| 1 | Supply, Installation, Testing & Commissioning of factory fitted mircoprocessor based self diagnostic auto check VRV/VRF system outdoor unit equiped with PCBs, accumulator, oil seperator, burshless DC inverter fan motor, OEM self manufactured hermetic sealed multi valve scroll type compressors. Compressor should be based on low pressure shell technology for longer life with integrated IPM & PWM to ensure effective operation even at low/partial load conditions for better efficiencies. Compressor shall be fixed in metallic chamber for lower noise with enhanced fire saftey protection. Outdoor unit shall be equiped with highly efficient induction type heater using eliminated wasted heat. VRT/VET system shall be based on advanced & automatically modulation evaporating refrigerant temperature between 0°C to 11°C for instant cooling and better energy effiency as per user's demand. Outdoor units shall be essentially equiped with saftey devices like fuse, noise filter PCB, low pressure switch, high pressure switch, pulse based LEV for optimized refrigerant flow control, isolating valve, protective corrosion resistant polyster coating on panels, hydrophilic coating on Aluminium fins, protective polyeurethane coating on PCB, OEM provided Inbuilt automatic reverse phase detector & sequencer/corrector to avoid any kind of failure due to phase sequence reversal which makes system relaible and redundant. Heat exchanger must be essentially equiped with internally grovved copper tubes for better heat exchange performance and operate in extreme conditions i.e. even at ambient temparature of 52°C or more. Outdoor units shall be pre-charged with R401A gas, pump down fucntion and shall also be equipped with charging valve/ports for additional charge of refrigerant as per site requirement. All outdoor unit shall be able to perform in duty cycle mode to optimize wear and tear of system when more than one outdoor unit is connected to a circuit. Outdoor units must also be equiped with four way valve for necessary provision of heating during winters. All outdoor shall have approximately following as per OEM standards rated capacities at ARI conditions and, with the criteria of delivering 95% capacity at 43 °C being most likey temperature to occur during summers.to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. Make : O General, Mitsubishi, Daikin. |
| 2 | Outdoor Unit per HP |
| 3 | Supplying, Installation, Testing and Commissioning of following minimum capacity and external static pressure VRF/VRV ceilingmounted mid high static ductable type Indoor unit equipped with washable synthetic media prefilter, fan sectionwith low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor) High Static Ductable units (minimum 49 to 77 pascal external static pressure) to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax, sale tax Gst or other taxes as imposed by the Govt time to time where applicalble . Make :- Daikin/O General/ Mitsubishi |
| 4 | Ductable Type Indoor Unit 5.5 TR High Static Ductable units (minimum 78 pascal external static pressure) |
| 5 | Ductable Type Indoor Unit - 4.0 TR |
| 6 | Supply, Installation, Testing and Commissioning of The Double Skin Modular Air Handling Unit is designed based on modular paneling concept to fulfill the indoor air quality requirement. Technical for Ceiling Suspended AHUs, 0.6 mm pre coated sheet outside , 0.6 mm plain GI sheet inside, 25 mm panel non thermal break aluminium profile , Static pressure 40 mm (TSP), Pre Filter 10, micron efficiency , 4 RD DX cooling coil , forward curve fan with IE 2 motor complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. Make : System Air / Zeco Aircon / Edge Tech / Flaktwood / VTS Ventus |
| 7 | AHU - (2000 CFM) |
| 8 | AHU - (4000 CFM) |
| 9 | AHU - (6000 CFM) |
| 10 | Supply and installation of Refrigerant Piping Y/T-Joints or Headers as required to connect theabove outdoor units and indoor units. ( liquid and gas line as one set)o complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 11 | Supply and installation of Refrigerant Piping Tuning Kit Joints or Headers as required to connect theabove outdoor units ( liquid and gas line as one set)to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 12 | Supply installation testing and commissioning of Centralized Remote Controller to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 13 | SITC of PVC (Minimum 15 Kg/Sqcm pressure rated) Drain Water Piping complete with fittings (elbows, tees, reducers, sockets etc.), supports, jointing and any other item required to make the system complete. Nominal Diameters of Pipes in mm as indicated below: to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.Make:-Supreme/ AKG/ Vectus |
| 14 | 25 mm ( with 9 mm Class- O XLPE) |
| 15 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cellelastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble . Make: Maxflow/Rajco/Mandev/Jobu/Hariom |
| 16 | 34.9 dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 17 | 31.8 dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 18 | 28.58 dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 19 | 25.4 dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 20 | 22.2 dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 21 | 19.1dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 22 | 15.86 dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 23 | 12.7 dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 24 | 9.5 dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 25 | CONTROL CABLING |
| 26 | Providing, laying and fixing of PVC round sheathed 2 core 1.5 sqmm FRLS copper conductor flexible cable for voltage grade up to 1100 volt , as required complete in all respect. to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.Make :-Finolex/Havell/Polycab/KEI |
| 27 | Supplying and fixing of following sizes of heavy class FRLS PVC conduit along with accessories insurface/recess including painting in case of surface conduit, or cutting the walland making good the same in case of recessed conduit as required.to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.MAKE:- BEC/DIPLAST/POLYCAB/ NIC |
| 28 | Supply and fixing of perforated of indicated thick CRCA GI perforated cable tray painted of required colour, of following sizes complete with bends/tee joints, coupling plate & nuts bolts etc. including Supporting structure as per specification complete as required.to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 29 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 30 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 31 | Supply and installation of AHU Panel with contactor 32 Amp 3 Phase to connect the above outdoor units and indoor units. ( liquid and gas line as one set)to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work:-Make of switchgear:- L&T/ABB/ Hager/ Legrand |
| 32 | Supply and installation of AHU Kits to connect the Unitsabove outdoor units and indoor units. ( liquid and gas line as one set)to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 33 | Supply, fabrication, installation, balancing and commissioning of site fabricated MS Galvanized 24 Gauge rectangular/spiral oval ducting complete with neoprene rubber gaskets, elbows, hangers, Thread road, c-channel, anchor fastner supports etc. as per approved drawings and specifications of following gauges.to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.make :-Sail/Tata steel/jindal |
| 34 | Supply and Installation of Nitral inslulation 12mm Thickness as per specification complete as required.to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.Make:-Armaflex/Aerocell/Supreme/A-flex |
| 35 | Supply and installation of Canvas Connection for supply and return Air for ductable and AHU to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 36 | Supply and installation of Alluminum Air Supply and Return grills Size (600 X 600 MM)to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. make:- Caryaire/Conaire/Dynacraft/Systemair |
| 37 | Supply and fixing of Square Dampers (500 X 500)MM) for Controller the air throw to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work.make:-Honeywell / Siemens / Johnson controls / Belimo |
| 38 | Earthing and lightening arrestor Earthing with Gl earth plate 600mm x 600mm x 6mm thick including accessories and providing masonary enclosures with cover plate having locking arrangement and watering pipe etc (but without charcoal or coke and salt) complete as required to complete the job including five year on site warranty. The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble The system shall be compatible with BMS and contractor shall submit shop drawings before starting the work. |
| 39 | Axial Flow Fans |
| 40 | Supplying, Installing, Testing and Commissioning of AMCA Certified (Air perfromance) Vane Axial flow fan for exhaust suitable for Horizontal/Vertical installation. The motor shall be suitable for 415±10%, three phase. The SP of the fan should be checked by vendor and motor should be selected accordingly prior to award of contract. The fans shall have GI weldmesh inlet guard, back draft dampers etc. as part of unit prices. Thickness of the casing shall not be less than: For Dia (300 to 650) mm – 2mm, Dia (700 to 1140) mm – 3 mm, Dia (1200 to 1400) mm – 4mm & Dia 1600 – 5 mm. The Fans shall be installed with vibration isolators of suitable rating.including five year warranty The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble make:- Nicotra / Kruger / Flaktwoods / Green Huck |
| 41 | For all Fire Rated Fans as mentioned, Fan and Motor shall be suitable for operation at minimum 250 deg C for 2 hrs. Certificate of conformity for 250 deg for 2 hours operation as per BSEN 12101-3 : 2015 issued by Internationally recognized Independent Fire Laboratory (TUV SUD Singapore/UL/CE) should be submitted alongwith type test report. |
| 42 | All fans should have fire retardant flexible canvas connection at the inlet and outlet . The cost should include in the cost . |
| 43 | All ceiling suspended fans shall have vibration isolator as a part of unit price. |
| 44 | All floor mounted fans shall have vibration pads as a part of unit price. |
| 45 | 2000(Two thousand) CFM; SP 15 mm of wg; Power 0.75 KW, 4 Pole, 450 mm dia for Ladies / Gents Change Room Exhaust - GF (Axial ) |
| 46 | 9000(Nine thousand) CFM; SP 10 mm of wg; Power 2.25 KW, 4 Pole, 710 mm dia for - Liftwell Pressurisation (Axial) |
| 47 | 10500(Ten thousand five hundred) CFM; SP 10 mm of wg; Power 3.75 KW,4 Pole, 710 mm dia for - Staircase Pressurization (Axial ) |
| 48 | All the fans shall be AMCA Certified/Equivalent for air. |
| 49 | The outlet velocity of normal exhaust/ fresh air fans should not exceed 16m /s |
| 50 | The sound level of fans should be within 65 dB for fans <8000 CFM 75 dB for fans between 8000-20000 CFM and within 80 db for fans between 20001-40000 CFM and within 83 db for fans >40000 CFM. Db level to be measured at 3m distance.(unless specified in line item) |
| 51 | The motors shall be with IE-2/IE-3 Effeciency and suitable to operate through VFD if required. EFF> 85% for Motor >3HP, EFF>78% for Motor <3HP |
| 52 | All Exhaust / Fresh Air fans shall have back draft dampers inbuilt in the cost of the fan |
| 53 | The efficiency of all fans should be > 65%.preference to fans with > 70% eff will be given |
| 54 | The pole for this fan should be suitably selected to meet all parameters as mentioned above.The RPM, dia. should be selected suitably to match the KW, Efficiency and Noise Requirements. |
| 55 | All ceiling suspended fans shall have spring type vibration isolator of suitable ring as part of unit price. |
| 56 | All floor mounted fan shall have spring type vibration isolators of suitable rating as part of unit price. |
| 57 | Total |
| 58 | Comprehensive Annual maintenance contract of whole VRV/VRF system including comprehensive maintenance of All Cassette and hi wall Units complete including servicing, repair/ replacement of all defective spare parts blower motor, compressor, gas charging etc as required to running the system in working condition .Attending to any number of breakdowns calls during normal working hours on all working days.Providing of four quarterly preventive services mandatory.inclusive of Refrigerant gas charging or topping up during leakage repairing .All the equipment’s/installations shall always be kept in good and trouble-free operating conditions.The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble .Comprehensive Annual maintenance contract 2nd year after one year warranty period. |
| 59 | Comprehensive Annual maintenance contract of whole VRV/VRF system including comprehensive maintenance of All Cassette and hi wall Units complete including servicing, repair/ replacement of all defective spare parts blower motor, compressor, gas charging etc as required to running the system in working condition .Attending to any number of breakdowns calls during normal working hours on all working days.Providing of four quarterly preventive services mandatory.inclusive of Refrigerant gas charging or topping up during leakage repairing .All the equipment’s/installations shall always be kept in good and trouble-free operating conditions.The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble . Comprehensive Annual maintenance contract for 3rd year |
| 60 | Comprehensive Annual maintenance contract of whole VRV/VRF system including comprehensive maintenance of All Cassette and hi wall Units complete including servicing, repair/ replacement of all defective spare parts blower motor, compressor, gas charging etc as required to running the system in working condition .Attending to any number of breakdowns calls during normal working hours on all working days.Providing of four quarterly preventive services mandatory.inclusive of Refrigerant gas charging or topping up during leakage repairing .All the equipment’s/installations shall always be kept in good and trouble-free operating conditions.The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble . Comprehensive Annual maintenance contract for 4th year |
| 61 | Comprehensive Annual maintenance contract of whole VRV/VRF system including comprehensive maintenance of All Cassette and hi wall Units complete including servicing, repair/ replacement of all defective spare parts blower motor, compressor, gas charging etc as required to running the system in working condition .Attending to any number of breakdowns calls during normal working hours on all working days.Providing of four quarterly preventive services mandatory.inclusive of Refrigerant gas charging or topping up during leakage repairing .All the equipment’s/installations shall always be kept in good and trouble-free operating conditions.The rates are inclusive of carriage of materials within all leads and lifts and all taxes of octroi ,royality, malkana, toll tax,sale tax Gst or other taxes as imposed by the Govt time to time where applicalble .Comprehensive Annual maintenance contract for fifth year Please Enable Macros to View BoQ information |