Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | SCH 'A' PART-I: BUILDING/STRUCTURESNote: This schedule is not pre-priced by MES and the rate indicated as \\"Rs 0.00\\" under Col 5 signifies this fact only |
| 2 | Engineering, Procurement & Construction (EPC) of buildings/ structures including all internal services & external services (except Sch 'A' Part-l (B) to XIV) as defined in Annexure-I to VI, complete as detailed in scope of work and other documents of tender, complete all as specified and directed. |
| 3 | NOTE: Schedule ‘A’ Part-I (B) to X items which are Prepriced by MES, Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 4 | Total amount of Sch 'A' Part-I (B) (Septic Tank and Soakage well) |
| 5 | Total amount of Sch 'A' Part-II (Site Clearance, Excavation and Earthwork) |
| 6 | Total amount of Sch 'A' Part-III (Road, Paths & Culverts ) |
| 7 | Total amount of Sch 'A' Part-IV (Sewage Disposal) |
| 8 | Total amount of Sch 'A' Part-V (Area Drainage) |
| 9 | Total amount of Sch 'A' Part-VI (Fencing & gate) |
| 10 | Total amount of Sch 'A' Part-VII (External Water Supply) |
| 11 | Total amount of Sch 'A' Part-VIII (External Electric Supply) |
| 12 | Total amount of Sch 'A' Part-IX (Rain water harvesting) |
| 13 | Total amount of Sch 'A' Part-X (Standby DG Set ) |
| 14 | SCHEDULE 'A' PART-XI ( FURNITURE WORK) |
| 15 | Supply of Round Conference Table for 8 Persons with computer cable inside tray. All as specified and directed by Garrison EngineerMake :- Durian Model:- DWS/34762 or Techno commercial equivalent make in Methodex and Featherlite |
| 16 | Supply of Chair Revolving Executive. All as specified and directed by Garrison EngineerMake :- Durian Model:- LAURA or Techno commercial equivalent make in Methodex and Featherlite. |
| 17 | Supply of Hat Stand Large With Mirror (6 Pegs). All as shown on Drawing No FD-362 and as specified and directed by Garrison Engineer |
| 18 | Supply of Cubical Officer Table with computer cable tray. All as specified and directed by Garrison EngineerMake :- Durian Model:- 65/5x5 Plus or Techno commercial equivalent make in Methodex and Featherlite. |
| 19 | Supply of Chair Executive Revolving for Officer High Back. All as specified and directed by Garrison EngineerMake :- Durian Model:- HOPE or Techno commercial equivalent make in Methodex and Featherlite. |
| 20 | Supply of Chair Visitor Revolving Steel. All as specified and directed by Garrison EngineerMake :- Durian Model:- BLISS or Techno commercial equivalent make in Methodex and Featherlite. |
| 21 | Supply of Hat Stand Small With Mirror (4 Pegs). All as shown on Drawing No FD-233 and as specified and directed by Garrison Engineer |
| 22 | Supply of Cupboard With Two Shelves. All as specified and directed by Garrison EngineerMake :- Durian Model:- BECKLE TT or Techno commercial equivalent make in Methodex and Featherlite. |
| 23 | Supply of Table Dining 120 X 90 cm. All as shown on Drawing No FD/E6/MAP-II/03 and as specified and directed by Garrison Engineer |
| 24 | Supply of Chair Dining With Cushion Map. All as shown on Drawing No FD/E6/MAP-II/04 and as specified and directed by Garrison Engineer |
| 25 | Supply of Continue Joint Table for 2 Computers. All as specified and directed by Garrison EngineerMake :- Durian Model:- DWS/3475-B or Techno commercial equivalent make in Methodex and Featherlite. |
| 26 | Supply of Continue Joint Table for 3 Computers. All as specified and directed by Garrison EngineerMake :- Durian Model:- DWS/3475-C or Techno commercial equivalent make in Methodex and Featherlite. |
| 27 | Supply of Continue Joint Table for 4 Computers. All as specified and directed by Garrison EngineerMake :- Durian Model:- DWS/3475-D or Techno commercial equivalent make in Methodex and Featherlite |
| 28 | Supply of Charpoy Double Bunk Steel. All as specified and directed by Garrison EngineerMake :- Durian Model:- GINNY or Techno commercial equivalent make in Methodex and Featherlite |
| 29 | Supply of Locker Bedside Steel. All as shown on Drawing No FD-1029 and as specified and directed by Garrison Engineer |
| 30 | Supply of Chair Computer All as shown on Drawing No FD/E6/MAP/01 and as specified and directed by Garrison Engineer |
| 31 | Supply of Almirah Large Steel With Shelves. All as shown on Drawing No FD-1031 and as specified and directed by Garrison Engineer |
| 32 | Supply of White Board of Size 6' × 4' (Trade Pattern) -- White Board (TP) of size 6'×4' shall be provided all as per following specifications:-1. The white board shall be 2-in-1 to serve as White Board and Notice Board both. It shall be a Magnetic Whiteboard which will serve as both a dry-erase writing surface and a magnetic bulletin board.2. The White Board shall have durable surface material which shall be designed with a triple-coated steel surface, featuring an acrylic resin top coat over a galvanized steel base. This smooth, glossy, and scratch-resistant surface ensures effortless writing and easy erasing.3. The white board shall have sturdy frame with safe corners and shall be provided with a strong aluminium frame and chrome-plated rounded corners to provide durability and safety from sharp edges.4. The white board shall have fixing arrangement so that it may be mounted both horizontally and vertically, depending on the available space and board size.5. The White Board shall be compatible with whiteboard markers.6. The White Board shall be of Make : AlkoSign/Pragati Systems/Wipro/Eduway or equivalent |
