| 1 | M&L for earthing with galvanized steel earth plate electrode 600x600x6mm size burried directly in ground to depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, including provision of galvanized earth strip 32 x 6mm connected by means of bolts, nuts, check nuts and washers of galvanized iron or steel, provision of 40mm dia GI pipe medium grade for earth strip protection connected from earth plate electrode to main switch board, provision of 20mm dia GI pipe perforated medium grade for watering arrangement and PCC 1:3:6 type C1 chamber, MS funnel, wire mesh, 50mm thick RCC 1:2:4 type B1 for earth pit cover with 6 Nos, 8mm dia high strength deformed steel TMT bars on both ways, including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to a distance n.exc.50m, provision of charcoal and salt complete all as shown in electrical plate No.3 of Schedule Part-I 2009 incl taking down unserviceable earthing pit complete all as specified and directed and testing and recorded resistence in Ohm on completion.Note:- (i) Cost of GI earth strip/wire and GI protection pipe upto 7.5 Mtr length shall abe deemed to be included in the rate quoted for this item.(ii) The unit rate shall also includes for Wire mesh, funnel, excavation,returninng & filling, PCC chamber pit,RCC cover complete |
| 2 | M&L for earthing with copper earth plate electrode 600x600x3.15mm size burried directly in ground to depth not less than 2.25m below ground level with top edge of the plate not less than 1.5 mtr below normal ground level surrounded with char coal and common salt filling in alternative layers of 15cm thick and connected to copper earth strip 25 x3.15 mm by means of nuts/bolts and washers etc made out of galvanized iron including 40mm dia GI pipe light grade for protection of earth strip from earth electrode to test point 20mm dia GI pipe medium grade connected to funnel heavy wire mesh for watering purpose including necessary excavation and earth work PCC (1:2:4) type B1 for earth pit 10mm thick cast iron cover with angle iron frame all as specified and shown in electric plate Nos No.3 of Schedule Part-I 2009 incl taking down unserviceable earthing pit complete all as specified and directed and testing and recorded resistence in Ohm on completion.Note:- (i) Cost of GI earth strip/wire and GI protection pipe upto 7.5 Mtr length shall abe deemed to be included in the rate quoted for this item.(ii) The unit rate shall also includes for Wire mesh, funnel, excavation,returninng & filling, PCC chamber pit,RCC cover complete. |
| 3 | Taking down old complete and M&L labour for earthing complete with galvanised mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level steel earth plate connected with GI wire 04 mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipe medium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion complete all as specified and directed. Note : (i) Cost of GI earth strip and GI protection pipe upto 7.5 Mtr length shall be deemed to be included in the rate quoted for this item.(ii) The unit rate shall also includes for Wire mesh, funnel, excavation,returninng & filling, PCC chamber pit,RCC cover complete. |
| 4 | Taking down old and supply & fix test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm, drilled and screwed including 3 nos. 8 mm dia 25 mm long hex. Head screw incl , all as specified and as directed incl taking down old test point all as specified and directed.. |
| 5 | Taking down old and Supply & fixing Air termination, single pointed aluminium rod 12mm dia and 300mm long including making mounting base, complete suitable for fixed properly on top of the roof of building/ESHs at any height complete all as specified and as directed . |
| 6 | Supply and fixing in replacement of Aluminium strip 25 x 3.15mm with and including ceramic/porcelain vitreous insulator (at not more than 100cm c/c) for base of suitable size and saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface or drawn through pipe as earth grid and down conductor of lightening protection system of building/ESHs at any height complete all as specified and as directed by Engineer-in-Charge. |
| 7 | Supply and fix in Replacement of copper strip 20 x 3.15 mm including ceramic/porcelain vitreous insulator (at not more than 100cm c/c) for base of suitable size and saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface or drawn through pipe as earth grid and down conductor of lightening protection system of building/ESHs at any height complete all as specified and as directed by Engineer-in-Charge. |
