| 1 | Sub Head - I (Worker/Staff Establishment) Providing services for day to day maintenance, upkeep & operation of Internal Electrical Installaion, Compound Lights /Flood Lights & water supply Pump, (Inventory & staff details as per annexure-A) at DSEU Campus Narela on all working days excluding sunday or as per directions of Engineer-in-charge, terms and conditions etc. as reqd.Wireman cum Operator-1 NoKhallasi-1 No. |
| 2 | Sub Head - II (Internal &Exteral Electrical Installation )Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 4 | 3 x 4 sq. mm |
| 5 | 3 x 6 sq. mm |
| 6 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 7 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 8 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 9 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 10 | Supply of one number XLPE insulated and PVC sheathed aluminium conductor, armoured underground power cable of 1.1 KV grade of following size and in following manner on wall / surface as required.4 x16 sq.mm |
| 11 | 3x 25 sq.mm |
| 12 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm |
| 13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE insulated power cable of 1.1 kV grade of following size on wall surface, including necessary clamps, wooden/metal saddles, nails, bolts, nuts, etc. as required and making good the surface if damage, complete with connections, testing and commissioning as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 14 | SH-III (Drinking water pump Rewinding and Reapir)Repairing of all type of damage pumps (of water supply/sewage etc. pump sets) i/c dismantling from site, shifting to workshop, turning & polishing of shaft, replacement of GM bearing bush, ball bearing, O ring, thrust bush, thrust plate etc. all items/parts i/c buy back of dismantle material to contractor (dismantle material shall retained with agency) i/c trasfer from workshop to site of work including reassembled, isnatllation, testing and commissioning etc complete as required at site.3 HP pump motor sets (all types) |
| 15 | Dismantling of exisitng motor pump sets, transfer to workshop from site, rewinding of motor with super enameled copper wire including inspection of motor suspension arrangement and tightness of nuts and bolts, cotter pin, rubber reel and replacement of the same wherever found defective during inspection for safe running of motor i/c cleaning the motor with detergent i/c less for old dismantle complete etc as required icluding reassemble, transfer to site of work including installation, testing and commissioning etc. complete as required at site.3 HP pump motor sets (all types) |
| 16 | Lifting of existing submersible bore well / open well 3 HP to 10 HP capacity Pump set from the bore well with chain pulley block & tripod stand i/c cartage charge at site from the work shop. |
| 17 | Lowering of 3 HP to 10 HP capacity bore well/open well pumpset in the bore well with chain pulley block and tripod stand i/c cartage charge pump set from work shop to site credit of old dismantle etc, as reqd. |
| 18 | Supplying, Lowering of G.I Pipe 50mm dia medium class having length of 3 mtr. Each length having threading on both ends i/c 2 nos flanges welded at each ends, gasket, nut, bolts etc complete as reqd. |
| 19 | Supplying & fixing of 3 core 4 sq.mm flat water proof copper conductor submersible cable i/c water proof joint, connection for submersible pumpset etc. complete as reqd. |
| 20 | Fabrication ,Supplying,installation, testing & commissioning of factory assembled outdoor feedar pilar dust and vermin proof powder coated self suported suitable for Single Phase 2 wire, 230 volt AC supply and having front area not less than 0.9 sq mtr and 300 mm deep nominal size fabricated out of 2 mm thick CRCA sheet with locking arrangement i/c supplying & fixing following accessories as below i/c copper wire of suitable size with inter connection,arrangement for cable entery/ support/termination 2 Nos. earthing stud inter connection with 25 mmX 5 mm GI strip(externally) having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated painting 40 mm X40 mmX5 mm MS angle iron base frame etc. complete as required. required.63 Amp DP MCB 10 kA =01 No ( Incomer)40 Amp DP MCB 10 kA =02 Nos ( Outgoing)Pump Controller suitable for 3HP single phase Motors( Relay range-13-22 A) -2 Nos 1 Module Red Indicating Lights(1 Set)Three phase LED Ammeter (class 1) with selector switch and CT having ration 50/5 A (1 Set)Three phase LED Voltmeter (class 1) with selector Switch (1 Set)etc. complete as required. |
| 21 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 22 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 23 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 24 | Sub Head - IV - AC comprenhsive maintenanceComprehensive maintenance & Servicing of following capacity Window/Split AC and water cooler installed at the above mentioned site i/c replacement, defective i.e. blower motor, Gas Charging, PCB, remote, Plug Top, Starting Capacitor, Running Capacitor, Starting Relay,Thermostat, Propeller Fan, Over load Relay i/c condenser unit, evaporative unit charging of refrigerant gas in case of leakage i/c refrigerant gas pipe with insulation, lead wire, etc complete as per terms and conditions attached:-a) Window type AC/ Split type AC of 1.8TR capacity. (30 Nos. for 8 Months- 240 Jobs (Anual maintenance shall be considere after 1st 'B' Check servicing as mentioned in item no 22.) |
| 25 | Supplying & Charging of R 22/410A refrigerent gas for top-up of gas in the existing Split AC i/c leakage testing i/c rectification of leackage complete etc complete as required ( AMC of AC will be started after ) |
| 26 | SH-V (Supply of materials)Note:- No labour is considered for fixing of these itemsS.P. 5/6 A, one way modular switch, ISI marked |
| 27 | S.P. 15/16 A, one way modular switch, ISI marked |
| 28 | 3 pin 5/6 A modular socket outlet, ISI marked |
| 29 | 6 pin 15/16 A modular socket outlet, ISI marked |
| 30 | Stepped type Modular Fan regulator (2 module) |
| 31 | Modular base & cover plate for 8 module |
| 32 | 6 A, to 32 A, ratings, SP MCB, \\"C\\" curve, 10 KA breaking capacity |
| 33 | 12-15 Watt LED recessed/surface down lighter (Round/Square /Rectangular) SMD Type (System lumen efficacy ≥ 105 < 120 lm/Watt ), Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector complete etc as reqd. |
| 34 | 36 Watt LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) of CRCA Sheet Body (Thickness > 0.50 mm) body materials. |
| 35 | 36Watt LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) of CRCA Sheet Body (Thickness > 0.50 mm) body materials. |
| 36 | 1200 mm ceiling fan, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) ceiling fan with Brush Less Direct Current (BLDC) Motor, etc. complete as req |
| 37 | 3 pole MCCB, 100A, 16kA Ics=100% Icu and Operational Voltage 690V |
| 38 | 4 pole MCCB, 200A, 36 kA Ics=100% Icu and Operational Voltage 690V |
| 39 | 40 Amp DP MCB 10 kA rating \\"C\\" Curve |
| 40 | 63 Amp 4P MCB 10 kA rating \\"C\\" Curve |
| 41 | 100 Amp 4P MCB 10 kA rating \\"C\\" Curve |
| 42 | 300 mm sweep 900 RPM, exhaust fan Please Enable Macros to View BoQ information |