Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-06-2026 | datecorrigendum | Date | 02-07-2026 |
| 2 | 18-06-2026 | drgcorr | Other | 02-07-2026 |
| 3 | 18-06-2026 | drgcorrigendum | Other | 02-07-2026 |
| 4 | 18-06-2026 | amendment2 | Other | 02-07-2026 |
| 5 | 18-06-2026 | BOQ | BOQ | 02-07-2026 |
| 6 | 09-06-2026 | Corrigendum1 | Date | 26-06-2026 |
| Sl. No. | Item Description |
| 1 | Lumpsum price worked out by the tenderer for BUILDINGS / STRUCTURES as listed in Schedule ‘A’ Part-I |
| 2 | Lumpsum price worked out by the tenderer for SITE CLEARENCE AND DEVELOPMENT as listed in Schedule ‘A’ Part-II |
| 3 | Lumpsum price worked out by the tenderer for INTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part-III |
| 4 | Lumpsum price worked out by the tenderer for INTERNAL ELECTRIC SUPPLY as listed in Schedule ‘A’ Part-IV |
| 5 | Lumpsum price worked out by the tenderer for ROADS/PATH/CULVERT as listed in Schedule ‘A’ Part-V |
| 6 | Lumpsum price worked out by the tenderer for AREA DRINAGE as listed in Schedule ‘A’ Part-VII |
| 7 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ EXTERNAL WATER SUPPLY Part-VIII |
| 8 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ EXTERNAL ELECTRIC SUPPLY Part-IX |
| 9 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ FIRE FIGHTING Part-X |
| 10 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ LIGHTENING PROTECTION Part-XI |
| 11 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ HOT WATER SUPPLY Part-XII |
| 12 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ RAIN WATER HARVESTING Part-XIII |
| 13 | Lumpsum price worked out by the tenderer for as listed in Schedule ‘A’ LIFT Part-XIV |
| 14 | SCHEDULE 'A' PART XV (MISCELLANEOUS ITEMS)Note: This schedule is not pre-priced by MES |
| 15 | SEWAGE DISPOSAL |
| 16 | DCWPE (SN8) 180 (OD)/ 163 (ID) mm diameter pipes laid on 150 mm thick bed complete all as specified and directed. |
| 17 | INTERNAL WATER SUPPLY |
| 18 | S & F 15 mm bore Push cock for urinal for iron pipe and fixed( 1.5 LPM)Make - Jaquar Model No PRS-CHR-073 orMake - GROHE Model No37396000 orMake - Cera Model No F8010109 or equivalent |
| 19 | Supply & Fixing Health faucet (ABS Body) mild steel chromium plated suitable 15 mm dia pipe with 1.25 meter long flexible tube and ABS wall hook with including making connections and fixed in position complete in all respect as specified ) with 1 mtr, flexible pipe 15 mm bore ( braided tube) & hook,complete all as specified & as direcetd. Make - Jaquar Model No KUP-35041PMGE orMake - Hindware Italian Collection Model No F160192CP Make - Kohler Model No K-12925IN-CP or equivalent |
| 20 | S&F Two way bib cock chromium plated with wall flange quarter turn (Low-flow) 16 mm dia. complete all as specified and directed by Engineer-in-Charge Make - Jaquar Model No KUP-35041PMGE (1.3 LPM) orMake - Hindware Italian Collection Model No F260003CP Make - Kohler Model No 25432IN-4-CP or equivalent |
| 21 | Supply & Fixing Pillar taps/cock cast copper alloy with capstan head,chromium plated ,fancy type screwed down high pressure with or without lettered \\"Hot or Cold\\",complete all as specified & as directed for 15 mm bore dia of pipe.Make - Jaquar Model No. KUP-35001 PMG (2.5 LPM) orMake - Hindware Italian Collection Model No F360001CP Make - Kohler Model No K-27484IN-4-CP or equivalent |
| 22 | INTERNAL ELECTRIC SUPPLY |
| 23 | S & F 3 pin 3-phase (2P+E) type 16A switch socket, Gas groups IIA/IIB made of AI Die Cast, Ingress Protection IP66, Temperature class T6, Class Zone 1 & 2. Certification CIMFR Dhanbad & PESO Nagpur, conforming to IS 1293:2005 complete all as specified and directed by the engineer-in-charge. |
| 24 | S & F modulae type 1 module co-axial type TV socket all as specified and directed by the engineer in charge. |
| 25 | Supply and fixing load line distribution board TPN vertical, 4 way double door type, fixed on wall semi flush with incoming MCCB 4 poles and, busbars, neutral link, blanking plates complete with all accessories all as specified and as directed by Engineer-in-charge. |
| 26 | S & F MCCB for conforming to IS/IEC 60898-1-2002, having breaking capacity Icn= 16kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shuttera, etc. complete all as specified in IS 732:2019 and directed by the engineer-in-charge. 32A,415V,50Hz,4P MCCB |
| 27 | S & F 1 X 20 Watt Flameproof / Weatherproof LED Tubelight capable of delivering 100 Lumen per watt, input Voltage - 220-240V AC, input frequency 50 - 60 Hz, Surge Voltage protection - 4KVA, CCT - 5500 TO 6500K, CRI ˃ 70%, Glass type - Borosilicate, Gasket O Ring endless neoprene rubber Gasket, Wire Guard Mild Steel Cable entriesM20 - 2 NOS material of construction - AI Die Cast, Area of classification IP66, Temperature class T6, Certification CIMFR & PESO including electrical connection with flexible steel conduit including providing of suitable SS gland to the fixture complete all as specified and directed by the engineer - in - charge. |
| 28 | S & F 6W LED study lamp light having Luminous efficacy of > 100 input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed by the engineer-in-charge. |
| 29 | S & F 12W LED study lamp light having Luminous efficacy of > 100 input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed by the engineer-in-charge. |
| 30 | S & F 40 W security light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 2600 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885(Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressuer die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top openning for easy maintenance, suitable for side entry, wall mounting with bracket arm OD 35 mm to 42mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete in all respect as specified and directed by engineer-in-charge. |
| 31 | Supply and fix Wall Mounting Fan, steel body AC single Phase, 230V, With Sweep size, 450mm; Motor Speed 84 CMM, 3 blades, and frame and louvers complete all as specified and directed by engineer-in-charge. |
| 32 | Supply and fix flameproof exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep with, blades, and frame and louvers, Gas groups IIA/IIB made of AI Die Cast, Ingress Protection IP66, Temperature class Zone 1 & 2. Certification CIMFR Dhanbad & PESO Nagpur, conforming to IS 1293 : 2005 complete all as specified and directed by the engineer-in-charge. |
| 33 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type BUILDING PANEL ( MDB-L & W) (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required rating , conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to al internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1;6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade wit necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.MAKE: Schneider, Siemens, ABBThe BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 80A, covered with PVC insulated sleeves including insulator, nuts,bolts, etc. with complete connection [B] INCOMING |
| 34 | [i] 63A, 415 V, Ics = 100 % Ics = 16kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [ii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts-01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING[i] 32A, 415 V, Ics = 100 % Ics = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-06 Nos. [ii] LED phase indicators ( Red, Yellow, Blue)-06 Set |
| 35 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type BUILDING PANEL ( CDB-1) (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required rating , conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to al internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1;6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade wit necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.MAKE: Schneider, Siemens, ABBThe BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 80A, covered with PVC insulated sleeves including insulator, nuts,bolts, etc. with complete connection [B] INCOMING |
| 36 | [i] 63A, 415 V, Ics = 100 % Ics = 16kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [ii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts-01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING[i] 63A, 415 V, Ics = 100 % Ics = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. |
| 37 | [ii] 40A, 230V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [iii] 20A, 230V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. LED phase indicators (Red, Yellow, Blue) -1 Set |
| 38 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type UTILITY PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required rating , conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to al internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1;6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade wit necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.MAKE: Schneider, Siemens, ABBThe BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 50A, covered with PVC insulated sleeves including insulator, nuts,bolts, etc. with complete connection [B] INCOMING |
| 39 | [i] 40A, 415 V, Ics = 100 % Ics = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [ii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts-01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING[i] 32A, 415 V, Ics = 100 % Ics = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. LED phase indicators (Red, Yellow, Blue) -2 Set |
| 40 | [ii]16A, 415V, Ics = 100% Icu = 16 kA, 50 Hz 2P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. LED phase indicators (Red, Yellow, Blue) -1 Set[iii] 16A, 415V, Ics = 100% Icu = 10 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. |
| 41 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type FIRE FIGHTING PANEL (MCC-1) (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required rating , conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to al internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1;6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade wit necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.MAKE: Schneider, Siemens, ABBThe BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 40A, covered with PVC insulated sleeves including insulator, nuts,bolts, etc. with complete connection [B] INCOMING |
| 42 | [i] 32A, 415 V, Ics = 100 % Ics = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [ii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts-01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING[i] 25A, 415 V, Ics = 100 % Ics = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [iii] 10kw Dol Startor - 02 Nos[v] LED phase indicators (Red, Yellow, Blue) -2 Set |
| 43 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type FIRE WATER SUPPLY (MCC-1) (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required rating , conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to al internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1;6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade wit necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.MAKE: Schneider, Siemens, ABBThe BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 40A, covered with PVC insulated sleeves including insulator, nuts,bolts, etc. with complete connection [B] INCOMING |
| 44 | [i] 32A, 415 V, Ics = 100 % Ics = 25kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [ii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts-01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING[i] 25A, 415 V, Ics = 100 % Ics = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [iii] 10kw Dol Startor - 01 Nos |
| 45 | [iv] 20A, 230V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short - circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-01 Nos. [v] LED phase indicators (Red, Yellow, Blue) -3 Set |
| 46 | EXTERNAL WATER SUPPLY |
| 47 | M/L for cutting the existing bituminous road to a widh of 45 cm for laying of cables etc. |
| 48 | S & F valve, reflux, with bypass arrangement, 65 mm dia complete all as specified & directed. |
| 49 | Supply, install testing and commissioning of open well submersible pump set Horizontal type, multistage with cast iron impeller capable of pumping 6.9 LPS at 26 Mtr head, coupled to submersible electric driven motor, 3 phase, 415V AC, 50 Hz including provision of non-return valve both ends screwed of size 65 mm dia fixed to 65 mm dia bore of pipe including connecting to 3 core copper conductor submersible cable (water proof) of suitable size complete all as specified and as directed.Make: Kirloskar Model KOS 527 or equivalent |
| 50 | Material and labour for Earthing of machinery/equipment Installed at power house/substation complete using galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 32x 6 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI pipe 40 mm dia medium grade and connecting to main panel board/switch board/control board all as shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like exczvation, returning filling back disposal etc complete. |
| 51 | Note :- The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs, PCC 1:2:4 type B1 for earth pit cover 6 Nos 6 mm dia CTD bar on both direction, earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI strip length up to 7.50M will be measured as one unit) |
| 52 | M & L for construction of valve chamber 900 x 900x 900mm depth with PCC foundation in the ratio 1:4:8 brick work cement mortar in the ratio 1:6 using of class B brick, PCC 1:2:4 type B0 using 12.5 mm aggregate at the top, plastering 15mm thick in the ratio 1:4 including MS sheet cover 3mm thick with angle iron frame 50x50x6mm locking arrengement complete with painting on steel surface with two coats of synthetic enameeled paint over one coat of red oxide paint all as specified anddirected. ( Earth work shall be measured and paid seperetely in the respective items) |
| 53 | Supply, install, test and commission LT feeder piller box/ Panel board IEC -614391 , CPRI approved ,indoor type IP-65 , vermin proof, dust proof , fabricated with 3.15 mm CRCA sheet mounted on 50x50x6mm MS angle, 3 phase 4 wire , 440 volts , AC , 50hz with TPN aluminium busbar of capacity with pvc insulator heat shrink colour code sleeves , mounted on procelin insulators duly prewired complete volt and amp meter , selector switch with all accessories and consists of the following switch gears :- (a) Bus bar chamber with electrolytic aluminium bus bar suitable capacity for 3 phase - 01 set (b) MCCB 4 pole adjustable thermal/magnetic setting ,63 A, 415 V ,25 KA- 01 Nos (c) MCCBTPN ,25 A, 415 V ,16 KA- 02 Nos (d) Submersible Pump Starter, 5 HP - 02 Nos(e) Digital voltmeter, Ammeter, indicator lamp, selector switch(f) MCB TPN 6-32 Amp 10 KA -02 Nos(g) Single phase preventer-04 Nos |
| 54 | PLC BASED WATER SUPPLY MONITORING/ ANNUNCIATING AUTOMATION SYSTEM |
| 55 | Supply, Installation, Testing and Commissioning of Indoor type PLC (Programmable Logic Controller) based Slave Monitoring / Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 02 Nos Submersible pumps, 04 Nos Motorized butterfly valves, magnetic level sensors, 01 Nos Ultra Sonic Level Sensor, 02 Nos Pressure transmitters, 02 Nos air release valve & the panel shall consist of the following equipments;(a) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC etc.(b) HMI - 7\\"(c) Transformer with regulated output voltage of 230V, +/-5%,(d) SMPS of 6 A rating, ( e) Set of Control Relays and suitable MCB (f) audio visual generator etc.(g) Suitable No. of LED Indicators for easy visualisation (h) Selecetor Switches(k) Push Buttons/ illuminated Push Buttons |
| 56 | (l) 0.5 sqmm multistarnded internal wiring with ferruling and suitable lugs.(m) GPRS communication Modem along with suitable external antenna of suitable gain, patch chord and mounting accessories with following specification. Make of Control Panel : Rkom Solution / Integrated Control System / Dynatek India Pvt Ltd Location : Pump House |
| 57 | Supply, Installation, Testing and Commissioning of Indoor type PLC (Programmable Logic Controller) based Slave Monitoring / Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 02 Nos Submersible pumps, 04 Nos Motorized butterfly valves, magnetic level sensors, 01 Nos Ultra Sonic Level Sensor, 02 Nos Pressure transmitters, 02 Nos air release valve & the panel shall consist of the following equipments;(a) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC etc.(b) 7\\" HMI(c) Transformer with regulated output voltage of 230V, +/-5%,(d) SMPS of 15 A rating, ( e) Set of Control Relays and suitable MCB (f) audio visual generator etc.(g) Suitable No. of LED Indicators for easy visualisation (h) Selecetor Switches(j) Push Buttons/ illuminated Push Buttons |
| 58 | (k) 0.5 sqmm multistarnded internal wiring with ferruling and suitable lugs.(l) GPRS communication Modem along with suitable external antenna of suitable gain, patch chord and mounting accessories Make of Control Panel : Rkom Solution / Integrated Control System / Dynatek India Pvt Ltd |
| 59 | Supply, Installation, Testing and Commissioning of rust proof maintenance free magnetic sensors.Make: Rkom / Mahalami / Techtrol |
| 60 | Supply, Installation, Testing and Commissioning of Motor Actuated Butterfly valve with the following specifications including all accessories as required:- (a) Valve size: 50 mm dia (b) Designed line pressure: 10 kg/ sq cm.( c) Operating Angle: 90 degrees (d) Disc Material: C.I. with nylon coating (e) Limit switches: 02 nos. for open and close ( f) Type: Direct mounting / Indirect Mounting Actuator Make : Rkom / ICS / Realtork / Emtork Butterfly Valve Make : L & T/ Normex / Leader / Zoloto |
| 61 | Supply, Installation, Testing and Commissioning of pressure transmitter with following specification: (a) Power supply: 10-36 V DC (b) Process connection: G 1/2 \\"( c) Enclosure: Whether proof IP 65(d) Process temperature:- 30 to 120 celcius ( e) Accuracy:1% Make: DANFOSS/ INDFOSS/ Siemens |
| 62 | Supply, Installing, Testing and Commissioning of Ultrasonic Level Transmitter Range : 0-5 metres, Accuracy: 0.5% minimum, Supply Voltage : 24V dc, Output : 4-20 mA Make: NIVELCO/ E+H/ SIEMENS/ BANNER/ KROHNE MARSHAL |
| 63 | Supply, Installing, Testing and Commissioning of 2C x 1.5 sq.mm cable of 1.1kv Grade XLPE, insulated, sheathed steel armoured with Copper Conductor Power Cables. The rates quoted for laying shall include laying of cables on surface with saddles, screws etc. including material and labour charge etc complete. |
| 64 | Supply, Installing, Testing and Commissioning of 4C x 1.5 sq.mm cable of 1.1kv Grade XLPE, insulated, sheathed steel armoured with Copper Conductor Power Cables. The rates quoted for laying shall include laying of cables on surface with saddles, screws etc. including material and labour charge etc complete. |
| 65 | Supply, Installing, Testing and Commissioning of 6C x 1.5 sq.mm cable of 1.1kv Grade XLPE, insulated, sheathed steel armoured with Copper Conductor Power Cables. The rates quoted for laying shall include laying of cables on surface with saddles, screws etc. including material and labour charge etc complete. |
| 66 | Supplying and fixing 5 pair 0.5 mm dia copper armoured communication cable insulated, sheathed steel armoured with Copper Conductor Power Cables. The rates quoted for laying shall include laying of cable on surface with saddles, screws etc. including material and labour charges etc complete. |
| 67 | EXTERNAL ELECTRIC SUPPLY |
| 68 | Dismantling all the HT/LT distribution of existing 160 KVA Transformer of Zone B Area and shifted to proposed location of the proposed site with mechanical means/transportation and commissioning of tranportation with all connection of HT/LT supply and charge the transformer complete all as specified and directed by engr-in-charge. |
| 69 | Supply and fix pole mounted FRP box weather proof type with hinged type doorof white colour of size 250 x 181 x 98 mm with 4 way PVC connector including 1 No MCB SP 6 amps and with suitable clamping arrangements for street light fitting all as specified and directed by Engr-in-charge. |
| 70 | Material and labour for Earthing of machinery/equipment Installed at power house/substation complete using galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 32x 6 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI pipe 40 mm dia medium grade and connecting to main panel board/switch board/control board all as shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like excavation, returning filling back disposal etc complete.Note :- The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs, PCC 1:2:4 type B1 for earth pit cover 6 Nos 6 mm dia CTD bar on both direction, earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI strip length up to 7.50M will be measured as one unit) |
| 71 | Material and Labour for Earthing complete with galvanized steel earth plate electrode 60cmX60cmX6mm thick, buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of plate not less' than 1.5meters below normal ground level, earth plate connected to galvanized earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES SSR-2009 (part I Specifications) connected to earth test point all as specified or indicated including testing on completion, with and including 15 mm bore light grade GI protection pipe 7.5 meters long for earth including PCC (1:2:4) pit and pre cast RCC 1:2:4 type B1 cover 40 mm 1thick reinforced with 6mm dia MS bars @ 100 mm both ways with lifting hook made out of 6mm dia MS bars watering arrange, ent with funnel wire, common salt and charcoal filling, necessary excavation and earth work in any type of soil complete all as specified.Note: The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs , PCC 1:2:4 type B1 for earth pit cover 6 Nos 6 mm dia CTD bar on both direction , earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI wire length up to 7.50M will be measured sa one unit. |
| 72 | Supply, installation, testing and commissioning of LT feeder pillar box, factory made, CPRI approved, outdoor type floor mounding with channel iron pedestal frame made out of 3mm thick CRCA sheet steel for outer body and 2mm thick for inner partition, compartmental type, dust proof, free standing , suitable for working on 440 volts 3 phase 50 Hz AC supply, Vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip 25 x 4mm, 3 phase and neutral aluminium bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, copper strip of suitable size for connecting MCCB, Digital Voltmeter, digital ammeter with suitable rated CTs, LED phase indication lamps & PCC works complete all as specified and directed with the following switch gears:-MLTP)Incoming : (a) MCCB 4 Pole, 415 V, capacity 315 Amps- 01 No Out going : (b) MCCB 4 Pole adjustable type, 125 Amp, 415 Volts 35 KA - 02 Nos (one APFC panel and other spare)(c) MCCB 4 pole fixed type, 63 Amp, 415 Volts 16 KA- 03 Nos |
| 73 | (d) MCCB 4 pole 16 Amp 415 Volt - 01 Nos(g) MCB SP 6-32 Amp-01 No (h) Indicating lamps (set 03 Nos) - 01 set (R,Y & B)(i) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs. |
| 74 | Supply, installation, testing and commissioning of LT feeder pillar box, factory made, CPRI approved, outdoor type floor mounding with channel iron pedestal frame made out of 3mm thick CRCA sheet steel for outer body and 2mm thick for inner partition, compartmental type, dust proof, free standing , suitable for working on 440 volts 3 phase 50 Hz AC supply, Vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip 25 x 4mm, 3 phase and neutral aluminium bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, copper strip of suitable size for connecting MCCB, Digital Voltmeter, digital ammeter with suitable rated CTs, LED phase indication lamps & PCC works complete all as specified and directed with the following switch gears:-MLTP)Incoming : (a) MCCB 4 Pole, 63 Amp, 415 V,25 KA - 01 No Out going : (b) MCCB 4 Pole , 32 Amp, 415 Volts 16 KA - 03 Nos (one APFC panel and other spare)(c) MCB TPN, 10 Amp, 230 Volts 10KA - 01 No ( d) Indicating lamps (set 03 Nos) - 01 set (R,Y & B) |
| 75 | (e) Digital panel mounted Voltmeter and ammeter flush type of size 96 x 96 mm three phase (f) Timer with Conductor - 01 Set(g) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs. |
| 76 | S & F cable route indicator Oval shape 200 x 150 x 6mm cast iron fixed on 25 x 25 x 6mm angle iron including marking of HT/LT UG Cable duly painted and grouted in PCC |
| 77 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure |
| 78 | M/L for cutting the existing bituminous road to a widh of 45 cm for laying of cables etc. |
| 79 | FIRE FIGHTING |
| 80 | Supply, installation, testing and commissioning of Fully automatic DOL starter, suitable for the booster pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, Overload protection, current sensing type single phase preventer complete with all accessories and wiring etc. with complete all as specified and directed by the engineer-in-charge |
| 81 | M & L for 1.1 kV grade 3 core, 6 mm2 Copper conductor, XLPE insulated armoured cable conforming to IS 7098-1: 1988, having stranded aluminium compact shaped conductors as per CI. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by the engineer-in-charge. |
| 82 | Supply, installlation, testing and commissioning of FM approved and UL listed Network Control Display (NCD) / Repeater Panel capable of full supervision of all inputs and network integrity, having 10\\" high definition 1024 x 600 colour touchscreen display, environmental adjustment controls to maximize LCD legibility, LED status indicators (for power supply and off normal condition), network connection, three USB connections, trouble relay, tamper and trouble inputs, etc. and features viz. network-wide acknowledge silence, reset, lamp test, fully programmable node-mapping subsystem, colour coded icon based evevt notification, event vectoring, etc. along with UL listed non-resettable 24 VDC power source complete all as specified by the engineer-in-charge. |
| 83 | Supply, installation, testing and commisioning of FM approved & UL listed Remote power supply conforming to UL 864 & 1481 and NFPA 72 with integral battery charge of charging up to 18 Ah batteries to provide regulated and filtered 24 VDC power to notification appliance ciecuits, havinf power-supervision relay, fully regulated and filtered power output, AC trouble report selectable for immediate 2-hour delay, selectable earth fault detection, etc. complete all as specified and directed by engineer-in-charge. |
| 84 | M & L for low smoke zero halogen(LSOH) flame retardant fire alarm cable conforming to BS-7629-1, BS-6387 and BS EN 50200 and rated for 500V drawn concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicon rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheathed conforming to BS 7655, suitable for operating temp -30 deg centigrade to +70 deg centigrade and min bending radius being six time the overall cable diameter, red in colour, including laying termination and ferruling complete all as specified and as directed |
| 85 | 2 core, 1.5 mm² (for repeater panel to FACP panels) |
| 86 | 2 core, 2.5 mm² (supply to MCP & hooter / strobe) |
| 87 | Supply, installation, testing and commissioning of UL listed ( fire fighter's) addressable Telephone Jack mounted to a single-gang electrical back box with suitable iterface mouule for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed by engineer-in-charge. |
| 88 | S & F of Office plate made out of 6mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 Kg/cm² complete all as specified and directed by the engineer-in-charge. |
| 89 | S & F of CL#150 rated three-piece design 25mm NB Cast Steel (CS) Straight pattern ball valve, conforming to IS 9890: 1981 and tested as per BS 6755-1, having Cast iron body, Stainless steel AISi 304 ball, renewable PTFE seat & gland packing, CS fastners & lever having screwed / socket weid end connection with accessories complete all as specified and directed by the engineer-in-charge. |
| 90 | M & L for FM approved and UL listed, PN 1.6 rated lever operated, wafer type CI Butterfly valve, conforming to IS 13095: 1991, fitted with visual indicator & temper switch, having Cast iron (CI) body with ductile iron EPDM coated disc, SS431 stub shaft, PTFE bushing, flange drilling standard end connection conforming to IS: 1538- 1993 along with necessary accessories complete as specified and directed by the engineer-in-charge. |
| 91 | 100 mm NB |
| 92 | S & F 6 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed |
| 93 | S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed NOTE: [i] Oprating pressure: 10 to 15 bars [ii] Operating temperature: -30°C to + 55°C[iii] Performance criteria : Discharge time not less than 45 sec , throw not less than 4 meters[iv] Hydro test and burst pressure test : Shall pass hydro test pressure of 35 bars 2.5 minutes and with stand a burst pressure of 55 bar EXIT Signage shall meet the following technical / operational requirements:[i] Product Material: Alluminium ALLOY Extrusion [ii] Protuct Finish:- Matt Black / Snow white finish after phosphochromate treatment [iii] Wattage:- 5 Watt [iv] Mounting : Surface / Hanging |
| 94 | NOTE:[i] Installation, testing and commissioning of the fire pump shall conform to IS 15301 : 2003 or NFPA 20. [ii] Installation, testing and commissioning of internal hydrants and hose reels shall conform to IS 3844: 1989. |
| 95 | LIGHTING PROTECTION |
| 96 | Supply, Installation, Testing and Commissioning of aviation obstruction light LED type minimum 10 watts made out of die-cast aluminium alloy housing, IP-65 with built in circuit, junction boxes for installing on top/highest portion of Bldg consisting of (S+7) & (S+8) floors complete withall connected accessories such as including all necessary cables, contactors/timer switches, controls and connections etc as per requirement and as specified. The minimum size of cable shall be XLPE, armoured aluminium conductor of not less than 4.0 sq.mm cross-section. It can be changed from lift electric panel. |
| 97 | Material and labour for Earthing of machinery/equipment Installed at power house/substation complete using galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 32x 6 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI light grade pipe 40 mm dia and connecting to main panel board/switch board/control board all as shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like exczvation, returning filling back disposal etc complete. |
| 98 | Note :- The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs, PCC 1:2:4 type B1 for earth pit cover 6 Nos 6 mm dia CTD bar on both direction, earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI strip length up to 7.50M will be measured as one unit) |
| 99 | HOT WATER SUPPLY |
| 100 | M & L for MCB SPN 240 Volts, 'B' series, Double pole breaking capacity 10 KA of rating 20 Amps including its enclosure complete all as specified and as directed. |
| 101 | Supply and fix 20mm dia gun metal Non return valve, ISI marked screwed at both ends for iron pipes and fixed and complete all as specified and directed. |
| 102 | STAND BY ELECTRIC SUPPLY |
| 103 | Supply, install, test and commissioning of silent Diesel Engine Generating set 415 Volts,3 phase, 4 wire engine as per IS : 10001 / 10002 conforming to Latest CPCB Norms, and alternator as per IS : 13364 of capacity 40 KVA/ 32 KW at site complete with control panel having meters, sound proof canopy etc including all accessories as per manufactures standard and as per the details given below and independent relay panel for automatic on mains failure:- AC Generator should be suitable for ambient conditions at Secunderabad and confirming to IS. (Note:- The capacity of generator set shall be net after all de-rating factor as per relavent IS design)(A) Alternator :- Standard design alternator rated at (32 KW) net output at site after considering all derating factors, site conditions at power factor0.8 AC, 3 - phase 4 - wire 415 volts 50 Hz, Cycles/ Second, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design, voltage regulation ± 2.5%.(B) Diesel Engine:- Vertical diesel engine of suitable capacity, water cooled, closed circuit as per BS-649 or IS- 1002 direct injuction type. Electric starting system having rated speed 1500 RPM. |
| 104 | The DG set Shall be capable for running 24 hrs continuously with 10% over loading for 01 hour in every 12 hours as per BS-5512/BS-649. Engine shall be multi cylinder, multi stroke, direct injection and equipped with all standard fitting as per manufacture's recommendations and mountad on common base frame with following Specifications:-(i) Fly wheel with housing:- Common base frame of sturdy design suitable for anti vibration mounting and permanent concrete foundation for mounting engine and alternator as per manufacturer's instructions [ii] Cooling system:- (a) Mounted radiator with fan & belts & guard, rubber house and thermostat. (b) Colling water pump centrifugal type. (iii) Governer :- Mechanical Governer (iv) Electric Starting System :- Electric Self starter, 12 volts DC (12 volt, 100 AH battery 1 no's) charging alternator as per manufacturer's design, copper leads with lugs of adequate size complete with initial charging of maintenance free battery 1 x 12 volt 100 AH capacity. Make:- Exide or as per manufacturer;s specification. |
| 105 | (v) Generator Mountoring Panel:- Comprising of following:- (a) Microprocessor based genset controller for metering, monitoring, governing and protection (b) Engine protection for low lib oil pressure, high coolant temperatre (Alarm & Shutdown) ( C) Alternator protection parameters like under voltage, over current, under frequency, over frequency (Alarm & Shut down) (vi) Accessories:- AVM pads built or separately mounted to manufacture base frames. (vii) Coupling Arrangements:- Fixed coupling, flywheel to suit fixed coupling and fly wheel housing. (viii) Exhaust System:- Silencer complete with exhaust pipe of suitable size upto and out side the building all covered with asbetos rope of suitable size and complete design should be as per latest exhaust emission limits for DG sets confirming to as set by MoEF & CC gazette notification No. GSR 804 (E) dt 03 Nov 2022 (amended up to dated, if any ) complete all as directed (ix) Fuel Tank:- Daily service fuel tank of capacity suitable for 12 hours continuous operation made out of 3mm thick (heat retardant) sheet with indicating gauge, built inside the acoustic enclosures or as per manufacturer's design. |
| 106 | ( c) Acoustic Enclosure ( Sound Proof Canopy) :- All as per Latest CPCB norms and OEM of DG Set's design. ( D) AMF Panel :- Supply, install, testing and commissioning of AMF Panel outdoor type, cubical body, dust and vermin proof made up of CRCA sheet 3mm thick painted with two coats of synthetic enamelled paint over a coat of red oxide primer confirming to IP 45 with front and rear opening with louvers and mounted on floor with PCC pedastal pillars with a clearance of atleast 0.3 m above grount level wih glands sockets etc with provision of cable entry from bottom all pre wired and connected complete with following accessories:- (i) PLC-01 No (ii) Power Contactor heavy duty suitable for generator and mains (iii) Over load relay for genset (iv) Suitable rating isolating switch MCCB for both DG & main supply. (v) On Load changeover (mentiones in sr xiv) (vi) Multi function meter to indicate voltage, current, frequency, PF, KW & KWH etc (vii) Emergency stop push button (viii) Set of indicaters:- (a) Low lube oil pressure (b) DG Set over load (ix) Push button to start, stop (x) Mode selector switch i.e Auto/Manual/test/off. (xi) Set of insrtument fuse (xii) Set of aluminium bus bar of suitable capacity 3 ph, 4Wire system. |
| 107 | (xiii) Automatic battery charging unit with DC voltmeter, Ammeter and selector switch for trickle/ boost charging. (xiv) By Pass arrangement of main supply when AMF circuit fail due to any fault with provn suitable rating change overs and switches.The following items are deemed to be included in the rate quoted for al DG sets:-(i) One year Maint Spare as per manufacturer maint schudule and as directed by Engr-in-charge is deemed to be included in the above offer(ii) One set of latest Spare part catelogue with price, exploded view of parts and user's manual are deemed to be included in the offer.(iii) The rate quoted is deemed to be include for initial filling of radiator coolant and lubricating oil upto level.(e) Civil Works:- All civil works related to foundation, installation of panel and equipment and depth of foundation shall be minimum 300mm with antivibration pads, or as recommended by the manufacturers. Cables from DG set to AMF panel, AMF panel to main panel will be measured under relevant schedule |
| 108 | Note:- (i) The fuel for final testing of 12 hours shall be supplied by the contractor and coat deemed to be include in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/ rating and any other items required for final testing shall be provided by the contractor without any extra cost to department. (ii) The testing of Genset for continuous 12 Hours shall be done by an officer detailed by accepting officer after installation at site No load - 1/2 Hour25% load - 1/2 Hour50% load - 1 Hour75% load - 1 Hour 100% load - 8 Hours110% load - 1 Hour |
| 109 | Material and labour for Earthing of machinery/equipment Installed at power house/substation complete using galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 32x 6 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI light grade pipe 40 mm dia and connecting to main panel board/switch board/control board all as shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like exczvation, returning filling back disposal etc complete. |
| 110 | Note :- The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs, PCC 1:2:4 type B1 for earth pit cover 6 Nos 6 mm dia CTD bar on both direction, earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI strip length up to 7.50M will be measured as one unit) |
| 111 | COOLING APPLIANCES |
| 112 | S&F Refrigerator electrical driven (single phase) capacity 300 ltrs BEE 5 star rated suitable for operation on 230v 50HZ AC supply. |
| 113 | S&F Refrigerator electrical driven (single phase) capacity 200 ltrs BEE 5 star rated suitable for operation on 230v 50HZ AC supply. |
| 114 | Supply install test & commisioning metal top of Deep freezer hard top 300 ltrs capacity Double door type electrical driven (single phase) with R 134A/12 Gas suitable for operation on 230v 50HZ AC supply. |
| 115 | Supply, installation, commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage 80 ltrs and nominal cooling capacity 40 ltrs complete all as specified and directed. Make: Blue Star SSDLX4080B / Equivalent in Voltas / Usha |
| 116 | Supply, installation, commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage 120 ltrs and nominal cooling capacity 80 ltrs complete all as specified and directed. Make: Blue Star SSDLX4080B / Equivalent in Voltas / Usha |
| 117 | Supply and fix hi wall split AC complete with inverter compressor, variable speed, electric driven single phase of capacity of 2 Ton, copper conductor coil, BEEE 5 star rated Complete all as specified and directed by Engr-in-charge. |
| 118 | Material and labour for submain wiring using 3 runs of 4 Sq mm 1100 V grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade PVC recessed conduits, conforming to IS 9537 (Part- 3): 1983, of size not less than 25 mm NB, including making good of disturbed surfaces of wall / ceiling / floor all complete as specified in IS 732: 2019 and directed.NOTE: Phase & neutral conductors (02 runs), earth continuity conductor (01 run) and PVC conduit (01 run) shall be measured combined as one length. |
| 119 | Supply and fix power module 240V, 20A complete with 4 module mwtal flush box, cover plate, Starter, Plug & Socket all as directed. |
| 120 | S & F install commission and testing of Desert Cooler electrical driven (single phase) having nominal air floe capacity of 4000 CUM per hour ( or nearest size) with thermal overload protection, water level indicator, multi direction Castor Wheels with trolly & plastic / PVC body all as specified and directed. Make: Havells Model Supro 45/ Equivalent |
| 121 | Voltage stabilizer for automatic operation suitable for Refrigerator/deep Freezer/Water Cooler single phase naturally air cooled indoor type & designed for input variation between 170 V ti 250 V with output voltage stabilized at 230 V with accuracy of (+/-) 2.5% and capacity 1KVA. ( For Water Cooler & Deep Freezer) |
| 122 | Voltage stabilizer for automatic operation suitable for Split Air Conditionerr single phase naturally air cooled indoor type & designed for input variation between 170 V ti 250 V with output voltage stabilized at 230 V with accuracy of (+/-) 2.5% and capacity 5KVA. ( For Water Cooler & Deep Freezer) |
| 123 | S & F Unplasticiscd PVC pipes of pressure rating 10 kgf/cm² fixed complete to walls, ceilings or in floors etc., any type of pipe of 25 mm bore for AC drain type |
| 124 | ELECTRICAL CHIMNEY |
| 125 | Supply, Fixing, testing and commissioning of complete electrical chimney/Electrical Hood, 3 phase, 415V, 50 Hz with filters complete with the following accessories:- |
| 126 | Supply and install Kitchen hood made of SS 304 matt finish 22 gauge wall mounted type with removable grease stop and fixing brackets oil drain collector & connecting with exhaust ducting complete all as specified and as directed. Size:- (i) 6' x 36\\" + 18\\" + 6\\" =6 RFT (ii) 6' x 36\\" + 18\\" +6\\" = 6 RFT |
| 127 | Supply and install exhaust ducting of suitable size made of GI Sheet 24 SWG including connecting with ceiling mounted exhaust hood up to terrace with MS angle frame 25 x 25 x 3mm thick fixing of brackets with nut bolts, gaskets supporting thread rod, channels complete all as specified and as directed. |
| 128 | S/F Exhaust Blower 3 phase, 415V, 50 Hz of capacity 2 HP, minmium 3500 CFM including starter connecting with exhaust ducting and suitable electric copper cable connecting with starter complete all as specified and directed. |
| 129 | Supply and install collar damper of size 10\\" x 10\\" x 4\\" for connecting between duct and exhaust hood made out of GI 22 SWG with air control lever complete all as specified and directed. |
| 130 | M & L for Fabrication & fixing of Polister Canvases for Exhaust units all as directed. |
| 131 | S & F DOL starter MK1 suitable for 3 phase, 415 V, 50 Hz 2 HP motor including necessary connections with 2.5 sq mm copper conductor cable all as directed Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy