| 1 | Surface excavation nexc 30 cm deepand averaging 15 cm deep and getting out soft/loose soil complete all as directed . |
| 2 | Excavating over area ,nexc 1.5 m deep and getting out soft /loose soil complete all as specified and directed. |
| 3 | Ditto .above for each additional 1.5 m or part thereof in depth exc 1.5 m deep upto 3.0 m depth getting out soft /loose soil complete all as specified and directed. |
| 4 | Excavation in trenches not exc 1.5 m in depth and n exc 1.5 m wide for foundation etc,or for shafts ,wells,cesspits,manhole, pier holes etc getting out soft/loose soil,complete all as directed . |
| 5 | PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in mass filling in foundation and flooring complete all as specified and directed. |
| 6 | Returning filling including spreading, levelling, watering and well ramming in layers and not exceeding 25cm complete all as specified and directed |
| 7 | Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed |
| 8 | M & L for Reinforced cement concrete (design mix) M-25 using 20mm graded aggregate as in foundation footing concrete incl pile cap,plinth beam etc complete all as specified and directed. |
| 9 | M & L RCC- M25(Design Mix) using 20mm graded stone aggregate for tie beams etc complete all as specified and as directed.. |
| 10 | M & L RCC- M25 (Design Mix) using 20mm graded stone aggregate for Column complete all as specified and as directed. |
| 11 | Use and waste of formwork to rough finished sides of concrete foundation,footing, bases of column, rafts, rafts beams & side & side of foundation and plinth beam and semilar vertical battle complete all as specified and as directed. |
| 12 | Use and waste form work for fair finished surfaces of concrete measured flat for tie Beam etc complete all as specified and as directed. |
| 13 | Form work for fair finished surfaces of concrete measured flat for Column complete all as specified and as directed.. |
| 14 | M & L for Mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips (footing & column upto NGL) complete all as specified and as directed. |
| 15 | Ditto item no 11 above but 5 to 10mm dia in stirrups, spacers & binders. complete all as specified and as directed. |
| 16 | S&F mild steel (Fe- 410-W (Gde E- 250)Roof trusses (framed), trussed, purlins, crane gantries, rails,vertical posts and fastenings and heavy bracket framing (Beam, tee, angle, channel ,tubes or flat sections) including distance pieces,MS plate, cleats etc. complete all as specified and directed |
| 17 | S & F Mild steel rag,anchor bolts or lewis bolts, screwed one end, with hexagonal or square nuts and washers, the other end enlarged and jagged or lewised, of 20 mm dia bolt and length of bolt exc 30cm long complete all as specified and directed. |
| 18 | M&L applying two coats of synthetic enamel paint over a coat of red oxide or zinc chromate primer including preparation of new steel or iron surfaces exc 10 cm width or girth, complete all as specified and directed. |
| 19 | S & F Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified and as directed. |
| 20 | S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall,ridges etc, fixed with self tapping screws as specified |
| 21 | Material & Labour for fly ash brick work with straight or curved on plan built in cement mortar 1:6 complete all as specified and as sdpecified. |
| 22 | M & L for 150 mm dia PVC(SWR) pipe single socketed in any length with rubber ring joints fixed to walls etc complete all as specified and directed. |
| 23 | S & F stack clamps out of 50 mm by 5 mm flat iron and 16 mm dia round iron stays incl bolts and nuts and securing end of stays to wall or roof complete all as specified directed . |
| 24 | M & L hardcore of broken stone/boulders of gauge n.exc.63mm, eposited, spread and levelled in layers n exc. 15 cm thick, watered and well rammed to a true surface all as per specified and as directed |
| 25 | M&L for PCC 1:4:8 type D-2 using 40 mm graded aggregate as in sub base, foundation filiing and mass concrete incl necessary formwork etc complete all as specified and directed. |
| 26 | Excavation in post holes (or similar holes) each not exc 0.5 Cum and getting out, returning filling in and ramming earth or borken rubble mixed with earth around in layers not exc 25cm watering and removing surplus spoil to a distance not exc 50m and making good surface in soft/loose soil all as specified and directed. |
| 27 | M&L for sand cushioning under floors or in foundations including watering and consolidation complete all as specified and directed by Engr-in-Charge. |
| 28 | M&L for 80 mm thick machine pressed precast concrete interlocking paver block any shape and size M-40 grade with grey cement and no pigment confirming to IS 15658-2006 complete all as specified and directed by Engr-in-Charge. |
| 29 | M L Plain cement concrete 1:3:6 Type C1 using (20mm graded stone aggregate ) in roof kerbs or mud stops, rounded or chamfered on edges complete all as specified and as directed |
| 30 | Material and labour for point wiring with two single core 1.5 sqmm cable (nominal area) stranded copper conductor, PVC insulated unsheathed cable, 1100 V grade in and including concealed PVC conduit of size not less than 20mm dia with sunken type pressed steel terninal box 1.6 mm thick of suitable size, duly painted with one coat of red oxide primer and two coats of black bituminous paint for mounting fittings/ junction boxes and wiring to be terminated in pressed steel sunken boxes including all accessories and using single core 1.5 Sqmm (nominal area) stranded copper conductor, PVC insulated unsheathed cable as in earth wire (green colour) connected to common earth dolly complete all as specified and directed for following :- (a) One light point controlled by one switch. |
| 31 | (b) One 3 pin switch socket outlet point 5 Amps on same board. |
| 32 | (c) One 3 pin switch socket outlet point 5 Amps on independent board. |
| 33 | All as per item above here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 sqmm size. |
| 34 | Supply & Fix Single pole and Neutral enclouser with two pin and earth plug and socket complete with one single pole 20 Amps MCB , 230 Volts complete all as specified and directed. |
| 35 | M&L Switch piano flush type single pole, one way 5 Amps 230 Volts AC circuit complete all as specified & directed by Engr-in-Charge. |
| 36 | M&L Switch piano flush type single pole, one way 15 Amps 230 Volts AC circuit complete all as specified & directed. |
| 37 | M&L for socket outlet 5 Amps, 5 Pin flush type multipurpose, 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 38 | M&L for socket outlet 2 in 1, 3 Pin 5 & 15 Amps, 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 39 | S & Fix ceiling rose surface backlite 65x50mm 3 terminals complete. |
| 40 | S & F Electronic step type fan regulator 120 Watt 230 Volt 50 Hz two module C/S deluxe type complete all as specified and direcetd. |
| 41 | M&L for submain wiring with two single core FRLS insulated flexible copper conductor cable of sze 4 sqmm and one single core PVC FRLS insulated flexible copper conductor cable green colour of size 4 Sqmm as earth lead in & including concealed PVC conduit medium grade cutting chases to walls for laying conduit and making good the disturbed wall surfaces to match with existing specification all as required at site or directed by Engr-in- charge. |
| 42 | Supply & fix sheet metal enclosure MCB distribution board. Single pole & neutral 230 Volts 8 way with IP-43 IK-09 protection double door complete with appropriate size bus bar and neutral link, fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification . |
| 43 | Supply and replacement MCB single pole 230 Volts any rating from 6 to 32 amps, with reupturing capacity 10 KA,including providing thimble for out going cables. |
| 44 | Supply and replacement MCB SPN 230 Volts any rating from 32 Amps, with rupturing capacity 10 KA, including providing thimble for out going cables. Make:- Legrand/Hoper/Merlin Gerin multi-9. |
| 45 | Supply and fixing LED Street light fitting 35 Watt 230 Volt AC Outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver , lamp bracket with impact and corrission resistant including thermal management in multiple optics complete with IP 66/65 Protection complete all as specified and directed. |
| 46 | M&L for Copper Busbar Chamber box of capacity 100 Amps , 415 Volt , 3 Phase 4 wire AC Supply complete ,including taking down of old Unsv bus bar cahmber and reconnecting the cables with proper lugs and making the good distrubed surface of complete with all accessories, all as specified and directed by Engineer in Charge. |
| 47 | S & F in repair wall mounted LED Tube light fitting 20 Watts 6500K including making connections with 2 core flexible copper wire 0.50 Sq mm from ceiling rose after fixing fitting in position at site on 02 Nos new round blocks including complete all as specified and directed. |
| 48 | M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead wire 4mm dia size by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 3 of SSR part I including necessary excavation and earth work GI pipe 20mm dia light grade for watering and GI 15mm dia light grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to DB as indicated including testing complete. |
| 49 | Sand cushioning to the under ground electric cable complete all as specified considering 19.75 of SSR part -I |
| 50 | M/L Sub Class 'B' brick covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified |
| 51 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 35 Sqmm complete all as specified and directed. |
| 52 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 Core 25 Sqmm complete all as specified and directed. |
| 53 | Supply installation commission and testing of Out door LT Panel board of size 900 x 450 x 1200 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase, Bus Bar chamber comprising 4 Nos Aluminium strip bus bars air insulated and PVC sheathed capacity 200 Amps with colour coding with main indication IA with selector switch 03 Nos,digital ammeter with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos, factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMINGMCCB 100 Amps, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 25 KA) OUTGOINGMCCB 63 Amps, 4 Pole , 415 Volts rating with Adjustable Over load setting (Breaking capacity 25KA) = 01 Nos MCCB 40 Amp, 4 Pole , 415 Volts rating with,Adjustable Over load setting (Breaking capacity 16 KA) Ics=100% of Icu= 2 Nos.MCB SPN 32 Amps C Curve 10 KA -01 Nos |
| 54 | Installation, testing and commissioning of diesel engine driven Gen Set 10 KVA liquid Cooled with sound-proof Acoustic Enclouser cover to control the noise level as per limit of central pollution control board (CPCB-IV +) with STD Panel , 3 Phase 415 volts 1500 RPM, 4 wire 50 cycles with two years maintenance spares and set of tools as recommended by manufactures comprising of the following :-(a) Prime Mover / Engine : -Suitable for driving 10 KVA alternator, water cooled, battery start diesel engine of adequate BHP conforming to BSS frame pedestal support with anti vibration pad rated for continuous running capable of taking 10% over load for one hour in any 12 hrs operation with the following standard accessories and monitoring facilities :- (i) Fly wheel with starter ring(ii) Flexible coupling with guard (iii) Air cleaner oil bath type / dry type (iv) Lubricating oil filter (v) Fuel Pump with Governor(vi) Radiator,radiator fan and mounting(vii) Governor for class 'A' governing as per IS - 1601 of DS 349 /1958 (viii) Starter, motor for electric start complete with dynamic alternate, lead acid batteries Pre-carged heavy duty of capacity 12V 65 AH or adequate size and length of cable not less than 2m long including battery box all as directed.(ix) Hour meter and RPM indicator (x) Exhaust pipe brought outside the bud and lagging of entire exhaust pipe with 12mm dia arrestor rope.(B) Instrument / Control panel duly wired comprising of the following features(a) Control Panel consisting of built in on/off /Start Key(b) Battery charging voltmeter (c ) Electronic Hour Meter(d) Indication & Monitoring of Oil Pressure & Safety trip in case of Low Oil Pressure.(e) Indication & Monitoring of Coolant Tempreature & Safety trip in case of High Coolant Tempreature.(f) In-built engine shut down system in case of Engine Overspeed.(g) Indication & Monitoring of Fuel level and alarm.(b) ALTERNATOR 10 KVA/08 KW at 0.8 PF of brush less self excited, self regulated 3 phase, 50 Hz 415 V 1500 RPM 4 wire screen protected drip proof free from stimulation problem continuous rating conforming to BS 5000/IS:4722. The salient features of alternator are as under:- (i) Casing protection: As per IP-23 (ii) Over load capacity: 10 % of one hour in any 12 hrs of operation (iii) Repair/Maint tools to be supplied with DG Set as under: (a) STAINLEY 91-931-12 Master tool set of make : Stainley (iv) Acoustic Enclouser: Floor mounted acoustic enclouser suitable for 10 KVA DG Set as per CPCB Norms. Note :-(i) Any fitting / fixtures are deemed to be included above which are required for its proper functioning (ii) Necessary foundation (As per manufacturer's specification) for installation of DG Set shall be provided and cost deemed inclusive of the rates quoted above. WARRANTY: The generating set carry the respective manufacturer's warranty for a period of TWO YEARS or 5000 hrs whichever is earlier and TWO YEARS for Alternator from the date of supply for any in herent manufacturing defect as per manufacture's norms. Make : Cummins/Kirloskar Green/Ashok Leyland/Greaves Cotton |
| 55 | Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia medium grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion. |
| 56 | Material and labour for covered shed with CGI roof top 02 Nos of MS angle trusses (65mm x 65mm x 6 mm ) of size 2.5 m x 2.5m x 4m over a foundation of DG Set and finishing the surface even and smooth and erecting 4 Nos of 80 mm dia heavy duty tublar pipes having height 4 mtr including well grounted in foundation 0.45x0.45x0.6m with 6 Nos of purlins and 04 Nos of angle iron to hold the tublar pipes and CGI Fencing of required size over the trusses , purlins and painted with two coat synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in- Charge. Please Enable Macros to View BoQ information |