| 33 | SCHEDULE 'A' PART-XII (MISCELLANEOUS B/R AND E/M WORKS) Note: This schedule is not pre-priced by MES and the rate indicated as \\"Rs 0.00\\" under Col 6 signifies this fact only. |
| 34 | S&F of sluice valve of class PN 1.6 with steel spindle and both ends flanged of 80 mm bore , along with brass nut, gasket etc with both ends flanged confirming to IS-14846 with standard bolts hole ,fixing with nuts ,bolts, washers, rubber gasket etc complete in position of pipe line all as specified and directed. |
| 35 | M&L brick masonry valve pit chamber of internal dimension 120 em x 120 em x 120 cm depth with sub class 'B' bricks in CM (1:4) and 10 mm thick plastering in CM (1:4), PCC (1:4:8) type D2 (Using 40 mm graded broken stone aggregate) as in foundation lean concrete, PCC (1:3:6) type CI (using 20 mm graded broken stone aggregate) .as in bedding and copping MS frame with 40 x 40 x 6 mm angle iron 3 mm thick MS sheet cover plate with -locking arrangements, hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preparation of surface, three coats of white wash on plastered surface (exposed to view) including necessary excavation in soft loose, soil, returning filling in and removal of surplus soil to a distance not exceeding 50 m complete all as specified and directed. |
| 36 | Supply and fix Dewatering pump capacity 1 HP, 0.75 KW, 415 V, 2850 RPM, head range 10-24 Mtr (36-54 Ft) Discharge range 410-210 LPM, Suction and delivery pipe size 50 mm,double mechanical seals and auto cut protection, IP 68 protection,football, football pipe suitable size including sensor based automatic pump operating system for 1 HP motor are desiged to fully automatic water transfer between underground sump to bldg outside tank, typically using conductivity or float sensor to prevent over flow and dry running including manually operating mode (bypass system) for pump along with all connection accessories as per directed by Engr-in-Charge. |
| 37 | Supply and fix Monoblock pump set capacity 3 HP, 2.20 KW, 3000 RPM, Head range 15-27 Mtr (50-89 Ft), Discharge range 450-150'LPM, Solid handling Capacity 10.5 mm, Suction and delivery pipe size 50 x 40 mm, suitable for 415 V, three phase system having capacity 3 HP including Football, football oriole suitable size and all connection accessories. |
| 38 | Supply and fixing of DOL Starter, three phase starter with relay capacity 6 to 10 Amp suitable for pump set capacity up to 3 HP complete all as specified and directed by Engr-in-Charge. |
| 39 | M&L for PVC insulated and PVC round sheathed Multi core bright annealed bare copper conductor heavy duty industrial flexible cable size 4 Sqmm 3 core voltage ·grade 1100 Volts confirming IS 694:2010 complete with fixing on wall with PVC conduit of size 20 mm dia complete all as specified and directed by Engr-in-Charge |
| 40 | Supply of Gravel size 5 to 10 mm free from admixture, dust, clay and screened properly as specified and directed. |
| 41 | Supply, installation, commissioning & testing of silent, Diesel engine driven factory assemble, generating set of capacity 650 KVA, 3 phase, 4 wire, 50 Hz, 1500 RPM complete with engine and alternator mounted on a common MS fabricated base frame with AVM pads, Acoustic enclosure, relay panel for automatic starting on mains failure safety control and metering equipment mounted on & including common base frame and installed on PCC/RCC foundation as recommended by manufacturer and approved by GE and suitable for ambient conditions at Pune, environmental eco friendly as per CPCB P- IV plus norm including the following all as specified and directed. |
| 42 | Note: PCC foundation work as per manufacture instructions, anti-vibration pads and other standard accessories and comprising of the following:Diesel Engine: Cylinders 06 Nos as per OEM standard, inline type turbo charged after cooled (TCAC), with standard Gross Engine Power to drive alternator to deliver device minimum 630 KVA (504 KW) at atmospheric conditions of Pune, water cooled turbocharged with after cooled, rated output\\" 1500 RPM and overspeed trip 1650 RPM, engine is with electric start, compression ignition, stroke cycle designed to run continuously at 1500 RPM conforming to IS 2002, IS0-3046, BS 5514 standards. Diesel engines should comply with CPCB P-lV plus norms. The Diesel Engine are comprising of followings:(i)Radiator with fan (ii) Fuel injection equipment with electronic Governor having CRS (Common Rail Systern) and DG performance class G3, (iii) Dry type air cleaner(iv) Exhaust silencer type NA, max allowable backpressure (kPa) 17, exhaust temperature (Deg C) 5SO, (v) Lub oil filter (Spin on type) (vi) Fuel oil filter (Spin on type) (vii) 24V electric starting system (viii) Battery charging alternator (ix) Stop Solenoid (x) Lube oil pressure -gauge (xi) Water temperature gauge (xii) Lube oil temperature gauge (xiii) Battery voltage (xiv) Extended life coolant Alternator: Alternator type 4P, rotating field, automatic voltage regulator and voltage regulation ±. 1%, suitable for continuous duty operations rated at 1500 RPM, 415V, 0.8PF, 50 Hz, current (3Ph) Amps-174 in SPDP enclosure, self-exiles & Self-regulated, Brushless, 'H' class insulation, temperature rise (Deg C) 125, coupling type Fie Disc, unbalanced load capability 25% of rated amps, floor mounted with anti-friction Sealed ball bearing on end. Alternator charging 12V DC/35A, the alternator conforms to IS: 13364 (Part-II) suitable for tropical condition including making cable connection. connection. |
| 43 | Acoustic Enclosure: (a) Specially designed to meet stringent MoEF 1 CPCB norms of 75 dBA @ 1 Mtr at 75% load under free field conditions. (b) The followings are some technical features of Acoustic enclosure: (i) The enclosure is modular in construction. (ii) Base frame is made of sheet metal. (iii) Durable industrial locking system is provided on doors. (iv) Door gaskets are made in high quality EPDM material.(c) Corrosion Resistance: To make the enclosure weather proof:-(i) All sheet metal parts I components are hot dipped in seven tanks process, pretreated and passivated. (ii) Sheet metal components are with pretreated and passivated base powder coated. (iii) Base frame is epoxy coated 1 powder coated. (iv) Zinc passivated hardware's are used to avoid rusting. Acoustic insulation: (i) Sound proofing of the enclosure is done with quality rockwool confirming to IS:8183 standard.(ii) Acoustic foam shall be fire retardant and fire resistant. (iii) Attenuates are provided to control sound at entry and exit of container. (iv) Specially designed residential silencer is provided. (d) Ventilation And Air Circulation: Exhaust pipe inside enclosure is thoroughly insulated by cladding of rock wool and sheet. (e) Electrical: Neutral body earthing points at the sides of enclosure are isolated through moulded compound. (f) Safeties: Emergency push button to stop the DG set from outside, low fuel oil level, low lube oil pressure, low coolant level, high engine temperature. The canopies being offered are for output of noise level :S 75 dbA at a distance of 1-meter average, as per the CPCB IV norms. Batteries: 02 Nos. 12V 180 Ah batteries with leads for electric starting. Paint: DG set and panel package will be painted with powder coated type paint. STANDARD GENSET CONTROLLER UNIT WITH CONTROL PANEL: Genset controller unit with totally enclosed, steel construction control panel suitable for outdoor floor mounting installation having standard safeties and display parameters.(a) Bus bar with electrolytic copper bus bar (for mains and DG supply incoming and outgoing) suitable for 1000 Amps capacity for 3 phase and neutral (TPN) (all connection inside the panel shall r be through aluminium strip) connected duly supported with FRP _insulators including colour code } heat shrink insulating sleeves. (b) Three phase 4 pole, power contractor, 1000 Amps for ON-OFF the DG and mains supply- 02 Automatic generator controller unit with total control wiring with necessary relays and control fuses available contract-01 |
| 44 | Supply & Fixing/Laying Double Wall Corrugated (DWC) HDPE Pipes of outer dia 160 mm including 90 degree bends, with coupler and rubber ring, confirming to IS:16205 Part 24 Type 450N, for laying of LT cables protection in trenches etc complete with all accessories all as specified and directed. |
| 45 | Supply & Fixing/Laying Double Wall Corrugated (DWC) HDPE Pipes of outer dia 120 mm including 90 degree bends, with coupler and rubber ring, confirming to IS:16205 Part 24 Type 450N, for laying of LT cables protection in trenches etc complete with all accessories all as specified and directed. |
| 46 | Supply & Fixing/Laying Double Wall Corrugated (DWC) HDPE Pipes of outer dia 63 mm including 90 degree bends, with coupler and rubber ring, confirming to IS:16205 Part 24 Type 450N, for laying of LT cables protection in trenches etc complete with all accessories all as specified and directed. |
| 47 | Supply & Fixing/Laying Double Wall Corrugated (DWC) HDPE Pipes of outer dia 40 mm including 90 degree bends, with coupler and rubber ring, confirming to IS:16205 Part 24 Type 450N, for laying of LT cables protection in trenches etc complete with all accessories all as specified and directed. |
| 48 | M&L for cable route indicator duly embossed 11KV for HT UG cable of 11000 volts 80mm dia CI plate marked on HT cable bolted with 40x5mm flat iron of hight 0.4mtr embedded in PCC 1:3:6 type C2 ofsize20x20x30CM block complete all as spd and directed . |
| 49 | S&F LT cable junction box dust and water proof made out of PVC non metallic sheet FRP type, factory made out of PVC non metallic sheet FRP type, factory made, size of box 250mm x 200 mm x 100 mm deep with swivelling cover and locking clamp, MS clamps and nuts, bolts, for fixing the box on steel tubular pole, consisting of aluminium bus bar strip 150mm x 30 mm x 3 mm - 04 no's mounted on pole and provision of incoming and outgoing PVC insulated cable with grommets including inbuilt 6 Amp MCB SP 10 KA-01 No complete all as specified and directed. |
| 50 | Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor 04 Sqmm 2 core lSI marked LT Cross Linked Polythene insulated (XLPE insulated) galvanised steel strip armoured electric cable along the poles or passing through pipes or laid under floor or through pipes or laid under floor of through walls etc |
| 51 | Supply, installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 20 KA/3- sec,outdoor (IP-54), RMU (Ring main unit) 4-way comprising of 02 Nos motorized operated Load break Switch and 02 Nos 630 Amp Fixed-Type motorized spring-charging VCB electrolytic grade copper busbars all inside single, gas-filled; robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank with min. thickness 3+0.5 mm, IP 67 Degree of Protection, internal-arc classified 20KA/1 sec, on-site site repairable with site with site replicable bushing coupling/mechanism, gas refilling etc. The enclosure shall have padlock able double-door access with anti-theft hinges, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit along with Bus-connected, fixed-type Auxiliary transformer shall include the following along with all necessary accessories and fittings as required at site.(A) 02 Nos Incoming Load Break Switch module each. consisting of following accessories :~ (i) Each switch combines the function of switch-disconnector an earthing switch.(ii) 11 KV, 630 A Load Breaker Switch with interlocking fine earthing scheme both short circuit current, 21 KA for 3 sec making capacity- 50 kAp-01 No.(iii) Auxiliary contacts - 01 No + 1 NC ~ 01 No. (iv) Spring assisted motorized mechanism with un-inhabited operating shaft for emergency manual operation with integrated earthing switch - 01 No (v) Cable terminals cable bushing situated not beyond 300 mm or as per· OEM tested design from cable cover to allow ease of access for installation/testing with door arrangement for enhanced safety (IP54+ IP3X) interlocked to prevent access of size upto 11' KV, 300 Sqmm 3 core, along with XLPE AL cable termination/End kits each set of 3 |
| 52 | (vi) Right angle boots (push on type) Each set of 3 (vii) Arc proof cable covers having cable entry from bottom, front with interlocking mechanism including earth switch- 01 No(viii) Capacitive voltage indication fixed type system as per IEC 6123 with LED- 01 Set ((ix) Fault passage indicator - it is to be provided for each incomer Load break unit, FPI with LED/digital display to be added to detection of cable Dault - 01 No.(x) ON, OFF, Earth mechanical indication on the front mimic of the panel - 01 No cable cover standard -01 (xi) Mechanical interlock to be provided between both incomer to prevent simultaneously and accidently closing of both supplies.(B) 02 Nos Outgoing VCB module each consisting of following accessories :B) Outgoing VCB module- Each consisting of following accessories :-(i) Each function - unit consist of a vacuum - circuit breaker in combination with a three position - switch. The three-position switch fulfils the operation of the Amp fixed type VCB module with series disconnect or cum earthing switch of short circuit breaking disconnect or and earthing function.(ii) 11 KV, 630 current/withstand, 21 KA for 3 Sec making capacity - 50 kip - 01 No (iii) Auxiliary contacts - 01 No + 1 NC - 01 No (iv) Stored- energy motorized high - endurance spring charging mechanism (M1+) with inbuilt spring charging lever and mechanically latched ON/OFF push - buttons to allow handle less and uninhabited operation - or No (v) Cable terminals cable bushing situated not beyond 300 mm or as per OEM tested design from cable cover to allow ease of access for installation/testing with door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access up to 11 KV, 300 Sqmm, 3 core, along with XLPE AL Cable termination each set of 3. (vi) Right angle boots (push on type) Each set of 3.(vii) 3 0/C+ 1 E/F self powered numerical protection relay with low and high set for over current and Earth fault. Relay should have facilities to display the maximum loaded phase current also. Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol - 01 No/per VCB outgoing. (viii) Auxiliary Relay for OTI/WTI~ transformer protection - 01 No(ix) Associated ring core cast - resin insulated CTs .Dual ratio 100/50/1-1 Amp (for metering and protection) for both outgoing 2.5 VA, 5 P 10 protection - Each set of 3 (x) Arc proof cable covers having cable entry from bottom, front with interlocking mechanism including earth switch - 01 No. (xi) Capacitive voltage indication fixed type system as per IEC 6123 with LED - 01 Set. (xii) ON1 OFF; Earth mechanical indication on the front mimic of the panel - 01 No (xiii) Emergency trip push button. - 01 No (xiv) CB mechanical operation should be min 10000 Nos without any maintenance. (xv) Vacuum Interrupter and VCB must be RMU manufacturers own make better life cycle optimization. (xvi) CB operating sequence should be 0-0.3 sec-C0-3min_CO |
| 53 | (C) Bus connected, fixed type potential and Auxiliary transformer with floor mounted compartment of matching height and depth, positioned alongside RMU to provide required aux. supply for spring charging motor and metering consisting of following accessories :-(i) 2x12 Volt DC battery SMF type not less than 42 AH-01 Set (ii) 230 VAC/24 VDC Battery charger - 01 No, with indication of status of functioning. (iii) HRC fuse links for primary side isolation and AC/DC MCBs for secondary isolation - 01 Set (iv) Digital voltmeter & RYB LED indications to confirm AC/DC supply availability - 01 set (v) Anti condensation space heater with thermostat - 01 No (vi) LED lamp for illumination and 3 ion socket with switch - 01 No (D) Additional equipment delivered separately or mounted separately:- (i) Portioning Handle for manual Isolator/Disconnect or/Earthing Operation - 02 Nos (ii) Standard Manometer- 01 No (iii) Operation and maintenance manual- 01 No (iv) Installation and commissioning manual- 01 No (v) Cable clamping provision (standard)- 01 No (vi) RMU Foundation as per OEM Recommendation (Earth work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.60 mars from ground level.Note :- (i) It is preferable to have all feeder-switches inside single stainless steel compartment with incliner feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessary interlocking arrangement shall be provided for safety and operations.(iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/efectricafjshort-circuit operations, gas leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered.(iv)The above module consisting of load break switches and VCBs shall be aligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on platform as recommended by OEM. (v) The OEM should provide 2 years manufacturing warranty including service support at site without any cost from the date of commissioning of RMU at site. Certificate for the same to be submitted by OEM at the time of delivery. The rate quoted by the bidder shall include the service cost of RMUs and no extra claim be entertained at later stage. |
| 54 | Supply, installation, testing and commissioning of isolation Transformer 3 phase, 50 Hz, capacity 630 KVA, indoor type, copper wound, oil cooled, class of insulation A, metallic body powder coated design-ned for input Voltage range 415V, +- 5% and output Voltage range 415V +-with ration, with ration of 1:1 Vector group : Dyn 11, Delta-Star with first filling of transformer oil of requisite dielectric strength up to level, efficiency more than 95%, separate neutral bushing shall be brought out for earthing, potential difference between neutral less than one volt with all standard fittings like digital temperature meter, lifting hooks one set, Earthing terminal two nos. Note: Isolation Transformer foundation as per OEM Recommendation (Earth work and PCC works) for placing Isolation transformer on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.60 mtrs from ground level. |
| 55 | Supply, installation, testing and commissioning of Servo Voltage Stabilizer Capacity 630 KVA, 3 phase, 50 Hz (confirming as per BIS : 9815 Part 1 : 1994 reaffirmed 2019) Naturally Oil Cooled1 indoor/unbalanced type1 copper wound, Digital Display type1 relay free smooth and silent operation with 1st filling of Transformer oil (IS-335-2018) having following specification (a) Input voltage 360V-480V (b)Output voltage 415 V +- 1% (Adjustable) (c) Rated frequency 50 Hz (d) No distribution in wave form (e)response time not to exceed 10 Mile seconds (f) Sensitive ( +-) 1% (g) Rate of correction more than 6 Volt / second for per phase (h) Class of insulation A (i) No load losses less than 0.5% (j) Full load losses less than 2.5% (k) Duty cycle- continuous 24 x 7 (I) Efficiency more than 95% (m) Type of load 3 phase1 unbalanced type (n) Digital display Voltmeter/Ammeter complete with all fixing accessories all as directed by Engr-in-Charge Note : Servo Voltage stabilizer foundation as per OEM Recommendation (Earth work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.60 mtrs from ground level. |
| 56 | Supply, installation1 testing and commissioning of AMF panel indoor type floor mounted confirming of IS 8623 Part (one), CPRI approval, totally enclosed vermin proof suitably ventilated, factory built, modular, sectionalised, compartmentalized, extendable type suitable for operation on 3 phase, 4 wire 433/415 Volts, 50Hz, AC supply. The outer Sheel shall be fabricated out of 3.0mm thick CRCA sheet & MS angle section of suitable size for frame and compartmentalized inner shell shall be fabricated of out of 1.6 mm thick CRCA sheet for control gear. Front and back door operating with locking arrangement at front and back. This panel shall have mini9mum busbar at suitable capacity with colour insulating type/PVC sleeves mounted on suitable size \\"F' class non hygroscopic, non combustible insulators, provision for fixing of MCCBs/MCBs necessary interconnection with busbar /strip with colour code insulation with CT/PI & ammeter of required size. The panel shall have vibration free structure with Protection of enclosure IP 65 as per IS-2147 of 1962 with pre-treatment through 7 tank hot chemical process prior to powder coated with minimum 50-70 micron of approved colour. The bottom of outer shell contains a detachable gland plates shall be fabricated out of 3mm thick CRCA sheet having provision for entry of armoured cable of adequate size complete with stiffeners wherever required. The entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor. wires I copper strips, neutral links, control wiring with 2.5 sqmm. & 4.0 sqmm. The panel shall be provided with manufacturer rime plate, heavy duty SS cable glands of adequate size for incoming and outgoing cables. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bones and skull to be provided. |
