Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Upgradation work of Neurosurgery I.C.U. 14 Additional Beds in Old Dialysis Building at S.G.P.G.I. District-Lucknow (U.P.) |
| 2 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. For thickness of tiles above 25 mm and up to 40 mm |
| 3 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead. |
| 4 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In Cement mortar |
| 5 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge |
| 6 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer in-charge. |
| 7 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 8 | Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. |
| 9 | Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq.meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge. With cement mortar 1:4 (1cement: 4 coarse sand) |
| 10 | Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete. |
| 11 | Raking out joints in lime or cement mortar and preparing the surface for re-pointing or replastering, including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge. |
| 12 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 13 | Providing and laying Cement concrete 1:4:8 (1 cement : 4coarse sand : 8 graded stone ballast 40 mm nominal size) including supply of all materials.labour and T&P etc. required for proper completion of the work and curing complete. also including cost of formwork in foundation |
| 14 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 15 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 16 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:4 cement & coarse sand). |
| 17 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 18 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 19 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 20 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 21 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C.SLAB |
| 22 | TMT FE-500 or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of all steel and and over lapping & hooks. |
| 23 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 24 | Suspended floors, roofs, landings, balconies and access platform. |
| 25 | Providing and laying Vitrified tiles in floor without lean concrete of 500x 500mm sizes (thickness 10mm), with water absorption less than 0.08% and onforming to IS:15622, of approved brand & manufacturer, in desired colours and shades, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, including grouting of joints. Same as above but for 600X600mm size. |
| 26 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 15mm thick cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 27 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. Granite stone slab of colour black, Cherry/Ruby red Area of slab over 0.50 sqm |
| 28 | .Imported Self leveling compound: The hyper- fluid self-leveling product with prolonged work ability, extra rapid hardening, compensated shrinkage, suitable for high resistant adjustment from 2 to 4 mm of irregular non- planer substrates Before laying homogenous tiles with very low TVOC emission and hypo-allergenic cements. |
| 29 | P/L Vinyl Flooring 2mm complete of Superior Quality |
| 30 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part |) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. |
| 31 | 25 mm thick (for cupboard) including ISI marked nickel plated bright finished M.S. Piano hinges IS : 3818 marked with necessary screws with Extra for Providing and fixing flush doors with decorative veneering instead of non decorative ISI marked flush door shutters conforming to IS: 2202 (Part I) both side laminated. |
| 32 | Providing and fixing ISI marked magnetic catcher of approved quality in cupboard / ward robe shutters, including fixing with necessary screws etc. complete. Triple strip (horizontal type) |
| 33 | Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595 mm of approved texture, design and patterns having NRC (Noise Reduction coefficient) of 0.50 (minimum) as per IS 8225:1987, Light reflectance of 85% (minimum). Non combustible as per BS:476 (part-4), |
| 34 | fire performance as per BS:476 (part 6 &7), humidity resistance of 100%, thermal conductivity < 0.043 W/m K as per ASTM 518:1991, in true horizontal level suspended on inter-locking metal powder\ coated T-Grid of hot dipped galvanised iron section of 0.40 mm thick on Silhouette profile,rotary stiched double webbed white with 6 mm reveal profile (white/ black),comprising of main-T runners of size 15x42 mm of length 3000 mm, cross - T of size 15x42 mm of length 1200 mm and secondary |
| 35 | intermediate cross-T of size 15x42 mm of length 600 mm to form grid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 85x25x2 mm. |
| 36 | Galvanised iron perimeter wall angle of size 22x19x0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-Charge. 26.23.1 With 15 mm thick integral densified micro edge light weight calcium silicate false ceiling tiles |
| 37 | COST OF ROLLER BLINDS |
| 38 | Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm |
| 39 | for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, |
| 40 | EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, |
| 41 | plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. |
| 42 | After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. |
| 43 | Casement door double panel with French (False) Mullion with zinc alloy (Zamak) 3D hinges, multi point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. |
| 44 | Using R4 series with frame (64 mm & above) x (55 mm & above) & sash (64 mm & above) x (100 mm & above) & French (False) mullion (64 mm & above) x (60 mm & above). (Height above 2.5 metre). |
| 45 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). |
| 46 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 47 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 48 | Three track three panels sliding door with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, zinc alloy (Zamak) powder coated handle on two panels along with multi-point locking system, adjustable nylon rollers with SS 304 body. |
| 49 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 50 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 51 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 52 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. |
| 53 | (a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. Single leaf. |
| 54 | DOUBLE LEAF |
| 55 | Mild steel or iron work of small sizes and sections such and holding down bolts, hold fast tierods,gratings etc. ( when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work fabrication of holes doors, chaukhats nosing. |
| 56 | Fabrication of hold fast for door chaukhats and windows. |
| 57 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat withapproved steel primer all complete. Fixed to steel windows by welding |
| 58 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 59 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 60 | Providing and fixing flush doors with decorative veneering instead of non decorative ISI marked flush door shutters conforming to IS: 2202 (Part I) |
| 61 | Providing & fixing S.S. sliding door bolts ISI marked to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 62 | Providing and fixing S.S. Steel tower bolts with necessary screws etc. complete |
| 63 | (a) 250mm x 10mm. |
| 64 | (b) 200mm x 10mm. |
| 65 | Providing and fixing S.S. Steel handles with screws etc. complete (a) 125 mm |
| 66 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade. New work (Two or more coats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm). |
| 67 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material &sand papered smooth including cost of all materials. [Inside walls+Ceiling Area] |
| 68 | Painting with Anti-Fungal hygiene paint with approved quality which prevents the growth of mould, bacteria and yeasts for at least 5 years. The unparalleled durability of hygiene coatings helps to extend the maintenance cycle and to minimize all related material, labour and shut down costs. It shall have highly resistant to abrasives, detergents and weak acids and alkalis used in cleaning regimes & can be regularly steam cleaned without any loss |
| 69 | Providing and applying white cement based putty of average thickness 1mm approved brand and manufacture over the plastic wall surface to prepare the surface even and smost complete. |
| 70 | Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after .The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineerin-charge .The elevational area of the scaffolding shall be measured for payment purpose .The payment will be made once irrespective of duration of scaffolding. |
| 71 | Providing Medium Back Chair, Adjustable Back, PU Arm, PU Moulded Seat & Back, PP Seat Back Cover, Gas Lift, Nylon Base, Fabric Tapestry. Synchro Knee Tilt Make-GEEKEN model No-GB-408 |
| 72 | Providing 3 Seater Sofa With Powder Coated Arms & Legs, Perforated Seat Back, Leatherette Tapestry Size in mm - 1750(L) X 630(D) X 810(H) Make-GEEKEN model No-CUBIS 3 |
| 73 | Curtain Track V-Track Curtain Track - Its strong functional and fully reversible profile. itsmade of aluminium 606035- T6 –F22. White powder coating colour will be RAL 9010, in accordance with Qualicoat standard. Size of the profile are 34mm in height and 15 mm in thickness and reversible design. The weight of the profile is 448gm/meter. Runner/Glider hooks are made of nylon 6.6 with SS 304 grade hooks. Suspension Hanger Is made of aluminium 606035-T6-F22. White powder coating colour is RAL 9010. Size of profile is 14mm round tube. V-Track curtains - 100% polyster fabric treated with Water Repllant. |
| 74 | IV Hanger Telescopic & flexible IV Hanger- Bag holders is a telescopic i.e. raise and lower without disturbing the needles and tubes or causing patient discomfort. when in use with the suspension supported by Eze-Lock IV Carriage. The IV Bag Holder is to be made from stainless steel grade 304 for sanitation with foldable arms. It should be capable of running in the track suspended from the ceiling. Arms fold for sterilization and easy storage, compatible with IV track. |
| 75 | The Door Double leaves must be available in ground or powder coated version, The powder coating has to match in colour, surface and gloss-degree th e wall system the outer edges of the door must be closed with a continuous aluminium profile. Door window the insulating glass must consist of two glasses the door glass element has tob be connected to the door leaf with a reversible frame. the surface , colour and gloss degree has to match the door leaf (Hermetically Sealed Door) Door Size 1840 *2125 |
| 76 | X-Ray View Box: LED Twin Plate X-ray viewing screen ( 1000 x 700 x 100 mm), designed to provide a high level of control luminance without flicker. |
| 77 | Magnetic Writing list board |
| 78 | NURSE CALL SYSTEM- A nurse call system is a communication tool in healthcare facilities that allows patients to alert staff for assistance. The systems typically consist of a patient-activated call button (often at the bedside or in bathrooms), a central monitoring station for nurses, and various indicators like a light outside the room. Modern systems can be wired or wireless and may use IP (Internet Protocol) technology to send data over a hospital's existing network, enabling advanced features like real-time alerts, call tracking, and integration with other hospital systems. |
| 79 | CENTRAL MONITORING SYSTEM IN ICU A central monitoring system in an ICU is a centralized network that connects multiple bedside monitors, allowing a single nurse or technician to continuously track the vital signs and physiological data of several patients from a central location, like a nursing station. It displays real-time information such as ECG, heart rate, blood pressure, and oxygen saturation on a single screen, provides alerts for patient deterioration, improves efficiency, and allows for remote viewing to facilitate collaboration and timely intervention |
| 80 | SANITATION WORK |
| 81 | Providing and fixing water closet squatting pan ( Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS:7231, Parryware/Hindware/Seabird/Orient (Coral) with all fittings and fixtures complete including cutting and making good the walls and floors wherever required. |
| 82 | White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests |
| 83 | Providing and fixing white glazed earthen wate (European type) W.C. Pan 580mm dia,(10 ltr) PVC Flushing Cistern complete with G.I. Pull chain,M.S.Bracket of Engineer-in-Charge.(Standered size) |
| 84 | Providing & fixing white vitreous china wash basin with C.I. brackets painted white, 15 mm C.P. brass pillar taps, C.P. brass chain with rubber plug, 32mm C.P. brass waste of standerd pattern including cutting & making good the walls wherever required. |
| 85 | a)White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps |
| 86 | Providing and fixing white vitreous china flat back half stall urinal of size 580*380*350mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in D.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass including painting of fittings and cutting and making good the walls and floors wherever required: |
| 87 | Range of single half stall urinals with 5 litre PV.C. automatic flushing cistern. |
| 88 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 89 | Semi rigid pipe |
| 90 | 32 mm dia |
| 91 | 40 mm dia |
| 92 | Providing and fixing 600x450mm bevelled edge mirror of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 93 | Providing and fixing Stainless Steel AISI 304 (18/8) kitchen sink as per I.S. 13983 with C.I. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required : |
| 94 | Kitchen sink with drain board |
| 95 | 510x1040 mm bowl depth 250 mm |
| 96 | Providing and fixing PTMT Bottle Trap for Wash basin and sink |
| 97 | Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms |
| 98 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 99 | 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms. |
| 100 | CP Brass fittings |
| 101 | Providing and fixing unplasticised PVC connection pipe with brass unions |
| 102 | 45 cm length |
| 103 | 15 mm nominal bore |
| 104 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 |
| 105 | a) 15 mm nominal bore |
| 106 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. |
| 107 | a) 15 mm nominal bore |
| 108 | Providing and fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS:8931 |
| 109 | a) 15 mm nominal bore |
| 110 | Providing and fixing C.P. brass shower rose with 15 or 20mm inlet |
| 111 | 150 mm diameter |
| 112 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: |
| 113 | 15mm nominal bore |
| 114 | RAIN WATER SUPPLY |
| 115 | Providing and fixing unplasticised-PVC pipe clips of approved design to unplasticised-PVC pipes by means of 50x50x50 mm hard wood plugs, screwed with MS screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 116 | 110mm |
| 117 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 118 | 100 /90 mm dia |
| 119 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 120 | 110 mm |
| 121 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 122 | Bend 87.5 degree |
| 123 | 110 mm Bend |
| 124 | Shoe (Plain) |
| 125 | 110 mm Shoe |
| 126 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 127 | Providing and fixing unplasticised-PVC pipe clips of approved design to unplasticised-PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with MS screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 128 | 110 mm |
| 129 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 130 | INTERNAL WATER SUPPLY |
| 131 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testiang of joints complete as per direction of Engineer in Charge. |
| 132 | Concealed work including cutting chases and making good the walls etc. |
| 133 | 25mm dia nominal outer dia pipes |
| 134 | 50mm dia nominal outer dia pipes |
| 135 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 136 | Internal work-Exposed on wall |
| 137 | 20 mm nominal outer dia Pipes |
| 138 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 139 | Concealed work, including cutting chases and making good the walls etc. |
| 140 | 20 mm nominal outer dia Pipes |
| 141 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 142 | 25mm dia nominal bore |
| 143 | 50mm dia nominal bore |
| 144 | Providing and fixing brass stop cock of approved quality. |
| 145 | b) 20 mm nominal bore |
| 146 | Providing and placing on terrace (at all floor levels)polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fitting and base support for tank.[Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license]. |
| 147 | Capcity in Per Liters |
| 148 | SANITARY INSTALLATIONS & C.P FITTINGS |
| 149 | Providing and fixing in floor and wall face Ringfit UPVC ASTRAL ULTRADRAIN Conventional system for soil and waste water pipes conforming to (HSN CODE: 3917) Type B including jointing with seal ring. (i) Double socketed pipes. |
| 150 | a) 110mm dia P.V.C. pipe |
| 151 | b) 90mm dia P.V.C. pipe |
| 152 | Providing & fixing UPVC Floor trap of self cleansing design with CP Jali complete in all respects. (Make : Supreme / Finolex / Prince) |
| 153 | P-Trap type Floor Trap 110 x 90 mm |
| 154 | Providing and fixing terminal guard. |
| 155 | a) 110mm |
| 156 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 157 | 110mm bend |
| 158 | 90 mm bend |
| 159 | Coupler |
| 160 | 110mm |
| 161 | Single tee with door |
| 162 | 90x90x90 mm |
| 163 | 110x110x110 mm |
| 164 | Providing and fixing C.P. brass Two-way angle valve for EWC points & for fixing Ablution Health Fauct of approved quality conforming to15 mm nominal bore |
| 165 | Providing and fixing clean out plug |
| 166 | 110 mm dia. |
| 167 | Providing and fixing on wall face unplasticised-Rigid PVC pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 168 | 160mm dia Under floor |
| 169 | Providing and fixing pvc Inlet fitting with 2 inlets 80 mm size fabricated from 110 mm dia PVC pipes(approx. length=150mm to 300mm) and fixed to PVC trap with joint and set in cement concrete as per standard drawing complete. |
| 170 | SUB-HEAD - 1 : INTERNAL WIRING & LIGHTING PROTECTION SYSTEM |
| 171 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 172 | Group C |
| 173 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc .as required. |
| 174 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 175 | 2 X 2.5 sq . mm + 1 X 2.5 sq. mm earth wire |
| 176 | 2 X 4 : sq. mm + 1 X 4 sq. mm earth wire |
| 177 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 178 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 179 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 180 | 25 mm |
| 181 | 32 mm |
| 182 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch,connection etc. as required. |
| 183 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
| 184 | Supplying and fixing modular blanking plate on the existing modular plate& switch box excluding modular plate as required |
| 185 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/wooden block including connections etc. as required. |
| 186 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 187 | Extra for fixing the Louvers/ shutters complete with frame for exhaustfans of all sizes. |
| 188 | SUBHEAD 2: Miscellaneous Items |
| 189 | Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass as directed by Engineer Incharge. |
| 190 | Providing Safety mat made of elastomeric polymers Material (Class B) 1.2 M wide with thickness 2.5 mm to withstand 12KV dielectric strength AS PER relevant IS Code |
| 191 | SUB-HEAD-3 : TELEPHONE & TV SYSTEM |
| 192 | Supplying, drawing, connecting and testing of 0.5 mm dia annealed copper conductor PVC insulated PVC sheathed telephone wire inexisting conduit/wire way duct etc. as required of following sizes: |
| 193 | 2 Pair (4 core) |
| 194 | Supplying and fixing following size/ modules, GI box alongwith modularbase & cover plate for modular switches in recess etc as required |
| 195 | 4 Module (125mmX75mm) |
| 196 | 6 Module (200mmX75mm) |
| 197 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modularplate etc. as required |
| 198 | Telephone socket outlet |
| 199 | TV socket outlet |
| 200 | RJ-45 Data Socket outlet |
| 201 | Telephone Tag Box 10 pair |
| 202 | 6U Data Rack |
| 203 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existingsurface/ recessed Steel/ PVC conduit as required. |
| 204 | 2 run of cable |
| 205 | SUB-HEAD-4 : LIGHT FIXTURES: |
| 206 | Supplying, installation, Testing & Commissioning of LED Recessed/ surfaceDown lighter (Round/ square/ Rectangular) SMD type of following bodymaterial with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum powerconsumption should not more than the specified rating and Fixture shallbe confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. asrequired with Minimum 5 year OEM warranty. System lumen efficacy ≥105and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for alltesting required for LED fixtures as per BIS shall be submitted. Shape sizeand CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LEDjunction temperature shall not rise above 90°C) |
| 207 | 12 -15 watt |
| 208 | Supply & fixing of water tight-oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming to IP65 and above protection, IK 08, High purity/ transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detachable driver set, open and short circuit protection, suitable for 24 |
| 209 | Supply and fixing of LED Tube Light with heavy duty Metal Box type Tube Light fitting 1x22 watt suitable for upto 1x 22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect |
| 210 | Supply and fixing of LED Tube Light with heavy duty Metal Box type Mirror Light fitting 10 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended Complète in all respect |
| 211 | Supply and fixing of wall bricket 10 watt LED bulb Polycarbonate tube light complete Including tube suitable for both surface & suspended Complète in all respect |
| 212 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., offollowing body material and construction as per IS : 10322 with driver as perthe requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuitprotection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified GlareRating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver& electrical circuitry), of minimum 50000 Burning Hours with, 70% of initialLumen maintained till life ends as per LM80 extrapolation IES TM-21-11report, CCT 3000°K / 4000°K / 5700°K /6000°K / 6500°K (As perANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximumpower consumption should not more than the specified rating and Fixtureshall be of relevant BIS standard and trade mark certificate ( T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. complete in all respect i/c connections with 1.5 sq mm FRLS,PVC insulated copper conductor single core cable and earthing etc. asrequired with Minimum 5 year OEM warranty. System lumen efficacy ≥105<120 lm/Watt output . LM79 & LM80 Test report from NABL lab for alltesting required for LED fixtures as per BIS shall be submitted. Shape sizeand CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LEDjunction temperature shall not rise above 90°C). |
| 213 | Supply, Installation, Testing and Commissioning of ceiling fan with BrushLess Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit,safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS :374-2019), THD (Total Harmonic Distortion) less than 10%, remote(preferably mobile app based) for speed control and all remainingaccessories including safety pin, nut bolts, washers, temperature rise=75degree C (max.), insulation resistance more than 2 mega ohm, suitable for230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fanSupply, earthing etc. complete as req |
| 214 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min(Minimum) |
| 215 | Supply and fixing of Ex-Fan 200mm Complète in all respect |
| 216 | SUBHEAD- 5: DISTRIBUTION BOARD |
| 217 | Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 218 | 12 way, Double door |
| 219 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (Butwithout MCB/RCCB/Isolator) |
| 220 | 4 Way Double door |
| 221 | 6 way Double door |
| 222 | Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioningetc. as required |
| 223 | 40 amps 4P MCB |
| 224 | 63 amps 4P MCB |
| 225 | DP MCB |
| 226 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB),having a sensitivity current 30 mA in the existing MCB DB complete withconnections, testing and commissioning etc. As required. |
| 227 | 25 amps |
| 228 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing andcommissioning etc. as required. |
| 229 | Single pole 6-32Amp C Curve |
| 230 | Supplying and fixing single pole blanking plate in the existing MCB DBcomplete etc. as required. |
| 231 | SUB-HEAD-6 : EARTHING SYSTEM |
| 232 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 233 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. without charcoal/ coke and salt as required. |
| 234 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 235 | Supply and laying of 25mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm) |
| 236 | SUB-HEAD-7 : CABLES |
| 237 | Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 238 | 25 sq. mm 3-1/2 core |
| 239 | 35 sq. mm 3-1/2 core |
| 240 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kv grade as required. |
| 241 | 25 sq. mm 3-1/2 core |
| 242 | 35 sq. mm 3-1/2 core |
| 243 | SUB-HEAD-8 : CABLE TRAY |
| 244 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray With perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspendersincluding G.I. bolts & nuts, etc. as required. |
| 245 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 246 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 247 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspendersincluding G.I. bolts & nuts, etc. as required. |
| 248 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 249 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 250 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 251 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 252 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 253 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 254 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 255 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 256 | Intelligent Fire Alarm System |
| 257 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 258 | Four loop panel |
| 259 | Supplying, installation, testing & commissioning of repeater panel wih 320 character display with inbuilt reset, acknowledge and silence switches complete as required. |
| 260 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 261 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 262 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 263 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 264 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 265 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 266 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 267 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 268 | Cable & Wiring |
| 269 | Supplying & laying of 2 X1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 270 | AIR CONDITIONERS SYSTEM |
| 271 | AIR HANDLING UNITS |
| 272 | Supply,installation,testing and commissioning of factory fabricated double Skin Chilled Water Air handling Unit floor mounted fabricated out of extruded aluminium section with 0.8 mm pre plasticized / pre coated Galvonized steel sheet out side & 0.8 mm polished SS sheet inside with backward curved fan in Supply and forward curved in exhaust, Supply & Exhaust fan for operation on 415 volts + 10%, 50 Hz + 5% AC supply , 8 row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with Coil section, Copper Header, Pre Filter , Fine Filter and Hepa Filter in Supply Air and Pre Filter in Exhaust Air, mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated. AHU Must have Fresh Air Damper with Cowl & Bird Screen, Return Air Damper and Supply Air Damper. Make:Edgetech, Systemair, ZECO |
| 273 | 9000 cfm with 8 row cooling coil + 2 row heating coil (Pre+fine + Hepa filter) with 125 mm St. Pr. For supply Fan & 3000 CFM Exhaust Air, 40mm St. Pr. For Exhaust fan. |
| 274 | 2000 cfm with 8 row cooling coil + 2 row heating coil (Pre+fine + Hepa filter) with 125 mm St. Pr. For supply Fan |
| 275 | CHILLED WATER PIPING |
| 276 | Supply ,installation & testing of MS \\"C\\" Class Chilled Water Piping with supports etc. duly insulated with 50mm thick Expanded Polystrene, covered with GI Wiremesh, 12mm thick Sand, Cement & Plaster complete in all respect.Make:- Jindal/ Jindal Hissar/Tata/eqv. |
| 277 | 100 mm dia MS \\"C\\" Class |
| 278 | 80 mm dia MS \\"C\\" Class |
| 279 | 50 mm dia MS \\"C\\" Class |
| 280 | 40 mm dia MS \\"C\\" Class |
| 281 | 25 mm dia MS \\"C\\" Class |
| 282 | CHILLED WATER VALVES |
| 283 | Supply, installation & testing of Butterfly Valves/ Y-Strainers complete with gasket, flange, nuts, & bolts duly insulated with 50mm thick Expanded Polystrene, covered with GI Wiremesh, 12mm thick Sand, Cement & Plaster complete in all respect. MAKE :- Advance, Honeywell, Zoloto& C&R |
| 284 | Butterfly/ BAll Valves suitable for PN-16 Pressure. |
| 285 | 100 mm dia |
| 286 | 80 mm dia |
| 287 | 50 mm dia |
| 288 | 40 mm dia |
| 289 | 25 mm dia |
| 290 | \\"Y\\" Strainers: |
| 291 | 80 mm dia |
| 292 | 50 mm dia |
| 293 | 40 mm dia |
| 294 | 25 mm dia |
| 295 | Supply & installation of GI B Class Drain Water Piping duly insulated with 25mm thick Expanded Polystrene, covered with GI Wiremesh, 12mm thick sand cement plaster. Make:- Jindal, Tata |
| 296 | 40mm dia |
| 297 | Supply,installation & testing of Gate Valves complete with fittings like nipples, elbows, tees, bends, sockets etc. |
| 298 | 15 mm dia |
| 299 | 20 mm dia |
| 300 | Supply,installation,testing and commissioning of Auto Air Vents |
| 301 | 15mm dia |
| 302 | Supply, installation & testing of Pressure Guages complete with fittings like nipple socket etc.. |
| 303 | Supply,installation and testing of Industrial Type Thermometer complete with fittings. |
| 304 | Supply & installation of 2-Way Motorised / 3-Way Motorised Valves with Motor, Modulating Thermostat, 24V Transformer complete in all respect. |
| 305 | 80 mm dia |
| 306 | 50 mm dia |
| 307 | 40 mm dia |
| 308 | 25 mm dia |
| 309 | Supply & installation of Vibration Isolation Pads for Air Handling Units. |
| 310 | PCC Foundations for Air Handling Units complete with materials like sand, cement, coase sand, gitty & plster etc. |
| 311 | Supply,installation,balancing and commissioning of AL sheet metal rectangular ducting complete with rubber gaskets,elbows splitter , vanes, hangers, supports etc.as per approved drawings and specifications of complete as required.following sheet thickness |
| 312 | 20 Guage |
| 313 | 22 Guage |
| 314 | Supply and installation of Box Type GI Volume Control Dampers |
| 315 | Supply & fixing of Powder Coated Aluminium Grills/Diffusers. |
| 316 | Supply and installation of GI Fire Dampers with Fusible Links |
| 317 | Supply, fabrication and installation of Canvass connection for Air Handling Units. |
| 318 | Supply & fixing of Duct Insulation Chemically Crossed Linked Closed Cell Polyethylene XLPE Aluminium Foiled Supply and Return Air Duct sticked with adhesive etc. complete in all respect. |
| 319 | 13 mm thick Insulation |
| 320 | Thermocol Duct insulation with cement plaster |
| 321 | Masonary Civil Opening in walls for Piping and Ducting. |
| 322 | Charges for Scaffolding arrangement for installation of Supply and Return Air Duct. |
| 323 | SITC of Startor Pannel for AHU with suitable size incoming MCCB, complete with conector, relay, Push button, Auto/ Manual switch, on/off indication, power and control wirring complete in all respect micro switch remote wiring, (220-24v) Transformer for Damper, Supply should be provide in Startor Panel (1 No) |
| 324 | 100AMP TP MCCB as incomer 16 amps TP MCB with Star Deta/Dol Startor |
| 325 | 40AMP TP MCCB as incomer 16 amps TP MCB with 1 No. 3.5 Kw DOL Starter |
| 326 | Supply,installation,testing and commissioning of PVC insulated sheathed 1.1 KV grade Armoured Aluminium Conducter Power Cables from various Electrical Panels upto their respective equipment. |
| 327 | 4 C X 10 mm2 Aluminium Cable |
| 328 | 4 C X 16 mm2 Aluminium Cable |
| 329 | 4 C X 25 mm2 Aluminium Cable |
| 330 | 3.5 C X 120 mm2 Aluminium Cable |
| 331 | Supply,installation,testing and commissioning of PVC insulated sheathed Copper Control Cables. |
| 332 | 6 C X 1.5 mm 2 |
| 333 | SITC of Inline fan of 2200 CFM Capacity. |
| 334 | Provision for integration of AC system with BMS system including DDC panels with compatible Software and control wiring |
| 335 | Dismentling of existing AHU ,Duct and pipeing |
| 336 | Dismentling of existing FALSE CEILING |
| 337 | Earthing Electrorod copper dia 50 mm including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc, with charcoal/cock and salt as required. |
| 338 | Supplying and Laying of 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required.( jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 339 | Supplying and Laying of 25 mm X 3 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required.( jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 340 | MANIFOLD FOR OXYGEN SUPPLY |
| 341 | SITC of Oxigen Manifold 5+5 cylinder. |
| 342 | FULLY AUTOMATIC CONTROL PANEL |
| 343 | Supply, fixing, testing and commissioning of Fully automatic oxygen control panel as per Specifications |
| 344 | SUPPLY, FIXING, TESTING AND COMMISSIONING OF THE DISTRIBUTION PIPE : COPPER PIPE as per EN 13348 standards - R250 (half hard) upto 54 mm and R200 (annealed) for larger sizes, and the cooper fittings will be of Medical Grade as per specifications |
| 345 | 12 mm (OD) x 0.7 mm Thickness |
| 346 | 15 mm (OD) X 1.0 mm Thickness |
| 347 | 22 mm (OD) X 1.0 mm Thickness |
| 348 | 28 mm (OD) X 1.0 mm Thickness |
| 349 | INSTALLATION &TESTING- LINE ISOLATION VALVES |
| 350 | 12mm lockable line valves with Nut /Nipple Adopter |
| 351 | 15mm lockable line valves with Nut /Nipple Adopter |
| 352 | 22mm lockable line valves with Nut /Nipple Adopter |
| 353 | 28mm lockable line valves with Nut /Nipple Adopter |
| 354 | LINE PRESSURE ALARM |
| 355 | Area line pressure alarm - 3 Gases (2 gas & 1 vac) |
| 356 | GAS OUTLETS (TERMINAL UNITS) as per HTM 02-01 , BS 5682 standards |
| 357 | Oxygen |
| 358 | Vaccum |
| 359 | Medical Air |
| 360 | OXYGEN FLOW METER WITH HUMIDIFIER BOTTLE |
| 361 | Supply, Installation, testing and commissioning of Indigenous BPC Oxygen flow meter with Humidifier Bottle autoclavable 121 degree centigrate. 0-15 L/min standard flow rate. |
| 362 | WARD VACCUM UNIT |
| 363 | Supply,Installation,Testing & Commissioning of Indigenous Ward Vacuum Unit with collection jar size 600 ml autoclavable at 121 degree centigrate. |
| 364 | PRESSURE HOSES |
| 365 | HP Tube for Oxygen, Medical & Surgical Air |
| 366 | LP Tube for Vaccum |
| 367 | ZONAL VALVE BOX |
| 368 | 3 Gases |
| 369 | Bed Head Panel |
| 370 | 4 FT PANE L |
| 371 | SITC of D-Type Oxygen Cylinder |
| 372 | Dismantling of Old MGPS Line , Bed Head Panel |
| 373 | Double Medical Pendant System For ICU |
| 374 | The double medical pendant system is required for, intensive care units (ICUs), and similar clinical environments. It must be a ceilingmounted, dual-arm system designed to facilitate the organization and accessibility of medical gases, electrical outlets, and other utilities required for patient care. The system should feature a modular design that allows for future upgrades and easy integration of additional components. Each arm must have a load-bearing capacity of at least 60 kg, with a combined system capacity of 120 kg. The arms should offer a wide rotational range of at least 270 degrees, with smooth, stable movement and adjustable stops to prevent unintended repositioning. The pendant must incorporate an electro-pneumatic or friction-based braking system to ensure stability when in use. It should include a minimum of six electrical sockets per arm, capable of supporting high- and low-voltage applications. Additionally, the system should accommodate at least three types of medical gas |
| 375 | outlets, such as oxygen, vacuum, and compressed air, with integrated pressure and flow controls for each gas outlet. The pendant should also offer provisions for mounting medical monitors or displays, with adjustable height and swivel features to enhance ergonomics and usability. Constructed from medical-grade, corrosion-resistant materials, the system must ensure durability and ease of cleaning to support hospital hygiene standards. Compliance with international safety and quality standards, such as IEC 60601 or equivalent, is mandatory. Certification from recognized quality assurance bodies like CE or FDA must be provided. The pendant may also include optional features such as integrated LED lighting for localized illumination. |
| 376 | GST Extra as applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail