| 1 | Excavation in trenches, n.exc 1.5 m wide and n.exc 1.5 m depth and getting out in any type of strata for locating fault, laying of cable and pipe or taking out old u/s cable complete including taking out & stacking of old bricks/pipes, etc and making good to the disturbed surface complete all as specified and directed. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming excavated any type soil in layers not exceeding 25 cm thick each , filling back in trenches after cables have been laid and tested, poles,stays,struts have been erected and tested complete all as specified and directed. |
| 3 | Removal of excavated surplus soil any type to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 4 | Material and labour for Boring/drilling holes underneath road / PCC manually including insertion HDPE pipe of 100mm dia of pressure 0.4 Mpa complete all as specified and directed. |
| 5 | Material and labour for Cable route indicator showing \\" MES HT 11 KV UG Cable\\" and route of cable with arrow made of CI in suitable eliptical shape and fixed on angle iron 40x40x6mm, 800mm long painted in Brown Colour with two coats of synthetic enamel paint cover a coat of red oxide primer duly embaded in PCC block 0.40x0.40x0.40 in ground complete all as specified and directed. |
| 6 | Material and labour for clean river sand laid in trenches/ducts for bedding and cushioning to cable, including spreading and levelling complete all as specified and directed. |
| 7 | Material and labour for laying in trenches precast cement concrete cable cover, class HV type 2 with peak, size 300mm x 180mm x 40mm for cable protection complete all as specified and directed. |
| 8 | Material and labour for HDPE Pipe 100mm bore for cable protection in floor/road crossing/along pole complete all as specified and directed. |
| 9 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm complete all as specified and directed. |
| 10 | Supply, comissioning, testing and installation of 12 KV, 630 Amp Short time current 21 KA/3 Sec, outdoor, motar operated, IAC AFLR Type tested 21 KA/1 Sec, extensible 4 way RMU (1 Incomer VCB and 3 outgoing VCB), Configuration (+VVVV+M) , SF6 fully type tested according to IEC-62271 standards insulated with epoxy resin, microprocessor based over current and earth fault self powered relay (Make : ASHIDA/C&S/MISCOM), 11 KV CT of CT ratio 100/1- 03 Nos in each breaker for metering and protection with a accuracy 0.1. and PT ratio 11KV/√3/110√3 class 0.2 - 04 Nos with mechanical and electrical interlocking arrangements, metering instruments digital type ( volt meter, Ammeter 0-100 Amps) including dismantling from the existing location and shifting to MES Store yard by hydra complete all as specified and directed. |
| 11 | Supply, comissioning, testing and installation of 12 KV, 630 Amp, Short time current 21 KA/3 Sec, IAC AFLR Type tested 21 KA/1 Sec, outdoor, motar operated, extensible 5 way RMU (2 Incomer VCB and 3 outgoing VCB),Configuration (+VVVVV+M),SF6 insulated breaker, fully type tested according to IEC-62271 standards insulated with epoxy resin, microprocessor based over current and earth fault self powered relay (Make : ASHIDA/C&S/MISCOM), 11 KV CT of CT ratio 100/1- 03 Nos in each breaker for metering and protection with a accuracy 0.1. and PT ratio 11KV/√3/110√3 class 0.2 - 03 Nos with mechanicaland electrical interlocking arrangements, metering instruments digital type ( volt meter, Ammeter 0-100 Amps) including dismantling from the existing location and shifting to MES Store yard by hydra complete all as specified and directed. |
| 12 | Supply, comissioning, testing and installation of 11KV, 630 Amp ,Short time current 21 KA/3 Sec,IAC AFLR Type tested 21 KA/1 Sec, outdoor, motar operated , extensible 5 way RMU (1 Incomer VCB and 4 outgoing VCB),Configuration (+VVVVV+M),SF6 insulated breaker, fully type tested according to IEC-62271 standards insulated with epoxy resin, microprocessor based over current and earth fault self powered relay (Make : ASHIDA/C&S/MISCOM), 11 KV CT of CT ratio 100/1- 03 Nos in each breaker for metering and protection with a accuracy 0.1. and PT ratio 11KV/√3/110√3 class 0.2 - 03 Nos with mechanical and electrical interlocking arrangements, metering instruments digital type (volt meter, Ammeter 0-100 Amps) including dismantling from the existing location and shifting to MES Store yard by hydra complete all as specified and directed. |