| 57 | EPDM gasket of appropriate shape and size provided at all joints, door and covers including suitable size angle iron/flat iron frame work/support required with four legs 60cm long using angle iron 40x40x6mm duly painted with anti corrosive paint, air passing holes and locking arrangement at front with ·duplicate keys and making connection of incoming and outgoing cable using proper cable lugs, 4 x legs grouted in PCC 1:2:4 and making good disturbed surface complete including providing and fixing following switch gears and as per schedules and technical specifications etc.Motorized On load change over switch Capacity 1000 Amp- 02 NosMain IC ACB 4 pole 1000 amps 50 KA, 415 Volt Micro processor based with manual draw out UW-MTX 1G -01 NO (INCOMING)ACB 4 pole 1000 amps 50 KA, 415 Volt Micro processor based with manual draw out UW-MTX 1G -01NO (DG Incoming I/ C)Bus coupler ACB 4 pole 1000 amps 50 KA, 415 Volt Micro processor based with manual draw out UW-MTX1G -01 NoBypass system for Manual operating Change over switch capacity 1000 Amp - 01 NoElectrical & Mechanical Interlocking Interlocking system- 01 JobDigital Multi Function Meter- 01 NoIndicator lamp RYB (3 Nos)- 01 SetProtection MCB 6 Amp SP- 01 NoCurrent Transformer 1000/5 AmpDanger PlateBus bar Chamber 1500 Amp 4 Strip Aluminium - 04 (RYBN |
| 58 | Supply, installation, testing and commissioning of LT panel outdoor type floor mounted confirming Each of IS 8623 Part (one), CPRI approval, totally enclosed vermin proof suitably ventilated, factory built, modular, sectionalised, compartmentalized, extendable type suitable for operation on 3 phase, 4 wire 433/415 Volts, 50Hz, AC supply. The outer Sheel shall be fabricated out of 3.0mm thick CRCA sheet & MS angle section of suitable size for frame and compartmentalized inner shell shall be fabricated of out of 1.6 mm thick CRCA sheet for control gear. Front and back door operating with locking arrangement at front and back . The panel shall have aluminium Busbar at suitable capacity with colour insulating type/PVC sleeves mounted on suitable size \\"F' class non hygroscopic, non combustible insulators, provision for fixing of MCCBs/MCBs necessary interconnection with busbar /strip with colour code insulation with CT/PI & ammeter of required size. The panel shall have vibration free structure with Protection of enclosure IP 65 as per IS-2147 of 1962 with pre-treatment through 7 tank hot chemical process prior to powder coated with minimum 50-70 micron of approved colour. The bottom of outer shell contains a detachable ·gland plates shall be fabricated out of 3mm thick CRCA sheet having provision for entry of armoured cable of adequate size complete with stiffeners wherever required. The entire panel shall have a coml1)on earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires I copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm.The panel shall be provided with manufacturer name plate, heavy duty SS cable glands of adequate size for incoming and outgoing cables. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bones and skull to be provided. |
| 59 | angle iron/flat iron frame work/support required with four legs 60cm long using angle iron 40x40x6mm duly painted with anti corrosive paint, air passing holes and locking arrangement at front with duplicate keys and making connection of incoming and outgoing cable using proper cable lugs, 4 x legs grouted in PCC 1:2:4 and making good disturbed surface complete including providing and fixing following switch gears and as per schedules and technical specifications etc.Incoming:-ACB 4 pole 1000 amps 50 KA, 415 Volt with manual draw out UW-MTX 1G -01 NO (INCOMING)Insulated Bus bar of aluminium of 1500 Amps capacity for three phase, fixed on insulators, Busbar ·should be PVC sleeved with'Red, Yellow, Blue, green Colour, Bus bar support should be of SMC/DMC,Rated Impulse Withstand Voltage 8KV -01 SetOutgoing:-MCCB 315 Amp ,415 Volt,35 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = % Icu at 415 V (kA rms) 50%,frame tvoe,Confirms to IS/IEC60947-2 - 01 NO CAPACITOR BANK MCCB 250 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity leu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = % leu at 415 V (kA rms) 50%,frame type, Confirms to IS/IEC60947-2- 04 NOs {03 OUTGOING 01 standby) UPS, AC PlantMCCB 160 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = %leu at 415 V (kA rms) 50%,frame type, Confirms to IS/IEC60947-2 -02 NO (OUTGOING 01 Standby) DCPPMCCB 125 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity leu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = %leu at 415 V (kA rms) 50%,frame type, Confirms to IS/!EC60947-2 -03 NOs (OUTGOING 02 Standby 01) Bldg, Server Room, Fire Fighting MCCB 63. Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity leu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = %leu at 415 V (kA rms) 50%,frame type, Confirms to IS/IEC60947-2 -02 NOs (01 OUTGOING 01 Standby)Digital timer switch with Timeline DBs outdoor type factory made powder coated all along internal and external surfaces, weather proof dust/water proof with IP 55 protection, consisting of 01 No AC contractor three phase 32 Amp capacity 25 KA, one digital Timer switch three no's MCB 32 Amp 10 KA toggle switch having both auto manual and by pass system - 01 No(b) Digital Voltmeter of size 96x96mm (0-SOOV) with built in selector switch.(c) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch.(d) Indication lamp 22.5mm dia LED type 240vofts ACto show three phase availability-01Set. |
