| 1 | (A) Design,Manufacture,Supply,Packing & Forwarding,Transportation,Delivery At Site of Equipments and Material |
| 2 | Main Equipments |
| 3 | 105 MVA (ONAN/ONAF/OFAF), 220/132/11 KV Single phase Auto Transformer with OLTC, SCADA Compatible RTCC, WITHOUT NIFPES, HV and LV connectors and other required accessories and fittings with online DGA monitoring (7 gases),, online dehydration kit and maintenance free automatic Breathers as per detailed Technical specs, Inbuilt NCTsand other accessories , control cables and fitting With Mandatory Spares ( Current density for HV/LV/ Teritiary winding not more than 2.4 A/sq mm.Core Flux density not more than 1.5T) .The scope shall include ist filling of transformer oil and 10 percent extra. Mandatory spares for one autotransformer (as spare for autotransformer bank plus spare autotransformer) which shall include HV RIP bushing , OIP IV bushing ,1 No neutral and tertiary bushing,1 No OTI and WTI with contacts & sensing device , 1 Oil cooler pump with motor ,2 Cooler fans with motor , 1 No PRV and bucholz relay , bushing CT's, oil surge relay ,MOG, air cell for conservator, 2 No oil sampling bottle . |
| 4 | NIFPS for 1 Number 105MVA, 220/132kV Single Phase Spare Transformer with storage tank 10 KL capacity |
| 5 | 220KV Control and Relay Panel for Transformer Bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay. |
| 6 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing |
| 7 | IPS Tube 4' Al tube, OD 120 mm , ID 100 mm , wall thickness 10 mm, weight 9.33 kg/m |
| 8 | IPS Tube 3' Al tube, OD 90 mm , ID 78 mm , wall thickness 6 mm, weight 5.5 kg/m |
| 9 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (245KV, 3150 Amps of 3 phase, 50 c/s and 50 KA for 1 second) along with supporting structures etc. complete in all Respects. SS BODY,UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES per breaker like 1 no closing and 2 No tripping coils ,Relays, Power contactors, Push buttons, limit switches, timers, MCBs and switch fuse units, closing coil assembly and trip coil assembly |
| 10 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 3150Amps or higher, of 3 phase, 50 c/s and 40 KA for 1 second) along with supporting structures etc. complete in all Respects SS BODY,UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES per breaker like 1 no closing and 2 No tripping coils ,Relays, Power contactors, Push buttons, limit switches, timers, MCBs and switch fuse units, closing coil assembly and trip coil assembly |
| 11 | Single phase, 50 c/s 245KV Current Transformers (1800-9001-1-1-1-1 -1A or as per site specifications), 50KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class,1 NO 0.1s class, Galvanised tank including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc. |
| 12 | 33 KV rated Heat sink insulation sleeve for tertiary |
| 13 | Single phase, 50 c/s 145KV Current Transformers (1800-1500/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.1s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc. |
| 14 | Single phase, 50 c/s 145KV Current Transformers (1800-1600/1-1-1-1-1 A or as per site specifications),40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.1s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc. |
| 15 | 245kV, 50c/s , 2500 A, SCADA Compatible. 50kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing switches COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 16 | 245kV, 50c/s ,2500 A, SCADA Compatible, 50kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with one Earthing switches COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 17 | 245kV, 50c/s ,2500 A, SCADA Compatible, 50kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing switches COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 18 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type Single pole Isolators without Earthing BladesCOPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 19 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type Single pole Isolators with One Earthing BladesCOPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 20 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 KA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 21 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 22 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 kA for one second, AC motor operated horizontal double break, outdoor type 3 pole isolator with two Earth switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS , GALVANISED IRON MECHANISM BOX. |
| 23 | 36kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type two pole Isolators without Earthing Blades COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 24 | Single Phase 50 c/s, outdoor metal oxide gapless type, 200KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries. |
| 25 | Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries. |
| 26 | 220 KV Post Insulator Solid core/Polymer Type,Power frequency withstand voltage 460 KV RMS Dry lightning impulse withstand voltage 650 (KVP) |
| 27 | 132 KV Post Insulator Solid core/Polymer Type,Power frequency withstand voltage 275KV RMS Dry lightning impulse withstand voltage 1050 (KVP) |
| 28 | Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing |
| 29 | 33 KV Post Insulators Solid Core type power frequency withstand voltage 95 KV RMS Dry lightning impulse withstand voltage 170(KVP) |
| 30 | CONDUCTOR & HARDWARE FITTINGS |
| 31 | 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 32 | Disc insulator 70 KN , Ball and socket type , 145 mm height and 255 mm dia. Creepage total 430 mm and 260 mm protected |
| 33 | Disc insulator120 KN , Ball and socket type , 145 mm height and 280 mm dia. Creepage total 430 mm and 260 mm protected |
| 34 | Double Tension Fittings For Twin 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 35 | Double Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. |
| 36 | Connector suitable for 4\\" IPS tube to single moose conductor |
| 37 | Connector suitable for 3\\" IPS tube to single moose conductor |
| 38 | Double Tension Fittings suitable For Quad 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. |
| 39 | Double Suspension Fittings suitable For Quad 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. |
| 40 | Flexible connector suitable for interconnection of 4\\" Al tube with 4\\" Al tube |
| 41 | T Clamps Twin 500mm2 /Twin 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 42 | T clamps 500mm2/500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 43 | T clamps Twin 500mm2/ single 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 44 | Rigid Terminal connector for 33 KV BPI suitable for 3\\" Al tube |
| 45 | Rigid Terminal connector for BPI suitable for 4\\" Al tube |
| 46 | T Clamps Quad 500mm2 /Single 500 mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 47 | T connector suitable for 4\\" tube with twin moose conductor |
| 48 | P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 49 | Bimettalic Pad clamp twin 500mm2 , and shall comply in all respects with IS: 55561-1970 (latest edition) |
| 50 | Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162(rate given is 1.6xrate of(spacer for twin conductor),or it can vary) |
| 51 | Spacers For Quad 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162(rate given is 1.6xrate of(spacer for twin conductor),or it can vary) |
| 52 | Power and Control cables including termination of the cables |
| 53 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 54 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 55 | 10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 56 | 2 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 57 | 5 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 58 | 12 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 59 | 16 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 60 | 2 core, 6sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 61 | 4 core, 6sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 62 | 4 core, 16sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 63 | STRUCTURES |
| 64 | Fabrication, Galvanisation, supply including packing and forwarding, transportation charges of 220KV, 132KV structutres |
| 65 | Galvanised Nuts and Bolts |
| 66 | Pipe Type structure |
| 67 | (B) HANDLING, STORAGE, PRESERVATION, ERECTION (EXCEPT CIVIL WORKS), DEHYDRATION, TESTING & COMMISSIONING OF EQUIPMENTs AND MATERIAL |
| 68 | Main Equipments |
| 69 | 315 MVA Bank comprising of 4 no, single phase, 105 MVA Auto Transformer units (in place of existing 150MVA, 220/132KV Transformer Bank) as per the specification mentioned in the GTR and STR along with GI pipes and treated earthing of transformer |
| 70 | NIFPS for 1 Number 105MVA, 220/132kV Single Phase Spare Transformer |
| 71 | 220KV Control and Relay Panel for Transformer Bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay. |
| 72 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing |
| 73 | IPS Tube 4' Al tube, OD 120 mm , ID 100 mm , wall thickness 10 mm, weight 9.33 kg/m |
| 74 | IPS Tube 3' Al tube, OD 90 mm , ID 78 mm , wall thickness 6 mm, weight 5.5 kg/m |
| 75 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (245KV, 3150 Amps of 3 phase, 50 c/s and 40KA for 1 second) along with modification of existing foundations. |
| 76 | 3 pole SF6 gas filled, outdoor circuit breaker, including all accessories, auxillaries and marshalling boxes/kiosks 145KV,3150 Amp of 3 Phase 50c/s and 31.5KA for 1 sec along with modifications of existing fondations |
| 77 | Single phase, 50 c/s 245KV Current Transformers (1800-900/1-1-1-1-1-1 A or as per site specifications), 50KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s,1 No 0.1s class, Galvanised tank including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc along with modifications of existig foundations |
| 78 | Single phase, 50 c/s 145KV Current Transformers (1800-1500/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s,1 No 0.1s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc along with modifications of exiting foundations |
| 79 | Single phase, 50 c/s 145KV Current Transformers (1800-1600/1-1-1-1-1 A or as per site specifications),40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc along with modification of exiting foundations |
| 80 | 33 KV rated Heat sink insulation sleeve for tertiary |
| 81 | Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing |
| 82 | 36kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type two pole Isolators without Earthing Blades COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX along with mofification of existing foundations |
| 83 | 245kV, 50c/s , 2500 Amp, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades along with modification of existing foundations |
| 84 | 245kV, 50c/s , 2500 Amp, 40 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Blades along with modification of existing foundations |
| 85 | 245kV, 50c/s , 2500 Amp, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades. |
| 86 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades. |
| 87 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with one Earthing Blades along with modification of existing foundations |
| 88 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type Single pole Isolators without Earthing BladesCOPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. along with modification of existing foundations |
| 89 | 145kV, 50c/s , 2500 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type Single pole Isolators with One Earthing BladesCOPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX along with modification of existing foundations |
| 90 | 145kV, 50c/s , 3150 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades along with modification of existing foundations |
| 91 | Single Phase 50c/s, outdoor metal oxide gapless type,200KV(rms) surge arrestor including surge counters/monitors, insulating base or associated accessories, auxillaries |
| 92 | Single phase 50 c/s, outdoor metak oxide gapless type ,120 KV (rms) surge Arrestor including surge counters/,insulating base all associated accessories, auxilariesacmonitors 200 KV surge Arrestor |
| 93 | 220KV Post Insulators solid core Type,Power Frequency withstand voltage 460KVP dry lighting impulse withstand voltage + 1050(KVP),Max. RIV(in microV) between 0.5Mhz to 2.0Mhz at 156KV (rms) for 220KV phase to ground voltage 1000mV |
| 94 | 132 KV Post Insulator Solid core/Polymer Type,Power frequency withstand voltage 275KV RMS Dry lightning impulse withstand voltage 1050 (KVP) |
| 95 | 33 KV Post Insulators Solid Core type power frequency withstand voltage 95 KV RMS Dry lightning impulse withstand voltage 170(KVP) |
| 96 | CONDUCTOR & HARDWARE FITTINGS |
| 97 | 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 98 | Flexible connector suitable for interconnection of 4\\" Al tube with 4\\" Al tube |
| 99 | Connector suitable for 3\\" IPS tube to single moose conductor |
| 100 | Connector suitable for 4\\" IPS tube to single moose conductor |
| 101 | Disc Insulators 70KN Ball socket type,145mm height and 255mm dia creepage total 430mm and 260mm protected (antifog) |
| 102 | Disc Insulators 120KN Ball socket type,145mm height and 280mm dia creepage total 430mm and 260mm protected (antifog) |
| 103 | Double Tension Fittings For Twin 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 104 | Double Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. |
| 105 | Double Tension Fittings suitable For Quad 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. |
| 106 | Double Suspension Fittings suitable For Quad 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. |
| 107 | Rigid Terminal connector for 33 KV BPI suitable for 3\\" Al tube |
| 108 | Rigid Terminal connector for BPI suitable for 4\\" Al tube |
| 109 | T Clamps Twin 500mm2 /Twin 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 110 | T clamps Twin 500mmsq/ 500mmsq made of aluminium alloy and shall comply in all respects with IS:5561-1970(latest edition) |
| 111 | T clamps 500mmsq/ 500mmsq made of aluminium alloy and shall comply in all respects with IS:5561-1970(latest edition) |
| 112 | T Clamps Quad 500mm2 / single 500 mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 113 | T connector suitable for 4\\" tube with twin moose conductor |
| 114 | P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 115 | Bimettalic Pad clamp twin 500mm2 , and shall comply in all respects with IS: 55561-1970 (latest edition) |
| 116 | Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162(rate given is 1.6xrate of(spacer for twin conductor),or it can vary) |
| 117 | Spacers For Quad 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162(rate given is 1.6xrate of(spacer for twin conductor),or it can vary) |
| 118 | Power and Control cables including termination of the cables |
| 119 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 120 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 121 | 2 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 122 | 5 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 123 | 12 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 124 | 16 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 125 | 2 core, 6sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 126 | 4 core, 6sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 127 | 4 core, 16sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 128 | 10 core, 2.5sqmm ,1100 V , PVC insulated, PVC Sheathed, FRLS, Galvanised steel wire/ strip armoured stranded copper conmductor control cable complete |
| 129 | STRUCTURES |
| 130 | Fabrication, Galvanisation, supply including packing and forwarding, transportation charges of 220KV, 132KV structutres |
| 131 | Galvanised Nuts and Bolts |
| 132 | Pipe type structure |
| 133 | DISMANTALLING OF EQUIPMENT/STRUCTURE |
| 134 | Dismantling of existing transformer foundation if needed |
| 135 | Dismantling of existing firewalls if needed |
| 136 | Dismantaling of existing 220KV twin Moose bus bars main and transfer bus by bringing down including opening of connectors, jumpers, droppers, tiers , beams etc for facilitation of conversion(twin Moose into Quad Moose System) |
| 137 | De-errection of existing 53.33 MVA transformers including opening of jumpers,draining of oil into barrels,opening of conservator tank,bushings,radiators etc and transportation to other grid station |
| 138 | Extension of already laid retaining wall (RW04) between 220/132 kV transformer bank and 132 kV switchyard |
| 139 | Concrete of M-25 grade having cube strength of with 20 mm nominal size coarse aggregate in 1:1:2( 41 mtrx3.35 mtrx(0.6+.03/2) above plinth level |
| 140 | Form work in walls (2x41x3.35) |
| 141 | Gravel packing behind retaining wall including carriage….complete job (41x3.35x0.6) |
| 142 | PVC Vent Pipe for weep holes…complete job150 mm dia (28x0.5x2.. |
| 143 | Steel Reinforcement as per approved drg & bar binding scheduile |
| 144 | Back filling of wall by available earth inmcluding mecanical carriage with lead of 300 mtr |
| 145 | FOUNDATION FOR TRANSFORMER AS PER CONDITIONS LAID IN SBD |
| 146 | Excavation in all type of soils including mixed soils (i.e. soils containing pebbles/boulders etc.) for any section including all labour, POL, hire charges of equipments and T&Ps etc. including sheeting & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings and direction of Engineer in-charge. |
| 147 | Plain cement concrete of specified grade and strength conforming to IS: 456 placed as sub-base under structural concrete or as shown in approved construction drawings at all levels including cost of all materials, labour, hire charges of equipments and T&P, POL, etc. complete for handling, transportation, batching, mixing, placing, vibrating, compacting, leveling, curing etc. as per specification, construction drawings and direction of Engineer-in-charge. |
| 148 | Concrete of M-10 grade (below foundation) having cube strength of 10 N / mm2 with 40 mm nominal size coarse aggregate. |
| 149 | Structural Cement Concrete ( plain/ reinforced) of specified 28 days strength (nominal size of coarse aggregate 20 mm) at all levels, including cost of all materials, labour, hire charges of equipments and T&P, POL, shuttering, curing, etc. complete for handling, transportation, batching, mixing, placing, vibrating, and rendering, cleaning and finishing the exposed over ground surfaces with cement mortar 1:3 (1 cement: 3 sand) to give smooth and even surface but excluding the cost of reinforcement complete as per specification, construction drawings and direction of Engineer-in-charges. |
| 150 | Concrete of M25 grade having cube strength of 25 N/mm2 at 28 days. |
| 151 | Supply & installation of 62 Kg/m, broad gauge rails conforming to Indian Railways specifications and fixing on RCC pedstrals including cost of all materials, labour, hire charges of equipments and T&P, fixing bolts, base plates, clamping plates etc. but excluding the cost of excavation, concrete, reinforcement, shuttering etc complete as per specification, construction drawings and direction of Engineer-ln-Charge |
| 152 | High yield strength cold deformed steel reinforcement bars conforming to IS: 1786 for R.C.C. or any other work including the cost of all materials, binding wire, labour, hire charges of equipments and T&P, bending, binding, placing and tieing in position, POL etc. complete as per specification, construction drawings and direction of Engineer-in-charges. |
| 153 | Cement Plaster 15 mm in 1:4 Mix, |
| 154 | Form work (complete job) |
| 155 | Construction of Fire wall |
| 156 | Excavation in all type of soils including mixed soils (i.e. soils containing pebbles/boulders etc.) for any section including all labour, POL, hire charges of equipments and T&Ps etc. including sheeting & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings and direction of Engineer in-charge. |
| 157 | Plain cement concrete of specified grade and strength conforming to IS: 456 placed as sub-base under structural concrete or as shown in approved construction drawings at all levels including cost of all materials, labour, hire charges of equipments and T&P, POL, etc. complete for handling, transportation, batching, mixing, placing, vibrating, compacting, leveling, curing etc. as per specification, construction drawings and direction of Engineer-in-charge. |
| 158 | Concrete of M-10 grade (below foundation) having cube strength of 10 N / mm2 with 40 mm nominal size coarse aggregate. |
| 159 | Structural Cement Concrete ( plain/ reinforced) of specified 28 days strength (nominal size of coarse aggregate 20 mm) at all levels, including cost of all materials, labour, hire charges of equipments and T&P, POL, shuttering, curing, etc. complete for handling, transportation, batching, mixing, placing, vibrating, and rendering, cleaning and finishing the exposed over ground surfaces with cement mortar 1:3 (1 cement: 3 sand) to give smooth and even surface but excluding the cost of reinforcement complete as per specification, construction drawings and direction of Engineer-in-charges. |
| 160 | Concrete of M25 grade having cube strength of 25 N/mm2 at 28 days. |
| 161 | Steel Reinforcement( TMT bars Fe 500D or More |
| 162 | Foundation of BPIs and gantry structure |
| 163 | Laying of transformer cooler foundation for single phase 105 MVA (as per drawing) for the existing fondations |
| 164 | Concreting of yard and laying of gravel |
| 165 | Concrete M25 with excavation , form work steel reinforcement etc |
| 166 | Diagnostic tools and other vital equipments |
| 167 | Insulation tester 15 kV of reputed make |
| 168 | Digital multimeter/Clampmeter of high accuracy |
| 169 | SF6 Gas filling kit |
| 170 | BDV kit of reputed make |
| 171 | Chain block 5 ton 6m lift & double pulley 3 ton |
| 172 | Single pulley 5 ton |
| 173 | 16mm & 18mm rope 90m bundle each |
| 174 | hydraullic compressor 150 ton |
| 175 | Heavy duty welding machine |
| 176 | hydraullic ladder 30 ft |
| 177 | Providing and installation of Event Logger, Disturbance Recorder & GPS System with PC along with energy management system . |
| 178 | Providing and installation of Electric fire extinguishers |
| 179 | Providing and installation of HD CCTV cameras 32 No covering whole GSS including 8 power transformers on both 220/132kv side & all 220/132kv bays, stores etc. along with monitor more than 50 inch, zooming 10X plus & more than 10Tb HDD /as per site Engineer |
| 180 | Providing and installation of Ammeters(40 no's), voltmeters(10no's), MW meters(15no's), MVAR meters(10no's), Energy meters(5no's), T&C switches(20no's), |
| 181 | \\"Battery Bank 220 V,300 AH , of 110 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant.\\" along with \\"220 V Battery charger (Three phase):(i) Float charging and load current ratings:30 Amp / 60Amp / 70Amp / 100Amp at 220 V to 252 V D.C.(ii) Boost charging current rating:50 Amps / 55Amp / 60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C.\\" Please Enable Macros to View BoQ information |