| 1 | M&L for dismantling of old unserviceable ACSR or AAC conductors, all as specified and directed |
| 2 | M&L for dismantling of old u/s GI earth wire or service feeder or distribution span all as specified and directed |
| 3 | M&L for dismantling cross-arms of M.S. channel or angle sections etc. complete all as specified and directed |
| 4 | M&L for dismantling of old u/s insulators of any type and any size all as specified and directed. |
| 5 | Taking down old /unsv street light fittings with lamp bracket & set of clamps of any size by disconnecting of electric connection carefully & refixing to its original position with new copper cable from junction box to fittings complete all as specified and directed.. |
| 6 | Supply and fixing in replacement moulding compound street light junction box of size 250 mm x 250 mm x 160mm complete with shock and rust proof, termite resistant, tamper proof , front openable type for 3 phase 4 core cable size upto 25 sqmm incoming & outgoing loop -in loop connection and providing DIN rail for mounting one no. MCB including 6A MCB, clamps made out of MS flat iron 25 X 4 mm ,MS hexagonal bolts, nuts and washer for arrangement to pole /surface complete all as specified and directed.. |
| 7 | Supply and Fix, Two core PVC insulated copper cable with multistranded copper condutor of size 1.0 sqmm x two core, and drawing in to PVC Conduits & GI pipe bracket and connect to street light fittings complete all as specified and directed. |
| 8 | M&L for rigid non-metallic PVC FRLS conduit heavy duty of size 20 mm external dia, exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, to be fixed along the pole and including taking down complete all as specified and directed. |
| 9 | M & L for Painting to street light steel tubular pole of any type with two coat of aluminium paint after cleaning to rusted portion of pole and finishing the surfaces including one coat primer top to bottom, painting on FI clamps/street light brackets of any type including making alternative black and yellow strip or as per user direction with synthethic enemelled paint up to 1.5 Mtr height from ground level & writing of pole numbers with black paint on poles all as specified and directed. |
| 10 | Supply laying & testing of XLPE insulated, armoured, heavy duty electric under ground cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with crimping of suitable size aluminium lugs complete of size 16 Sqmm nominal cross section x 4 core. |
| 11 | Description all as per above item no 10.00, but 25 Sqmm nominal cross section x 4 core. |
| 12 | Description all as per above item no 10.00, but 35 Sqmm nominal cross section x 3.5 core. |
| 13 | Description all as per above item no 10.00, but 70 Sqmm nominal cross section x 3.5 core. |
| 14 | Description all as per above item no 10.00, but 95 Sqmm nominal cross section x 3.5 core. |
| 15 | Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for laying of cables, pipes etc. and getting out all excavated material in any type of soil complete all as specified and directed. |
| 16 | Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed. |
| 17 | Removing of excavated surplus soil to a distance not exc 50 m and depositing where directed at a level not exc. 1.5 m above the starting point complete all as specified and directed. |
| 18 | M&L of locally available river sand in trenches below and above / around UG cable for cable protection, in duct under & above the cables including punning around cable complete all as specified and directed.Note - Punned thickness shall only be measured and paid. |
| 19 | Supply and laying unreinforced PCC Cable protection cover, class LV, type-1 flat with size 250 x 150 x 40 mm laid flat width wise complete all as specified and directed. |
| 20 | M&L for Tubes, 'light grade,galvanised, with all fitting of size 40 mm ;laid in trenches or fixed in wall with saddles for cable protection/ mounting security lights incl bending and cutting to required length all as specified and directed |
| 21 | M&L for Tubes, 'light grade,galvanised, with all fitting of size 50 mm ;laid in trenches or fixed in wall with saddles for cable protection/ mounting security lights incl bending and cutting to required length all as specified and directed |
| 22 | M&L earthing GI Strip complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified.Note: The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point. |
| 23 | M&L earthing GI Strip complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron 4 mm wire by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified.Note: The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point. |
| 24 | S & F for sheet metal enclosure MCB TPN DB 4 way with 200 Amps rated bus bar 415 volts double door with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 25 | S & F for MCB tripple pole and neutral rated capacity 63 Amps, 415 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed. |
| 26 | Supply & Fix MCB SP 6 to 32 Amps current rating 'C' series 10 KA breaking capacitycomplete all as specified and directed. |
| 27 | M&L for providing under ground boring using mechanical pneumatic drilling equipment / manually for passing electric cables through by providing HDPE pipe of 100mm dia heavy quality, pressure rating 6 kg/cm2 under the existing bituminous/WBM road/PCC hard standings, depth range not more than 1.5mtr deep and making good the distrubed surfaces is to match with its existing specifications all as specified and directed.Note : Any damage to the existing cables/water pipes/structures shall be made good by the contractor at his own expense. |
| 28 | Supply, Installation, testing and commissioning of LT out door type panel board of suitable size factory assembled and fabricated(CPRI approved) and of suitable size and angle iron channel and MS sheet 3 mm to 3.15 mm thick (Inner compartment is 2.0mm thick) double door type, front and rear openable with locking arrangement duly powder coated, painted with metallic paint of approved colours, and independely housing for each control switch gear duly pre wired with colour coding for three phases and neutral, aluminum bus bar 600 Amps for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incomming and outgoing cables,grouting the panel boardon suitablePCC foundation , structure made out of equal angle iron of size 50x50x6 mm complete with the following switch gears/accessories:- (Contd 28.01...../-) |
| 29 | Incoming:- (For item No. 28.00)(a) MCCB TPN 400 Amps, 50 KA, 415 Volts, Ics=100% Icu, Adjustable short circuit setting type-01 Nos (b) Ammeter 0-600 Amps with CT rating and selector switch -01 Nos (c) Volt meter with selector switch 0-500 volt-01 Nos(d) Indicating lamp(RYB)-01 setOutgoing :- (a) MCCB TPN 125 Amps, 35 KA, 415 Volts, Ics=100% Icu, Adjustable short circuit setting type-03 Nos (b) MCCB TPN 63 Amps, 35 KA, 415 Volts, Ics=100% Icu, Adjustable short circuit setting type-05 Nos (c) MCB TPN 32 Amps, 16 KA, 415 Volts-01 Nos (d) Three Phase nature switch 12 KW, automatic switching on / off street light based on lux level of nature light, consisting of sensor, overload protection fuse gear, power contactor and MCB of suitable capacity, terminal blocks for cable entry & control unit enclosed in pole / wall mountable enclosure made out of rust proof, shock proof, termite proof FR grade SMC, conforming to IP 54, with universal lock and key arrangement complete all as specified and as directed.Make of nature switch :Swadeep Cat No. Navdeep-54-12kW3P or equivalent in Havells /Indoasian Note : Drawing of LT panel shall be submitted by the contractor duly showing the size and dimention of MCCBs/MCBs and Bus Bar and should be got duly approved by Engr In charge before execution at site. |
| 30 | Supply , installation , testing and commissioning LT PANEL board outdoor type (CPRI Approved) of suitable size Kiosk type factory assembled fabricated and of suitable size angle iron, channel and MS sheet 3 to 3.15 mm thick (inner compartment is 2.0 mm thick) double door type, front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and natural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables cubical type duly powder coated over a coat of primer, grouting of panel 60 cm above the ground level by provisioned 90 cm long angle iron frame bottom of panel 40 x 40 x 5 mm thick, welded on all four corners, embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate up to 30 cm and grouting the panel board on and including suitable size foundation structure with the following components. (a) MCCB 250 Amps capacity 4 pole, 16 KA, 415 V Ics =100 % Icu Adjustable short circuit setting type ( incoming ) - 01 Nos. (b) MCCB 63 Amps capacity 4 pole, 10 KA, 415 V Ics =100 % Icu Adjustable short circuit setting type type ( outgoing) - 06 Nos. (c) MCB TPN 40 Amp - 04 Nos (d) Aluminium Bus bar of capacity 400 Amps 3 phase and neutral -1 set. (e) Digital type Ammeter with CT of suitable ratio for reading up to 400 amps load-01 Nos (f) Digital type voltmeter 0-500 volts. (g) Set of indicating lamp with toggle switch RYB -01 Set. |
| 31 | Supply , installation , testing and commissioning LT PANEL board outdoor type (CPRI Approved) of suitable size Kiosk type factory assembled fabricated and of suitable size angle iron, channel and MS sheet 3 to 3.15 mm thick (inner compartment is 2.0 mm thick) double door type, front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and natural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables cubical type duly powder coated over a coat of primer, grouting of panel 60 cm above the ground level by provisioned 90 cm long angle iron frame bottom of panel 40 x 40 x 5 mm thick, welded on all four corners, embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate up to 30 cm and grouting the panel board on and including suitable size foundation structure with the following components. (a) MCCB 160 Amps capacity 4 pole, 36 KA, 415 V Ics =100 % Icu Adjustable short circuit setting type ( incoming ) - 01 Nos.(b) MCCB 63 Amps capacity 4 pole, 16 KA, 415 V Ics =100 % Icu Adjustable short circuit setting type type ( outgoing) - 04 Nos. (c) MCB TPN 40 Amp 3 Phase and neutral - 02 Nos(d) Aluminium Bus bar of capacity 400 Amps 3 phase and neutral -1 set.(e) Digital type Ammeter with CT of suitable ratio for reading up to 400 amps load-01 Nos(f) Digital type voltmeter 0-500 volts.(g) Set of indicating lamp with toggle switch RYB -01 Set. |
| 32 | Supply , fix , test & commissioning in replacement of LT weather proof panel board powder coated out door type double door shutter type made out of CRCA 3.15 mm thick outer and 1.6mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outdoor, floor mounting type with closed bus bar , chamber and with aluminium bus bar of cap 200 Amp with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digital ammeter 0-500A, digital voltmeter 0-500Volts, CT's of suitable ratio, indicator lamps R-Y-B,selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc.The bottom portion of enclosure shall be minimum 30 cm above ground level of legs of angle iron ) consisting of following accessories :- a) Aluminium bus bar capacity 200 Amps for Phase-R-Y-B-3 Nos & 200 Amps for neutral -1 No . Neutral link-01 Nob) MCCB TPN 25 KA, 125 Amp - 1 No (I/C) c) MCB TPN 63 Amps- 03 Nos (O/G) (d) MCB SP 20 Amps -06 Nos( O/G) |
| 33 | Supply and fix in repair of automatic street light switch using infrared sensor based on nature switch and voltage monitoring system (VMS) series for automatic switching of street lights. Nature switch operation should be based on nature light lux level. Required illumination level for switching ON is <30 lux and for switching OFF >10 lux.VMS should have adjustable over & under voltage trip level and protection against phase loss, neutral loss & phase reverse. The nature switch along with suitable power contactors , incoming and outgoing MCBs should be enclosed in a pole/ wall mountable enclosure made of rust proof , electric shock proof and FR grade SMC junction box with hinged lid confirming to IP 54 complete all as specified for the following: -a) Suitable of three phase load of 8-12 kw with contactors (single phase 3Nos), incoming& OutgoingMCB SP (6 Nos),rating of 32 Amps per phase & circuit wiring of min 10 sqmm. Make -Swadeep Cat No. Navdeep-54-12kW3P or equivalent in Havells / C & S / Bajaj / Philips |
| 34 | Supply and install Inverter type hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser for better indoor air quality with minimum 5 star rating and EER 3.2 of capacity 2 TR complete all as specified and directed by engineer in charge. |
| 35 | M & L sub main wiring with 2 runs of 04 sqmm single core multistranded FRLSH PVC copper wire as main wire along with 1 run of 04 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC concealed / surface conduit (medium grade) wherever necessary with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the disturbed surface by plastering and 02 coats of wall putty incl distempering to match with the existing surface complete all as specified and directed.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 36 | S & F repair metal plug and socket DB,double pole 240 Volts and including one 20 Amp MCB SP ,'C' Curve , ISI marked including taking down, complete all as specified and as directed. |
| 37 | S & F for sheet metal enclosure MCCB VTPN DB 4 way with 200 Amps rated bus bar 415 volts double door with magnitic locking system having provision of Incomer as MCCB upto 160 Amp including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 38 | Supply and fix of MCCB 3 Pole, 415 V, fixed type, 125 Amps with breaking capacity 25 KA in DB complete all as specified & directed. |
| 39 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and directed. |
| 40 | Supply and install inverter type Hi wall split units indoor / outdoor complete with cordless remote control unit and with in built air ioniser for better indoor air quality with minimum 5 star rating and EER 3.2 of capacity 1.5 TR complete all as specified and directed. Please Enable Macros to View BoQ information |