| 60 | Supply, installation, testing and commissioning of lT panel indoor type floor mounted confirming of IS 8623 Part (one), CPR! approval, totally enclosed ,vermin proof suitably ventilated, factory built modular, sectionalised, compartmentalized, extendable type suitable for operation on 3 phase, 4 wire 433/415 Volts, 50Hz, AC supply. The outer Sheel shall be fabricated out of 2.0mm thick CRCA sheet & MS angle section of suitable size for frame and compartmentalized inner shell shall be fabricated of out of 1.6 mm thick CRCA sheet for control gear. Front and back door operating with locking arrangement at front . The panel shall have aluminium Busbar at suitable capacity with colour insulating type/PVC sleeves mounted on suitable size \\"F' class non hygroscopic, non combustible insulators, provision for fixing of MCCBs/MCBs necessary interconnection with busbar /strip with colour code insulation with CT/PT & ammeter of required size. The panel shall have vibration free structure with Protection of enclosure IP 55 as per IS-2147 of 1962 with pre-treatment through 7 tank hot chemical process prior to powder coated with minimum 50~70 micron of approved colour. The bottom of outer shell contains a detachable gland plates shall be fabricated out of 3mm thick CRCA sheet having provision for entry of armoured cable of adequate size complete with stiffeners wherever required. The entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires I copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm.The panel shall be provided with manufacturer name plate, heavy duty SS cable glands of adequate size for incoming ancj outgoing cables. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bones and skull to be provided. |
| 61 | EPDM gasket of appropriate shape and size provided at all joints, door and covers including suitable size angle iron/flat iron frame work/support required with four legs 60cm long using angle iron 40x40x6mm duly painted with anti corrosive paint, air passing holes and locking arrangement at front with duplicate keys and making connection of incoming and outgoing cable using proper cable lugs, 4 x legs grouted in PCC 1:2:4 and making good disturbed surface complete including providing and fixing following switch gears and as per schedules and technical specifications etc.Incoming:-MCCB 250 Amp ,415 Volt,25 KA, 4 pol~ Rated Ultimate Short-circuit Breaking Capacity leu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics =% leu at 415 V (kA rms) 50%,frame overconforms to IS/IEC60947-2 -01 NO (OUTGOING)Insulated Bus bar of aluminium of 400 Amps capacity for three phase, fixed on insulators, Busbar shouldbe PVC sleeved with Red, Yellow, Blue, green Colour, Bus bar support should be of SMC/DMC, RatedImpulse Withstand Voltage 8KV -01 SetOutgoing:-MCCB 63 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity leu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = % leu at 415 V (kA rms) 50%,frame overconforms to IS/IEC60947-2 -08 NO(b) Digital Voltmeter of size 96x96mm (0-SOOV) with built in selector switch.(c) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch.(d) Indication lamp 22.5mm dia LED type 240volts ACto show three phase availability-01Set. |
| 62 | Supply, installation, testing and commissioning of LT panel indoor type floor mounted confirming of Each IS 8623 Part (one), CPRI approval, totally enclosed vermin proof suitably ventilated, factory built, modular, sectionalised, compartmentalized, extendable type suitable for operation on 3 phase, 4 wire433/415 Volts, 50Hz, AC supply. The outer sheaf shall be fabricated out of 2.0mm thick CRCA sheet & MS angle section of suitable size for frame and compartmentalized inner shell shall be fabricated of out of 1.6 mm thick CRCA sheet for control gear. Front and back door operating with locking arrangement at front . The panel shall have aluminium Busbar at suitable capacity with colour insulating type/PVC sleeves mounted on suitable size \\"F' class non hygroscopic, non combustible insulators, provision for fixing of MCCBs/MCBs necessary interconnection with busbar /strip with \\"Supply, installation, testing and commissioning of LT panel indoor type floor mounted confirming of Each IS 8623 Part (one), CPRI approval, totally enclosed vermin proof suitably ventilated, factory built, modular, sectionalised, compartmentalized, extendable type suitable for operation on 3 phase, 4 wire 433/415 Volts, 50Hz, AC supply. The outer sheaf shall be fabricated out of 2.0mm thick CRCA sheet & MS angle section of suitable size for frame and compartmentalized inner shell shall be fabricated of out of 1.6 mm thick CRCA sheet for control gear. Front and back door operating with locking arrangement at front . The panel shall have aluminium Busbar at suitable capacity with colour insulating type/PVC sleeves mounted on suitable size \\"\\"F' class non hygroscopic, non combustible insulators, provision for fixing of MCCBs/MCBs necessary interconnection with busbar /strip with colour code insulation with CT/PT & ammeter of required size. |
| 63 | The panel shall have vibration free structure with Protection of enclosure IP 55 as per IS-2147 of 1962 with pre-treatment through 7 tank hot chemical process prior to powder coated with minimum 50-70 micron of approved colour. The bottom of outer shell contains a detachable gland plates shall be fabricated out of 3mm thick CRCA sheet having provision for entry of armoured cable of adequate size complete with stiffeners wherever required. The entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires I copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm.The panel shall be provided with manufacturer name pfate,heavy duty SS cable glands of adequate size for incoming and outgoing cables. Computer cut self adhesive vinyl danger notice platehaving conventional symbol of bones and skull to be provided. EPDM gasket of appropriate shape and size provided at all joints, door and covers including suitable size angle iron/flat iron frame work/support required with four legs 60cm long using angle iron 40x40x6mm duly painted with anti corrosive paint, air passing holes and locking arrangement at front with duplicate keys and making connection of incoming and outgoing cable using proper cable lugs, 4 x legs grouted in PCC 1:2:4 and making good disturbed surface complete including providing and fixing following switch gears and as per schedules and technical specifications etc.Incoming:-MCCB 125 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics =%leu at 415V (kA rms) 50%,frame overconforms to IS/IEC60947-2 -01 NO Insulated Bus bar of aluminium of 400 Amps capacity for three phase, fixed on insulators, Busbar should be PVC sleeved with Red, Yellow, Blue, green Colour, Bus bar support should be of SMC/DMC, Rated Outgoing:-MCCB 63 Amp ,415 Volt,25 KA, 4 pole Rated, Ultimate Short-circuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = %leu at 415 V (kA rms) 50%, frame overconforms to IS/IEC60947-2 -04 NO MCCB 40 Amp ,415 Volt,16 KA, 4 pole Rated Ultimate Short-circuit Breaking capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics =% Icu at 415 V (kA rms) 50%, frame overconforms to IS/IEC60947-2 -02 NO (b) Digital Voltmeter of size 96x96mm (0-500V) with built in selector switch. (c) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch. (d) Indication lamp 22.5mm dia LED type 240volts ACto show three phase availability-01Set. Please Enable Macros to View BoQ information |
| 64 | The panel shall have vibration free structure with Protection of enclosure IP 55 as per IS-2147 of 1962 with pre-treatment through 7 tank hot chemical process prior to powder coated with minimum 50-70 micron of approved colour. The bottom of outer shell contains a detachable gland plates shall be fabricated out of 3mm thick CRCA sheet having provision for entry of armoured cable of adequate size complete with stiffeners wherever required. The entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires I copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm.The panel shall be provided with manufacturer name pfate,heavy duty SS cable glands of adequate size for incoming and outgoing cables. Computer cut self adhesive vinyl danger notice platehaving conventional symbol of bones and skull to be provided. EPDM gasket of appropriate shape and size provided at all joints, door and covers including suitable size angle iron/flat iron frame work/support required with four legs 60cm long using angle iron 40x40x6mm duly painted with anti corrosive paint, air passing holes and locking arrangement at front with duplicate keys and making connection of incoming and outgoing cable using proper cable lugs, 4 x legs grouted in PCC 1:2:4 and making good disturbed surface complete including providing and fixing following switch gears and as per schedules and technical specifications etc.Incoming:-MCCB 125 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short-circuit Breaking Capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics =%leu at 415V (kA rms) 50%,frame overconforms to IS/IEC60947-2 -01 NO Insulated Bus bar of aluminium of 400 Amps capacity for three phase, fixed on insulators, Busbar should be PVC sleeved with Red, Yellow, Blue, green Colour, Bus bar support should be of SMC/DMC, Rated Outgoing:-MCCB 63 Amp ,415 Volt,25 KA, 4 pole Rated, Ultimate Short-circuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = %leu at 415 V (kA rms) 50%, frame overconforms to IS/IEC60947-2 -04 NO MCCB 40 Amp ,415 Volt,16 KA, 4 pole Rated Ultimate Short-circuit Breaking capacity Icu at 415 V (kArms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics =% Icu at 415 V (kA rms) 50%, frame overconforms to IS/IEC60947-2 -02 NO (b) Digital Voltmeter of size 96x96mm (0-500V) with built in selector switch. (c) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch. (d) Indication lamp 22.5mm dia LED type 240volts ACto show three phase availability-01Set. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail