| 1 | Supply, installing, testing and commissioning, factory made cubical type, LT feeder pillar box outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar of 3 Phase and Half neutral fashion, the panel should be dust proof and made with 3mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement, Mild Steel Angle Iron Frame above the Normal Ground and duly powder coated on the out side and inside, complete all as specified and directed including following accessories(a) Aluminium bas bar 400 amps set of 3 phase and half neutral, supported with suitable size of heavy duty porcelain gland lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral.b) MCCB 250 amps, 415 volt, 36 KA Breaking capacity 4 pole electromagnetic release type duly connected to Bus Bar. Note: All incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc. The cost earth work, PCC foundation work is deemed to be included in the above item. |
| 2 | Supply, installing, testing and commissioning, factory made cubical type, LT feeder pillar box outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar of 3 Phase and Half neutral fashion, the panel should be dust proof and made with 3mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement, Mild Steel Angle Iron Frame above the Normal Ground and duly powder coated on the out side and inside, complete all as specified and directed including following accessories (a) Aluminium bas bar 400 amps set of 3 phase and half neutral, supported with suitable size of heavy duty porcelain gland lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral.b) MCCB 160 amps, 415 volt, 36 KA Breaking capacity 4 pole electromagnetic release type duly connected to Bus Bar. Note: All incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc. The cost earth work, PCC foundation work is deemed to be included in the above item. |
| 3 | Supply, laying and testing cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 16 sq mm 4 core |
| 4 | All as per item no 3.00 above but 3.5 Core 240 Sqmm |
| 5 | All as per item no 3.00 above but 3.5 Core 185 Sqmm |
| 6 | All as per item no 3.00 above but 3.5 Core 150 Sqmm |
| 7 | All as per item no 3.00 above but 3.5 Core 120 Sqmm |
| 8 | All as per item no 3.00 above but 3.5 Core 95 Sqmm |
| 9 | All as per item no 3.00 above but 3.5 Core 70 Sqmm |
| 10 | All as per item no 3.00 above but 3.5 Core 50 Sqmm |
| 11 | All as per item no 3.00 above but 3.5 Core 35 Sqmm |
| 12 | All as per item no 3.00 above but 4 Core 25 Sqmm |
| 13 | Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvanised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m. The GI Electrode shall be pre-filled with Crystalline Conductive Material (CCM). The GI electrode shall be surrounded with 25 kg Backfill compound to provide maximum contact between the electrode and Back Fill Compound. The earthing pit should be cover with PCC (1: 2: 4, B1) cover of 450 x 450 mm complete all as specified and directed. |
| 14 | Supply and install, testing and commissioning Out door LT feeder panel factory certified and cubicle type of suitable size and 3mm thickness of CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/ exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following: : -Incoming:(a) MCCB 4 pole Micro processor release type, 250 Amp, 415 Volts 36KA - 01 No Outgoings: (b) MCCB 4 pole Electro magnetic release type, 100 Amp, 415 Volts 36KA - 01 Nos (c) MCCB 4 pole Electro magnetic release type, 63 Amp, 415 Volts16KA - 02 Nos(d) MCCB 4 pole Electro magnetic release type, 40 Amp, 415 Volts 16KA - 02 Nos(e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital Voltmeter, Ammeter three phase class including CTs of ratio 400/ 5 with selector switch. Note: (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs glands nuts, bolts etc the cost of work is deemed to be included in the above item. (b) The cost shall also be include the breaking of floors/ walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfacesMake: C&S/ Legrand/ Siemens or Equivalent |
| 15 | Supply and install, testing and commissioning Outdoor LT feeder panel factory certified and cubical type of suitable size and 3mm thickness of CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/ exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following: - Incoming:(a) MCCB 4 pole Micro processor release type, 250 Amp, 415 Volts 36KA - 01 No Outgoing: (b) MCCB 4 pole Electro magnetic release type, 160 Amp, 415 Volts 36KA - 01 Nos (c) MCCB 4 pole Electro magnetic release type, 100 Amp, 415 Volts16KA - 01 Nos (d) MCCB 4 pole Electro magnetic release type, 63 Amp, 415 Volts 16KA - 02 Nos(e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital Voltmeter, Ammeter three phase class including CTs of ratio 400/ 5 with selector switch.Note: (a)All existing incoming and out going cables are to be connected to the above panel with proper lugs glands nuts, bolts etc the cost of work is deemed to be included in the above item. (b) The cost shall also be include the breaking of floors/ walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfacesMake: C&S/ Legrand/ Siemens or Equivalent |
| 16 | Supply and install, testing and commissioning Out door LT feeder panel factory certified and cubical type of suitable size and thickness of CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/ exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following: - Incoming:(a) MCCB 4 pole Micro processor release type, 160 Amp, 415 Volts 36KA - 01 No Outgoing:(b) MCCB 4 pole Electromagnetic release type, 100 Amp, 415 Volts 16KA - 01 Nos (c) MCCB 4 pole Electromagnetic release type, 63 Amp, 415 Volts16KA - 02 Nos (d) MCCB 4 pole Electromagnetic release type, 32 Amp, 415 Volts16KA - 02 Nos (e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital Voltmeter, Ammeter three phase class including CTs of ratio 400/ 5 with selector switchNote: (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/ walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfacesMake: C&S/ Legrand/ Siemens or Equivalent |
| 17 | S&F hot press moulded SMC junction/ terminal box of size with internal dimensions of 200 x 140 x 95 E mm with hinged door, incl provision of 4 way connector 415 Volts made out of polycarbonate or Bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/ glands, fixed on pole by means of clamps made out of MS flat iron of size 25mm x 3 mm 2 Set including dismantling of old unserviceable all as specified and as directed. Make Syntex/ C&S/ Havells |
| 18 | S&F 1.5 sqmm 3 core copper conductor cable for street lights complete all as specified and directed |
| 19 | Supply and fixing automatic street light switch using infrared sensor based nature switch for automatic switching of street lights Nature switch operation should bebased on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off > 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs The sensor along with suitable power contactors incoming outgoing MCB of TP and automanual (sensor bypass selection option should be enclosed in a pole / wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 three phase load of 8 KW with circuit wiring min 6 sq mm. 3 nos contactor each of 20 amps, incoming outgoing MCB (3 nos) rating 20 amps of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt (4 nos) for fixing on pole / wall complete all as directed including taking down old one Model no Swadeep-02 EC 8KW 3P or equivalent from Havells/ Legrand |
| 20 | Cutting the existing PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing underground cable and filing back with excavated soil up to 75% road portion and 25% shall be made with cement concrete 1: 2: 4 using 20mm graded aggregate stone complete all as specified and directed |
| 21 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 MPA working pressure |
| 22 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/ Steel pole, laying of underground cable in trenches etc and getting out in Hard / Dense soil complete all as specified and directed. |
| 23 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed. |
| 24 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. Please Enable Macros to View BoQ information |
| 25 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. Please Enable Macros to View BoQ information |