| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair/ Maint of LT Bus-Bar Trunking network of electrical infrastructure and connected accessories at CHNC under GE(U) Udhampur. Contract No: GE/U-56/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply and fix 2000A Sandwich type Aluminium Feeder busway (3L+N+PE), with Multi Layer PET Class-F Insulation,bus bar coated/Plated with Cu + Tin Throughout length,100% N, 65kA for 1 sec, Integral Earth in GI as Standard with IP-55, maximum support interval of 10ft , 12kV Impulse Withstand, C-Ribbed Housing in 1.5mm Thick, Paint:-RAL-7035 ,Temp rise: 55 deg. over ambient of 40 deg. & operating voltage = 1000V as conforming to IEC 60439-2 Standards with following specification, complete all as specified and directed by Engineer-in-Charge :-Make :- legrand,Schneider,Siemens |
| 3 | Flange End- IP55 |
| 4 | Elbows -IP55 |
| 5 | Straight Length -IP55 (Indoor) |
| 6 | Suspension Brackets |
| 7 | Copper Flexibles |
| 8 | Supply and fix 800A Sandwich type Aluminium Feeder busway (3L+N+PE), with Multi Layer PET Class-F Insulation,bus bar coated/Plated with Cu + Tin Throughout length, 100% N, 42kA for 1 sec, Integral Earth in GI as Standard with IP-55, maximum support interval of 10ft , 12kV Impulse Withstand, C-Ribbed Housing in 1.5mm Thick, Paint:-RAL-7035 ,Temp rise: 55 deg. over ambient of 40 deg. & operating voltage = 1000V as conforming to IEC 60439-2 Standards with following specification :-Make :- legrand,Schneider,Siemens |
| 9 | Flange End- IP55 |
| 10 | Straight Length -IP55 (Indoor) |
| 11 | Copper Flexibles |
| 12 | Tap-Off Boxes |
| 13 | Supply and fix 630A Sandwich type Aluminium Feeder busway (3L+N+PE), with Multi Layer PET Class-F Insulation,bus bar coated/Plated Cu + Tin Throughout length. 100% N, 42kA for 1 sec, Integral Earth in GI as Standard with IP-55, maximum support interval of 10ft , 12kV Impulse Withstand, C-Ribbed Housing in 1.5mm Thick, Paint:-RAL-7035 ,Temp rise: 55 deg. over ambient of 40 deg. & operating voltage = 1000V as conforming to IEC 60439-2 Standards with following specification :-Make :- legrand,Schneider,Siemens |
| 14 | Flange End- IP55 |
| 15 | Straight Length -IP55 (Indoor) |
| 16 | Copper Flexibles |
| 17 | Tap-Off Boxes |
| 18 | Supplying and install Heavy Duty cable tray (SRFL100G) ,hot-dip galvanised mild steel , with size 1000MMX60MM and 0.9mm thick ness. , complete with bends, tees, reducers, cross members, couplers, and all necessary accessories.The tray shall be hot dip galvanized after fabrication with zinc coating not less than 120 microns (or as specified), fixed on walls/ceiling with M.S. angle iron supports, threaded rods, clamps, anchor fasteners, including painting of supports with one coat of red oxide primer and two coats of synthetic enamel paint of approved shade complete all as specified and directed by Engineer-in-Charge.Note :- (a) Drilling, cutting and welding as required Fixing with dash fasteners / anchor bolts Earthing of cable tray with 25x3 mm GI strip along with cable tray is included in the quoted rate of the items.(b) Cost is included for L supports for wall with all accessories such as nut ,bolt ,washers etc.(c) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.d) All meterial such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays shall include in the quoted rates of the items. |
| 19 | Supplying and install Heavy Duty cable tray (SRFL100G) ,hot-dip galvanised mild steel , with size 450MMX40MM and 0.9mm thick ness. , complete with bends, tees, reducers, cross members, couplers, and all necessary accessories.The tray shall be hot dip galvanized after fabrication with zinc coating not less than 120 microns (or as specified), fixed on walls/ceiling with M.S. angle iron supports, threaded rods, clamps, anchor fasteners, including painting of supports with one coat of red oxide primer and two coats of synthetic enamel paint of approved shade complete all as specified and directed.Note :- (a) Drilling, cutting and welding as required Fixing with dash fasteners / anchor bolts Earthing of cable tray with 25x3 mm GI strip along with cable tray is included in the quoted rate of the items.(b) Cost is included for L supports for wall with all accessories such as nut ,bolt ,washers etc.(c) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.d) All meterial such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays shall include in the quoted rates of the items. |
| 20 | Supplying and install Heavy Duty cable tray (SRFL100G) ,hot-dip galvanised mild steel , with size 300MMX2.5MM and 0.9mm thick ness. , complete with bends, tees, reducers, cross members, couplers, and all necessary accessories.The tray shall be hot dip galvanized after fabrication with zinc coating not less than 120 microns (or as specified), fixed on walls/ceiling with M.S. angle iron supports, threaded rods, clamps, anchor fasteners, including painting of supports with one coat of red oxide primer and two coats of synthetic enamel paint of approved shade complete all as specified and directed by Engineer-in-Charge.Note :- (a) Drilling, cutting and welding as required Fixing with dash fasteners / anchor bolts Earthing of cable tray with 25x3 mm GI strip along with cable tray is included in the quoted rate of the items.(b) Cost is included for L supports for wall with all accessories such as nut ,bolt ,washers etc.(c) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.d) All meterial such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays shall include in the quoted rates of the items. |
| 21 | Supply fix in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 2000A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous, earth fault & individual fault LED indication, complete all as specified and directed by Engineer-in-Charge.Make: Lauritz Knudsen, ABB, Havells, |
| 22 | Supply fix in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 1600A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous, earth fault & individual fault LED indication complete all as specified and directed by Engineer-in-Charge.Make: Lauritz Knudsen, ABB, Havells, |
| 23 | Supply fix in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 1250A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous, earth fault & individual fault LED indication complete all as specified and directed by Engineer-in-Charge.Make: Lauritz Knudsen, ABB, Havells, |
| 24 | supply and fix Mild Steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, not exc 5cm long, complete all as specified and directed by Engineer-in-Charge. |
| 25 | Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick CRCA sheet mounted on 60cm long legs made out of 40X40X6 mm equal angles duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operationn, complete all as specified and directed by Engineer-in-Charge fitted with following accessories. (i) 1 No. 200 Amps MCCB incoming.(ii) 1 Set 200 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved.(iii) 2 No. 160 Amps TPN MCCB outgoing (iv) 2 No. 63 Amps TPN MCCB outgoing (v) 12 No. 40/63 Amps TPN MCB outgoing |
| 26 | Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick CRCA sheet mounted on 60cm long legs made out of 40X40X6 mm equal angles duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified and directed by Engineer-in-Charge fitted with following accessories. (i) 1 No. 160 Amps MCCB incoming.(ii) 1 Set 160 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved.(iii) 2 No. 100 Amps TPN MCCB outgoing (iv) 2 No. 63 Amps TPN MCCB outgoing (v) 12 No. 40/63 Amps TPN MCB outgoing Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |