| 1 | 1. Electrification. |
| 2 | 90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point |
| 3 | 90.15.4.5:Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 4 | 90.15.4.6:Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 5 | OD502859/2025-2026:Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 200 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230V single phase A/C. |
| 6 | 90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 7 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 8 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 9 | OD502860/2025-2026:Supply and providing every additional length of down rod of 15mm heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required. |
| 10 | 90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm |
| 11 | 1.17.13:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm |
| 12 | 1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 13 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 14 | 90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43) |
| 15 | OD502864/2025-2026:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2 metre long etc. with charcoal/ coke as required. |
| 16 | OD502862/2025-2026:Supply and providing earth lead from the test joint to the earth electrode using 25 x 3 mm GI strip of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate,test joint etc. as required. |
| 17 | OD502863/2025-2026:Providing and fixing 2x25mmx 3mm GI strip test joint for earthing system. |
| 18 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 19 | 90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class) |
| 20 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 21 | OD502861/2025-2026:Supply and providing 25 x 6 mm brass nut and bolt etc.as required. |
| 22 | OD502905/2025-2026:Supply & installation of dust and vermin proof, 1 Phase Sintex Meter Board (GS-MB- 3527 (350x270x200) including providing and fixing 32 A HRC Fuse Base with HRC Fuse link, 32 A neutral link and to fix KSEB meters, etc. as required including fixing it on wall, making good the damages color washing etc. as required. Please Enable Macros to View BoQ information |