| 13 | Supply, comissioning, testing and installation of 11KV, 1250 Amp ,Short time current 26.3 KA/3 Sec,IAC AFLR Type tested 21 KA/1 Sec, Indoor, motar operated , extensible 4 way HT Panel (1 Incomer VCB and 3 outgoing VCB), Air insulated breaker,fully type tested according to IEC-62271 standards insulated with epoxy resin, microprocessor based over current and earth fault self powered relay (Make : ASHIDA/ C&S/ MISCOM), 11 KV CT of CT ratio 100/1- 03 Nos in each breaker for metering and protection with a accuracy 0.1. and PT ratio 11KV/√3/110√3 class 0.2 - 03 Nos with mechanical and electrical interlocking arrangements, metering instruments digital type (volt meter, Ammeter 0-100 Amps) including PCC Foundation, earth work complete , dismantling from the existing location and shifting to MES Store yard by hydra complete all as specified and directed. |
| 14 | Supply, comissioning, testing and installation of 11KV, 1250 Amp ,Short time current 26.3 KA/3 Sec,IAC AFLR Type tested 21 KA/1 Sec, Indoor, motar operated , extensible 3 way HT Panel (2 Incomer VCB and 1 outgoing VCB), Air insulated breaker, fully type tested according to IEC-62271 standards insulated with epoxy resin, microprocessor based over current and earth fault self powered relay (Make : ASHIDA/ C&S/ MISCOM), 11 KV CT of CT ratio 100/1- 03 Nos in each breaker for metering and protection with a accuracy 0.1 and PT ratio 11KV/√3/110√3 class 0.2 - 03 Nos with mechanical and electrical interlocking arrangements, metering instruments digital type (volt meter, Ammeter 0-100 Amps) including PCC Foundation,earth work complete , dismantling from the existing location and shifting to MES Store yard by hydra complete all as specified and directed. |
| 15 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 Sqmm complete all as specified and directed. |
| 16 | Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm, Indoor/Outdoor type complete all as specified and directed. |
| 17 | Material and labour for Earthing complete with GI earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m below normal ground level, earth pit surrounded by 15 cm thick and packed layers of charcoal dust (100 kg) and common salt (100 kg), vegetable soil (300 kg) including GI strip 32 x 6 as earth lead fixed by means of nuts, bolts, check nuts and washers etc and other end connected to the test point including 40 mm dia light grade GI protection pipe upto 7.5 metre and watering pipe 20 mm dia light grade with funnel and wire mesh including necessary earth work i.e exacavation and removing upto 500 metre distance with dismantling old earthing, complete all as specified and directed. Note : The earth value/result must be less than 5 ohms. |
| 18 | Supply and fix RCC Precast (Factory Manufactured) Earthing pit of size 450 mm x 450 mm x 450 mm x 50 mm thickness with Mortar design precast Pit cover with 50 mm thick PCC at bottom including taking down old pit with cover, earth work complete all as specified and directed. |
| 19 | Material and labour for 100 mm thick PCC 1:4:8 type D- 2 (40mm graded aggregate) as in bases, sub bases of floors complete all as specified and directed. |
| 20 | Material and labour for PCC 1:2:4 type B0 (12.5 mm graded aggregate) as in Side Honching ,bases, sub bases of floors complete all as specified and directed. |
| 21 | Material and labour for rubberised machine pressed pre polished precast concrete interlocking paver block any shape, size, desired colour and pattern conforming to IS 15658-2006 of 60 mm thickness M-35 grade with grey cement and pigment , complete all as specified and directed. |
| 22 | Material and labour 50 mm sand cushioning for interlocking tiles including well rammed and consolidation complete all as specified and directed. |
| 23 | Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in any type of soil complete all as specified and directed. |
| 24 | Removing excavated material to a distance n.exc 50 m & depositing where directed at a level n.exc 1.50 m above the starting point complete all as specified and directed. |
| 25 | Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified and directed. |
| 26 | Design, fabrication, assembly, testing, supply, installation and commissioning of hybrid APFC PANEL with Active Harmonic Filter - Indoor - 200KVAr APFC + 100A AHF 3P/4W Hybrid APFC Panel. Power Quality conditioner panel with smart integrated hybrid controller and active filters with 3 level topology. The hybrid PQ filter panel shall be fabricated out of 1.6 for side doors and 2mm for structure and front door CRCA sheet steel in cubicle compartment, free-standing, floor mounted, dust and vermin proof with reinforcement of suitable size, angle iron, channel, ‘T’ sections and/or flats wherever necessary. Pre-treatment of the panel shall be carried out before epoxy powder coating of minimum 120 um thickness with nine tank process shall be ensured. The panels shall be designed to IP 42 protection standard as per IEC 60529. The color of powder coating shall be standard RAL 7035.The locks should be push type 3 pin locks with key. Two numbers of earthing terminals shall be provided on either side of the panel. Cable gland plates with minimum 3mm thickness shall be provided on bottom (or as per client’s requirements) of the panel for top / bottom entry. The panel shall be OEM Panel suitable for 415V +/- 10%, 3 phase, 4 wire 50Hz +/- 5% supply system. It shall seamlessly integrate active power filters and passive sections to have a integrated single control and deliver highest performance. Hybrid PQ Solution should comprise of Active:Passive is 1:1, i.e Active filter 100 Amps and Passive i.e. (200kVAr) Step ratings as per OEM recommendations to obtain desired P.F. |
| 27 | Main Incomer500A TP MCCB microprocessor based over-current and short-circuit protection and 50kA breaking capacity (Ics) as the incomer of the panel 100% Icu breakers shall be used. The main incomer shall provide supply to all the passive banks and also to the active filter modules. Control MCB of rating 10A-FP-10kA-C Curve to provide power supply to the control circuit of the active filter which shall be accessible on opening the front door of the active filter to switch off the control section when necessary. IGBT based Active technology; 3-Level Topology with Efficiency >98% . R,Y,B Indication LED lights and Three phase digital multi function meter should be provided at the main incomer for displaying the three phase current and voltages.Physical On/Off IP66 selector switch shall be provided on the front of the active filter. 7inch color touch-screen HMI (human machine interface) with Data on Modbus RTU for integration with SCADA/BMS system. The LCD should display all parameters like Currents, Fundamental Current, iTHD, iTDD, Aunb, Voltages, vTHD, kW, kVAr, kVA, PF, dPF, Filter Current, Filter Loading (%), Stack Temperature, Ambient Temperature etc including required hardwares, softwares, protections, cards, inscription plates, Danger notice board, suitable PC foundation etc., as required to be provided to complete the installation complete with all connected items for istalling the panel complete all as specified and directed. |
| 28 | Design, fabrication, assembly, testing, supply, installation and commissioning of hybrid APFC PANEL with Active Harmonic Filter - Indoor - 250 KVAr APFC + 150A AHF 3P/4W Hybrid PFC Panel. Power Quality conditioner panel with smart integrated hybrid controller and active filters with 3 level topology. The hybrid PQ filter panel shall be fabricated out of 1.6 for side doors and 2mm for structure and front door CRCA sheet steel in cubicle compartment, free-standing, floor mounted, dust and vermin proof with reinforcement of suitable size, angle iron, channel, ‘T’ sections and/or flats wherever necessary. Pre-treatment of the panel shall be carried out before epoxy powder coating of minimum 120 um thickness with nine tank process shall be ensured. The panels shall be designed to IP 42 protection standard as per IEC 60529. The color of powder coating shall be standard RAL 7035.The locks should be push type 3 pin locks with key. Two numbers of earthing terminals shall be provided on either side of the panel. Cable gland plates with minimum 3mm thickness shall be provided on bottom (or as per client’s requirements) of the panel for top / bottom entry. The panel shall be OEM Panel suitable for 415V +/- 10%, 3 phase, 4 wire 50Hz +/- 5% supply system. It shall seamlessly integrate active power filters and passive sections to have a integrated single control and deliver highest performance. Hybrid PQ Solution should comprise of Active:Passive is 1:1, i.e Active filter 150 Amps and Passive i.e. (250kVAr). Step ratings as per OEM recommendations to obtain desired P.F. |
