| 1 | Supply, Drawing and OLTS Testing, of stranded OS2 Single mode (9/125 µm) glass optic fiber cable G652D as per latest ammendments of TIA/EIA 568/ISO/IEC with outer sheath, cable should be used for LAN and WAN back bones, for indoor/outdoor installations these sheathed cable be placed in existing MS/PVC /HDPE Conduits/ slotted channels with ferruling at both ends for identification complete in all respect. |
| 2 | 12 Fiber |
| 3 | Supply, Installation, & Testing of Indoor duplex Singlemode patch cord (9/125 µm (OS2) made of glass fiber optic with LSZH jacket, F8 2.0x4.1 mm, yellow, singlemode G652.D (9/125 µm (OS2) Mounted on both sides with SC/LC/SN/CS type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical coding and lock protection on the patch cords which can be added on later stage. patch cords's performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per requirements. |
| 4 | Single Mode Patch Cord 1 Mtr. |
| 5 | Supply, Installation, & Testing of 19\\" 1U Rack Mounted/ surface mounted aluminum/ CRCA powder coated, OS2 Single mode glass Fiber Optic Cable Patch panel/LIU loaded with flangeless/screwable duplex adapters for SC/LC/SN/CS type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleeves, screws, nuts to install the panel for rackmount applications as per requirement complete in all respect. All as per pre approved by Engineer in charge. |
| 6 | 12 Ports |
| 7 | 24 Ports |
| 8 | Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches. Must be hot Pluggable, RoHS Complaint, etc. complete as required.(For Each SM Fiber) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Enterprise class. |
| 9 | 10 G SFP + Single Mode/Multi Mode |
| 10 | Fiber Fusion Splicing with OTDR/OLTS Testing of Fiber Single/ Multi mode (per splice) of glass Fiber Optic Cable including jointer box and cleaning the cable and making splice as per standard practice complete in all respect. |
| 11 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 12 | 50 mm |
| 13 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. |
| 14 | 100mm x 50mm x 1.6mm |
| 15 | Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 16 | Supply, Installation, & Testing of Indoor duplex OM2 Multimode patch cord (50/125 µm made of glass fiber optic with LSZH jacket, 2.0x4.1 mm, Multimode ITU G 651 Mounted on both sides with SC/LC/SN/CS type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical coding and lock protection on the patch cords which can be added on later stage. patch cords's performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per requirements. |
| 17 | 1 Mtr |
| 18 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 19 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 20 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 21 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 22 | 38 mm x 25 mm |
| 23 | GST @18% Please Enable Macros to View BoQ information |