| 8 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 32 x 6mm galvanised iron strip complete with taking down old all as specified and directed. |
| 9 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 25x4mm galvanised iron strip complete with taking down old all as specified and directed. |
| 10 | Supply and fixing white porcelain ceramic insulator with nut, bolt and washers for fixing eathing strip on wall/ceiling/roof all as directed incl taking down old unserviceable insulator complete all as specified and directed. |
| 11 | Re-Fixing and alignment of existing serviceable aluminium strip of any size , after proper cleaning the terminals with and including new vitreous ceramic/ procelein/ bakelite insulator (at not more than 100cm c/c) for base, saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface as earth grid and down conductor of lightening protection system of MSL shed building at any height complete all as specified and as directed by Engineer-in-Charge. |
| 12 | Re-Fixing and alignment of existing serviceable Copper strip of any size fallen on ground , after proper cleaning the terminals with and including new vitreous ceramic/ procelein/ bakelite insulator (at not more than 100cm c/c) for base, saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface as earth grid and down conductor of lightening protection system and inside and ouside of MSL shed building at any height complete all as specified and as directed by Engineer-in-Charge. |
| 13 | M&L for New earthing pit by making cement concrete pit PCC 1:3:6 type C2 with RCC precast slab 80mm thick with handle for lifting made out of 8 mm dia MS rod specified in plate No -02 of SSR part-I after incl dismantling of broken pit one complete all as specified and directed. |
| 14 | Material and labour for repairing of lightning conductor & air termination rod single or multi pointed of any type and size including dismantling of the full set and refixing after cleaning, replacing nut bolts, making straight of GI pipes, refixing of clamps and nut bolts, fixing of earth strip with proper welding/jointing by nut bolts without any loose joints, replacing of defective/broken saddle piece of any size and type and from air termination point upto earth pit, re-allignment of earth strip by fixing it on wall and reparing of disturbed portion and making good as per existing complete all as specified and directed. |
| 15 | Material and labour for cleaning the chamber of the earth pit, the vegetation/surplus soil around the earth pits upto 1.00 mtr all around the pit, replacing the rusted earthing leads/funnel / mesh with new ones etc cleaning with iron wire brush complete all as specified and directed. |
| 16 | M&L for testing of earthing (in Half Yearly Ending June and Dec ) inside/outside Depot Area after disconnecting from test point and other loops , testing by using ISI marked digital/Analog earth tester of reputed make and test result shall be entered in a Earth Testing register and put up to the Engr-in-Charge after testing complete, if required before testing the re-activating of earth pit using suitable measures as required to bring the results within the limits of 1 /2/3 ohm , also complete all as specified & as directed.NOTE :i) All materials required for re-activation of earthing pit will be measured and paid separately under supplied only of respective item of schedule. ii) The resistance test of earth pits to be carried out in dry season only.iii) Contractor has to submit the satisfactory earth test result duly countersigned by Engineer-in-Charge (iv) Earth tester or any other T&P will be scope of the contractor . |
| 17 | Supply only common salt for earth pit. |
| 18 | Supply only magnesium sulphate for earth pt. |
| 19 | Supply only Water Funnel as per existing |
| 20 | Supply & fixing in replacement of GI pipe 2.0 RM long medium grade vertically fixed by means of PCC 1:2:4 of size 1.5'x1.5'x1' for mounting of Copper air termination rod complete all as specified & as directed. |
| 21 | Supply and fix in repair SMC Junction box of size 200x140 x100mm made of poly carbonate for fitting of earth Test point mounted with made out of 2mm thick hot dip galvanized sheet drilled and screwed including 6 Nos 15mm long hexagonal head screws complete Please Enable Macros to View BoQ information |
| 22 | Supply and fix in repair SMC Junction box of size 200x140 x100mm made of poly carbonate for fitting of earth Test point mounted with made out of 2mm thick hot dip galvanized sheet drilled and screwed including 6 Nos 15mm long hexagonal head screws complete Please Enable Macros to View BoQ information |