), Modular 1NO.3-PIN. 16 Amp. Socket, Modular plate, cover and suitable GI box as required. |
| 4 | Wiring for 6Amp Plug with(P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Polycab/Havells/Finolex/ Apar/ Grandlay/ Equivalent make as approved by site engineer) Insulated Mulli strand Copper Conductor single core cable In surface/Recessed Conduit along with 1 x 2.5 sq.mm FRLSH Polycab/Havells/Finolex/eqt make as approved by site Engineer) PVC Insulated copper conductor single core cable for loop Earthing of approved quality and ISI marked as required, with 2 No.6Amp Modular switch(Anchor roma urban/legrand/SSK NV/ABB equivalent make as approved by site engineer), 2, 2 NO. Modular 6 Amp. 5-Pin Socket 6-8 Module Modular grid plate, cover and suitable Gl box etc as required |
| 5 | Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLSH PVC Insulated copper conductor, single core Cable in surface/Recessed medium class PVC condult as required. (wire shall be approved before execution of wok by SITE In-charge Engineer strictly. Incl. cost of conduit |
| 6 | 2X 10sq. MM+ 1 X 10 sq. MM (Phase +N+E) Power point Sub main in One run from Main Panel to. Distribution boards(Polycab/Havells/Finolex/Apar/ Grandlay/ eqt make) |
| 7 | 2X6 SQ MM 1X6. SQ.MM [Phase +N+E] For Lighting/inverter 5 Sub main in one sun from Main Panel to Distribution board (Polycab/Havells/Finolex/ Apar/ Grandlay/ eqt make |
| 8 | 2X4 SQ. MM 1X4.SQ.MM [Phase +N+E) For AC, Sub main in one run from Main Panel to Distribution board (Polycab/Havells/Finolex/Apar/ Grandlay/ eq. make |
| 9 | Supplying and fixing of 6Amp to 32Amp Rating, 240v, \\"C\\" Curve Miniature Circuit Breaker suitable for inductive load of following poles in existing DB. Complete with connections, testing and commissioning etc as required |
| 10 | SINGLE POLE (6-32Amp) Legrand /Havells or L&T /Schneider/ABB/ eq. make to be approved by EIC |
| 11 | Supplying and fixing following rating, Double pole, (P +N) 240 V, C Curve MCB in the MCB DB complete with connections, testing and commissioning, etc. as reqd. |
| 12 | 40Amp. Legrand/Havells or L&T /Schneider/AB/Siemens/ Eq. make to be approved by EIC |
| 13 | 63 Amp. Legrand/Havells or L&T/Schneider/ABB/Siemens / Eq. make to be approved by EIC |
| 14 | Supplying and fixing following way, Triple pole and neutral, sheet steel, MCB distribution board, (Havell/legrand/Scheinider/SSK/ABB/Eq. make) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) |
| 15 | 6 way, Double door |
| 16 | 4 way, Double door |
| 17 | SITC of 32A Industrial type metal clad AC Box socket outlet with Inter connections in heavy gauge powder coated duly fitted on wall with 40 Amp D.P MCB and 240 A 3 pin plug top complete with connections |
| 18 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER Rod EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value .Supplying, Installation and Testing of 75 mm copper Pipe Filled with Crystallineconductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 2OMM Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through DWC High Density Poly ethylene Pipe having Corrugation complete job |
| 19 | Supply installation testing and commissiening of 18 W+ LED Surface Mounted Panel light luminary fitting round shape with minimum system lumen efficacy of 120 lm/W with Pressure Die cast Aluminium Heat Sink and P.F>0.95, THO<10%, CCT 5700K, CRI 80. The LED with Useful life of 50000 Hrs at 170.. The Input voltage range shall be 150V to 270V The Flixture should have in bullt Surge 10 Protection of 2kV. Certificatlon:- LM79 & LM80 test report should be from govt approved In-house NABL lala/ government of India authorised lab. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Tovo years, which includes replacement of fixtures of Philps or Havel's or Wipro or Halonix or Eq. make |
| 20 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 nos. blades, 30 cm long down rod, 2nos, canopies, shackle kit, Power Factor not less than 0.9, Service Value including sallety pin, nut bolts, washers, temperature rise-75 degrce C (max.), insulation resistance more than 2 mega chin, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havels/Polycab/Eq make |
| 21 | Supply, Installation, Testing and Commissioning 320 Cum/Hr. AC 220 240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with 12 inbuilt thermo cut-off Protection and Noise Level not exceeding 37 ds of Following Sizes including connection etc. Compt 225-250mm Shutter Typed |
| 22 | Supply/Installation/Testing and Commissioning of CPRI Approved (IS/IEC:61439) Main Controlling Panel,fabricated out of heavy gauge sheet steel ,dully Painted with powder coated paint ,dust protected ,earth terminal fitted on epoxy cleats, volt meter & Ammeters with selector switch & CT Coil of required ratio with all necessary connections & inner wiring of panel on both heating and lighting circuits. The switches are connected with bus bars inside panel & manufacturer CPRI Certified.The switch are adjustable type made of Havells/ L&T/ABB/Legrand/Siemens / Eq. make to be approved by EIC and change over switch should be of Havells/ L&T/Legrand/ Schneider / Eq. make to be approved by EIC.(1) Normal Incomer:a) 250 AmpTPN MCCB with adequate breaking capacity =01 No. b) 400 Amps TPN Al. Bus Bar Set = 01 Set,Digital Voltmeter ,Ammeter ,C.T Coils with Selector Switch & Phase indicator Set.Outgoing:(1) Normal outgoing for Heating/AC/Lighting/Inverter etc load(a) 40-Amp DP MCB = 18 No. for AC's & Machine & Heating Sub Main(b) 63 Amp DP MCB = 4 No. for Heating Sub Main100 Amp Manual Changeover. |
| 23 | Supplying and fixing modular Ilarking plate on the existing modular clate and switch box excluding modular plate as required |
| 24 | Supply/Laying/Connecting and Commissioning of 185 sq.mm 3.5-Core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havells/Polycab/Eq. Make with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution) |
| 25 | Supply, Installation, testing & Commissioning of Bulk Head Fittings 16 of Havel's RUGBY Model HAVEL'S BULK HEAD Fittings with 12 watt each 175 LED Bulb at Philins never's make Providing, Laying of 25 mm dia./32mm dia 2mm thick PVC Unbreakable conduits including cost other accessories like bends Deep Junction Boxes Surface junctions etc complete |
| 26 | Providing, Laying of 25 mm dia./32mm dia 2mm thick PVC Unbreakable conduits including cost other accessories like bends Deep Junction Boxes Surface junctions etc complete (FOR Sub mains & Downs, if needed at site |
| 27 | Supplying, Installation, Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark (15:15683) suitable for \\"B' and 'C' class fires-inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires |
| 28 | Supply installation testing and commissioning of Sine Wave Inverter Capacity 10KVA, Rated Power 8400 W,Supports Four battery, 24 Month Warranty Safe for sensitive appliances with Sine wave out-put, Inverter should run heavy loads like AC, Geyser, Photocopiers, Auto over-load handling capacity Installation and maintenance friendly Offers high quality and reliable power back-up solution for office and homes, MCB for protection from Input mains, Bypass switch for supplying output directly from grid in case of Home UPS fault. Noiseless Operations with the help of low harmonic distortion, Intuitive Display to easily understand status of mains availability, battery status, etc.Comprehensive protection against short-circuit, reverse polarity, battery over-charge, deep-discharge etc.Adaptive Battery charging control system technology (ABCC) ensures faster battery charging and enhances battery life by around 70%. Supports a wide battery range, i.e. Flat Plate, Tubular & VRLA (SMF).praffered make Luminous/ Microtek/Exide.the job also includes 2 No. trollies for housing 4 No battries and inverter. |
| 29 | Supplying, Installation, Testing and Commissioning of ABC type Fire Extinguisher 4 Kg Capacity ISI Mark(IS:15683) and dully certified |
| 30 | Supply, Installation, Testing & Commissioning of 2 Ton, D.C invertor Techonology Hot and Cold Air Conditioner of Panasonic/ Godrej/ Samsung/ Daikan/ Mitsubushi/ eq. make to be approved by EIC (to provide heating as well as cooling and dehumidification) . remote controlled suitable for operation on 220-240 volt single phase AC Supply alongwith all the features that are in vogue in latest model .The job includes fitting of indoor unit on wall by employing suitable clamps and outdoor units on angle iron Stand for holding of out door unit fitted with nuts and bolts,laying of refrigerant copper piping upto 3 mtrs whereever needed, insulating the copper pipeline with nitrilic foam, topping up with refrigerant for additional length of piping etc.complete. Also, includes p/f of pvc flexible drain pipe of length 12 mts alongwith fittings. Further, it encompasses carrying out repairs to walls whereever the same are cut. The job includes p/f of relay type voltage stabilizer suitable for 2 Ton AC including AMC for a period of 2 years from the date of commissioning |
| 31 | Supply ,installation ,testing , &commissioning of 40 KVA 3 -Phase SERVO controlled VOLTAGE Stabilizer of Approved brand with following SPECIFICATIONS :(1). INPUT VOLTAGE: 156 Volt -430 Volts (2). OUT PUT VOLTAGE : 430Volts+ 1% (3).Winding Material Insulation : 99.97% PURE COPPER WOUND FIBER GLASS (4). IN DOOR TYPE(5). COOLING :OIL 1S 335(6).MICRO CONTROLLED TRUE RMS Based LCD display (7). Protections are Over Load COPPER wound of /Chinar / Electric Field /Alba /AE /Cosco etc ISI/1SO certified for smooth functioning/ constant voltage supply having Technical Specifications : Input voltage= 156-430 volts & output voltage=430 volts+ - 1% Buck Boost Transformer Copper wound 99.9% ,OIL Immersed COOLING OIL ,High cut/Low Cut /Time delay / Over Cut through Micro Control and Spike Protection including ,Carriages ,installation charges , testing & taxes complete job alongwith servo bypass switch of adequate rating including AMC for 2 years Please Enable Macros to View BoQ information |