| 29 | Main Incomer630A TP MCCB microprocessor based over-current and short-circuit protection and 50kA breaking capacity (Ics) as the incomer of the panel 100% Icu breakers shall be used. The main incomer shall provide supply to all the passive banks and also to the active filter modules. Control MCB of rating 10A-FP-10kA-C Curve to provide power supply to the control circuit of the active filter which shall be accessible on opening the front door of the active filter to switch off the control section when necessary. IGBT based Active technology; 3-Level Topology with Efficiency >98% . R,Y,B Indication LED lights and Three phase digital multi function meter should be provided at the main incomer for displaying the three phase current and voltages.Physical On/Off IP66 selector switch shall be provided on the front of the active filter. 7inch color touch-screen HMI (human machine interface) with Data on Modbus RTU for integration with SCADA/BMS system. The LCD should display all parameters like Currents, Fundamental Current, iTHD, iTDD, Aunb, Voltages, vTHD, kW, kVAr, kVA, PF, dPF, Filter Current, Filter Loading (%), Stack Temperature, Ambient Temperature etc including required hardwares, softwares, protections, cards, inscription plates, Danger notice board, suitable PC foundation etc., as required to be provided to complete the installation complete with all connected items for istalling the panel complete all as specified and directed. |
| 30 | Supply Erection, Testing and Commissioning in replacement of Automatic Power Factor Correction OEM built Capacitor Panel suitable for Indoor Application, 11 tank process for corrosion proof powder coating, Manufactured with highly precise modern Amada CNC machine, 150 kVAr rating, 440 volts, 03 phase AC, main incoming MCCB 320 Amps,35 KA. APFC Panel shall be designed and manufactured by OEM only, Advance C-MOS technology based micro processor relay for intelligent power factor control, Air core reactor for extra safety from inrush current (high currents), provision of top and bottom cable entry,Automatic temp. control through fans and louvers in panel,Double side earthing connection,all Components Make like MCCB, MPP Capacitors, Capacitor super heavy Duty Contactor, Reactors, APFC Relay, Wire, shall be of Same OEM including encapsulated Copper busbar, Pan Assembly shall be used for better heat dissipation and proper cooling, Outgoing MCB/MCCB must be directly mounted on the Pan Assembly to avoid any loose connection and short circuit, Capacitors shall be Super Heavy Duty type with high Overcurrent withstand capacity Capacitor Bank Size in 8 steps of (2x50 kVAr + 1x25 kVAr + 1x10 kVAr + 2x5 kVAr+ 1x3 kVAr+1x2 kVAr) for real time compensation which makes systems Reliable and Sustainable complete all as specified and directed. |
| 31 | Supply Erection, Testing and Commissioning in replacement of Automatic Power Factor Correction OEM built Capacitor Panel suitable for Indoor Application, 11 tank process for corrosion proof powder coating,Manufactured with highly precise modern Amada CNC machine, 100 kVAr rating, 440 volts, 03 phase AC,main incoming MCCB 160 Amps, 25 KA.APFC Panel shall be designed and manufactured by OEM only,Advance C-MOS technology based micro processor relay for intelligent power factor control,Air core reactor for extra safety from inrush current (high currents), provision of top and bottom cable entry,Automatic temp. control through fans and louvers in panel,Double side earthing connection,all Components Make like MCCB, MPP Capacitors, Capacitor super heavy Duty Contactor, Reactors, APFC Relay, Wire, shall be of Same OEM including encapsulated Copper busbar, Pan Assembly shall be used for better heat dissipation and proper cooling, Outgoing MCB/MCCB must be directly mounted on the Pan Assembly to avoid any loose connection and short circuit, Capacitors shall be Super Heavy Duty type with high Overcurrent withstand capacity Capacitor Bank Size in 8 steps of (4x20 kVAr + 1x10 kVAr + 1x5 kVAr+ 1x3 kVAr+1x2 kVAr) for real time compensation which makes systems Reliable and Sustainable complete all as specified and directed. |
| 32 | Supply Erection, Testing and Commissioning in replacement of Automatic Power Factor Correction OEM built Capacitor Panel suitable for Indoor Application, 11 tank process for corrosion proof powder coating,Manufactured with highly precise modern Amada CNC machine, 200 kVAr rating, 440 volts, 03 phase AC,main incoming MCCB 400 Amps,35 KA.APFC Panel shall be designed and manufactured by OEM only,Advance C-MOS technology based micro processor relay for intelligent power factor control,Air core reactor for extra safety from inrush current (high currents), provision of top and bottom cable entry,Automatic temp. control through fans and louvers in panel,Double side earthing connection,all Components Make like MCCB, MPP Capacitors, Capacitor super heavy Duty Contactor, Reactors, APFC Relay, Wire, shall be of Same OEM including encapsulated Copper busbar, Pan Assembly shall be used for better heat dissipation and proper cooling, Outgoing MCB/MCCB must be directly mounted on the Pan Assembly to avoid any loose connection and short circuit, Capacitors shall be Super Heavy Duty type with high Overcurrent withstand capacity Capacitor Bank Size in 8 steps of (3x50 kVAr + 1x25 kVAr + 1x10 kVAr + 3x5 kVAr) for real time compensation which makes systems Reliable and Sustainable complete all as specified and directed. |
| 33 | Supply Erection, Testing and Commissioning in replacement of Automatic Power Factor Correction OEM built Capacitor Panel suitable for Indoor Application, 11 tank process for corrosion proof powder coating,Manufactured with highly precise modern Amada CNC machine, 125 kVAr rating, 440 volts, 03 phase AC,main incoming MCCB 250 Amps, 25 KA.APFC Panel shall be designed and manufactured by OEM only,Advance C-MOS technology based micro processor relay for intelligent power factor control,Air core reactor for extra safety from inrush current (high currents), provision of top and bottom cable entry,Automatic temp. control through fans and louvers in panel,Double side earthing connection,all Components Make like MCCB, MPP Capacitors, Capacitor super heavy Duty Contactor, Reactors, APFC Relay, Wire, shall be of Same OEM including encapsulated Copper busbar, Pan Assembly shall be used for better heat dissipation and proper cooling, Outgoing MCB/MCCB must be directly mounted on the Pan Assembly to avoid any loose connection and short circuit, Capacitors shall be Super Heavy Duty type with high Overcurrent withstand capacity Capacitor Bank Size in 8 steps of (1x50 kVAr + 2x25 kVAr + 1x10 kVAr + 2x5 kVAr+ 1x3 kVAr+1x2 kVAr) for real time compensation which makes systems Reliable and Sustainable complete all as specified and directed. |
| 34 | Supply Erection, Testing and Commissioning in replacement of Automatic Power Factor Correction OEM built Capacitor Panel suitable for Indoor Application, 11 tank process for corrosion proof powder coating,Manufactured with highly precise modern Amada CNC machine, 275 kVAr rating, 440 volts, 03 phase AC,main incoming MCCB 500 Amps, 50 KA. APFC Panel shall be designed and manufactured by OEM only,Advance C-MOS technology based micro processor relay for intelligent power factor control,Air core reactor for extra safety from inrush current (high currents), provision of top and bottom cable entry,Automatic temp. control through fans and louvers in panel,Double side earthing connection,all Components Make like MCCB, MPP Capacitors, Capacitor super heavy Duty Contactor, Reactors, APFC Relay, Wire, shall be of Same OEM including encapsulated Copper busbar, Pan Assembly shall be used for better heat dissipation and proper cooling, Outgoing MCB/MCCB must be directly mounted on the Pan Assembly to avoid any loose connection and short circuit, Capacitors shall be Super Heavy Duty type with high Overcurrent withstand capacity Capacitor Bank Size in 8 steps of (1x100 kVAr + 2X50 kVAr + 2x25 kVAr + 2x10 kVAr+ 1x5 kVAr) for real time compensation which makes systems Reliable and Sustainable complete all as specified and directed. |
| 35 | Supply and laying of UG cable XLPE insulated armoured heavy duty electrical cable with stranded aluminium conductor 1100 volts grade cross section area 400 Sqmm 3.5 core laid in trenches/ fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts etc complete all as specified and directed. |
| 36 | Supply and laying of UG cable XLPE insulated armoured heavy duty electrical cable with stranded aluminium conductor 1100 volts grade cross section area 240 Sqmm 3.5 core laid in trenches/ fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts etc complete all as specified and directed. |
| 37 | Supply and laying of UG cable XLPE insulated armoured heavy duty electrical cable with stranded aluminium conductor 1100 volts grade cross section area 150 Sqmm 3.5 core laid in trenches/ fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts etc complete all as specified and directed. |
| 38 | Supply and laying of UG cable XLPE insulated armoured heavy duty electrical cable with stranded aluminium conductor 1100 volts grade cross section area 70 Sqmm 3.5 core laid in trenches/ fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts etc complete all as specified and directed. Please Enable Macros to View BoQ information |