| 1 | Supply and fixing in replacemment of surface mounted LED decorative type angle adjustable sport light / bed side study lamp light fitting with lamp in matt finish for premium aesthetics with based of suitable rating capacity 7Watt LED complete light fitting set all as per existing fitting type/ size of sample /model and make and required fitting use in both warm/white type colour complete light fitting and including providing of suitable type of flate fexible two/three core cable and making electric connection and including taking down of old existing fitting, complete all as specified and directed. |
| 2 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground, (Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to and including galvanised iron earth wire 4 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I(2010) including taking down old u/s earthing, complete all as specified and directed . |
| 3 | Note:- (a) Excavation and earth work for drilling hole for electrode in any type of Soil.(b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter.(c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed(d) 20 mm nominal bore medium grade GI protection pipe 7 meter long for protection of earthing lead complete all as specified and directed.(e) Requisite quantity of common salt and charcoal. |
| 4 | M&L for electrical high insulation tape roll of 25mm wide and 25 Mtr length (RYB) for repair/maintenance of cables joining in pannels (1100 Volts)/ conductors or fixing of thimbles or colour coding of cables in panels/joints and installation of securituy lights in poles etc., complete all as specified and directed. |
| 5 | S&F in replacement of rechargeable LED bulb of rated capacity 7 to 9 watt of shape pin or threaded type required in colour white / warm type, complete all as specified and directed. |
| 6 | Repair of existing earthing pit by using PCC work and making it serviceable condition including suitable size of pit cover made of plain cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregate, complete all as specified and directed |
| 7 | M&L in repair for earth continuity conductor or main earthing lead fixed to wall on batten or burried in ground or drawn in conduit /GI pipe 15mm bore as required 4 mm dia galvanised iron, complete all as specified and directed |
| 8 | Dismantling unserviceable main switch/DBs with MCBs including making good disturbed surface, complete all as specified and directed |
| 9 | Taking down submain wiring of any size capacity complete all as specified and making good disturbed surface to match with the existing surface, complete all as specified and directed |
| 10 | S&F in replacement sub main wiring with two runs PVC insulated FRLS wire, 1100 volt grade with multistranded copper conductor wire single core of size 2 runs of 2.5 Sqmm and 1 run of 2.5 Sqmm (Nominal area) (ISI Marked) any type any length drawn through in heavy duty ISI marked PVC Casing capping / PVC conduit of suitable size along with its all fittings and connected accessories and duly fixed concealed in wall or surface on wall and making good all disturbed surfaces match to the existing surface complete all as specified and directed.Note:- 3 runs of 2.5 sqmm cable and one run of conduit/ casing capping shall be measured and paid as one unit. |
| 11 | S&F in replacement sub main wiring with two runs PVC insulated FRLS wire, 1100 volt grade with multistranded copper conductor wire single core of size 2 runs of 4 Sqmm and 1 run of 4 Sqmm (Nominal area) (ISI Marked) any type any length drawn through in heavy duty ISI marked PVC Casing capping / PVC conduit of suitable size along with its all fittings and connected accessories and duly fixed concealed in wall or surface on wall and making good all disturbed surfaces match to the existing surface complete all as specified and directed.Note:- 3 runs of 4sqmm cable and one run of conduit/ casing capping shall be measured and paid as one unit. |
| 12 | S&F in replacement sub main wiring with two runs PVC insulated FRLS wire, 1100 volt grade with multistranded copper conductor wire single core of size 2 runs of 6 Sqmm and 1 run of 6 Sqmm (Nominal area) (ISI Marked) any type any length drawn through in heavy duty ISI marked PVC Casing capping / PVC conduit of suitable size along with its all fittings and connected accessories and duly fixed concealed in wall or surface on wall and making good all disturbed surfaces match to the existing surface complete all as specified and directed.Note:- 3 runs of 6sqmm cable and one run of conduit/ casing capping shall be measured and paid as one unit. |
| 13 | S&F in replacement of twin core flat/ circular cable of size 4 sqmm 1100 Volts grade, heavy duty cable PVC insulated multistranded aluminium conductor cable served with inner sheathed of PVC tap and overall PVC sheathed and making electric connection, complete all as specified and directed. |
| 14 | S&F in replacement of twin core flat/ circular cable of size 6 sqmm 1100 Volts grade, heavy duty cable PVC insulated multistranded aluminium conductor cable served with inner sheathed of PVC tap and overall PVC sheathed and making electric connection, complete all as specified and directed. |
| 15 | S&F in replacement of twin core flat/ circular cable of size 10 sqmm 1100 Volts grade, heavy duty cable PVC insulated multistranded aluminium conductor cable served with inner sheathed of PVC tap and overall PVC sheathed and making electric connection, complete all as specified and directed. |
| 16 | S&F Sheet metal enclosure factory made for DBs single pole and neutral double door 240 volts 12 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces, complete all as specified and directed. |
| 17 | S&F Sheet metal enclosure factory made for DBs single pole and neutral double door 240 volts 8 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces, complete all as specified and directed. |
| 18 | S&F Sheet metal enclosure factory made for DBs single pole and neutral double door 240 volts 6 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces, complete all as specified and directed. |
| 19 | S&F Sheet metal enclosure factory made for DBs single pole and neutral double door 240 volts 4 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces, complete all as specified and directed. |
| 20 | Supply and fixing of MCB, single pole and neutral, 240 Volts, 40-63 Amps, 10 KA breaking capacity, complete all as specified and as directed. |
| 21 | Supply and fixing of MCB, single pole, 240 Volts, 40 Amps, 10 KA breaking capacity, complete all as specified and as directed. |
| 22 | Supply and fixing of MCB, single pole, 240 Volts, 6-32 Amps, 10 KA breaking capacity, complete all as specified and as directed. |
| 23 | Supply and fixing PVC Casing capping of size 15/20 mm heavy duty with all fitting laid in trenches/ wall including providing clamping arrangment for holding of casing capping on wall in proper size of clamps, nut bolt ,and washer etc., complete all as specified.and directed. |
| 24 | S&F in replacment of MCCB 160 Amps, 36 KA, 4 pole 415V 50Hz, complete all as specified.and directed. |
| 25 | S&F in replacment of MCCB 160 Amps, 36 KA, 3 pole 415V 50Hz, complete all as specified.and directed. |
| 26 | S&F in replacment of MCCB 125 Amps, 16 KA, 4 pole 415V 50Hz, complete all as specified.and directed. |
| 27 | S&F in replacment of MCCB 100 Amps, 16 KA, 4 pole 415V 50Hz, complete all as specified.and directed. |
| 28 | S&F in replacment of MCCB 100 Amps, 16 KA, 3 pole 415V 50Hz, complete all as specified.and directed. |
| 29 | S&F in replacment of MCCB 125 Amps, 16 KA, 3 pole 415V 50Hz, complete all as specified.and directed. |
| 30 | S&F in replacment of Isolator TP 63 Amps, 16 KA, 3 pole 415V 50Hz, complete all as specified.and directed. |
| 31 | S&F in replacment of Isolator TPN 100 Amps, 16 KA, 3 pole 415V 50Hz, complete all as specified.and directed. |
| 32 | Supply and fixing of LED street light fitting of rated capacity 35Watt 230 volt AC with having LED driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optices complete with IP 65/66 protectiuon suitable for out door type made out of high pressure die cast hosing with heat resistant glass complete light fitting set including providing of suitable dia of GI bracket and it to as per match/setting thefitting fixture base hole attechment system and including providing of suitable type of flate fexible two/three core cable and makong electric connection, complete all as specified and directed. |
| 33 | M & L for bracket made out of GI tubing 25/20 mm dia,light grade 1.0 mtr long suitable for fixing 35 watt building security light including fixing with MS clamps 2 Nos of flat iron with M.S. nuts, bolts/screw 4 Nos & flat washer 01 No. for each including preparation of steel surfaces and painting with two coats of paint over one coat of red oxide to the M.S clamps & bracket etc., complete all as specified and as directed. |
| 34 | Supply and fixing of rigid non metalic PVC conduit of size 20/25 mm bore heavy duty with all fitting laid in trenches/wall including providing clamping arrengment for holding of pipe on wall in proper size of clamps,nut bolt, and washer etc., complete all as specified and directed. |
| 35 | Supply and fixing of GI water tubing 15mm bore light grade galvanised with all fittings like socket, union, elbow, bend, etc. jointed and laid in trenches, complete all as specified and directed. |
| 36 | S&F in repair / replacement sub main wiring system with two runs PVC insulated FRLS wire, 1100 volt grade with multistranded copper conductor wire single core of size 2 runs of 1.5 Sqmm and 1 run of 1.5 Sqmm (Nominal area) (ISI Marked) any type any length drawn through in heavy duty ISI marked PVC Casing capping / PVC conduit of suitable size along with its all fittings and connected accessories and duly fixed concealed in wall or surface on wall and making good all disturbed surfaces match to the existing surface complete all as specified and directed.Note: 3 runs of 1.5sqmm cable and one run of conduit/ casing capping shall be measured and paid as one unit. |
| 37 | Supply and fixing in repair SPN enclosure with 2 pole, 240 volts and earth metal plug & socket for incorporating 10 A SPN MCB, complete all as specified and directed. Note:- MCB 10 Amp SPN rate included in this item. |
| 38 | S&F in repair/ replacement LED spot light 9 watt Water proof multi colour for fixing in fountain including providing of suitable type of flat flexible two/three core copper cable and making electric connection, complete all as specified and directed. |
| 39 | Supply and fixing in repair IP65 LED Solar bulk head light of capacity 4 watt with built-in Solar panel, LED Light and Lithium battery with charge controller and PIR sensor. including finishing of disturb surface all as specified and direced. |
| 40 | Supply and fixing in repair IP65 LED Solar pillar light with built-in Solar panel, LED Light and Lithium battery with charge controller. including finishing of disturb surface all as specified and directed. |
| 41 | S&F in replacement of hanging decorative/ fancy lights suitable for including 7/9 Watt Led bulb, complete all as specified and directed. |
| 42 | S&F in replacement of B D fancy type lights warm -White LED Straight shaped picture suitable for lighting in Mirror /Name plate or as per existing type /wattage, complete all as specified and directed. |
| 43 | Supply and fixing in replacement of cuboid 400 mm 3 blade decorative type with inbuilt LED lights remote control fan concealed mounted down sizes 600 mmx 600 mm, 230 Volt ,95 watt plastic finish, complete all as specified and directed |
| 44 | S&F in repair/ replacement surface wall mounted decorative double type of wall bracket light fitting with having stainless steel rust free fixture with white glass diffuser alongwith bulb holder based adaptor suitable used for 7.5W / 9 W LED filament lamp E27 base system including providing of 2 x 9W LED lamp complete light fitting set use in both warm/white type colour complete light fitting set and complete set and including providing of suitable type of flat flexible two/three core cable and making electric connection, complete all as specified and directed. |
| 45 | Supply and fixing in repair New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source 25W, 5700K for fixing at gates with PCC work and GI pipe of suitable size including finishing of disturb surface, complete all as specified and directed. |
| 46 | Notes :-An amount of Rs 67954.00 on account of Credit Schedule for Schedule 'A' Part-II shall be deducted from total quoted amount of BOQ to arrive at the contract sum. Please Enable Macros to View BoQ information |