| 1 | Wiring for light point fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable of Polycab /Finolex /RR Kabels/Anchor /Salzer/ Apar/ Grandlay/ eq. make to be approved by EIC in surface/recessed medium class PVC conduit ((25 mm dia PVC Conduits with allied accessories including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering/pop/paiting etc complete job including cost of conduits /Bends and allied accessories), with 6 Amps modular switch, modular plate of Schneider /ABB/L&T/Legrand/ eq. make to be approved by EIC, suitable Gi box and earthing the point with 1.5 s q.mm FRLS PVC insulated copper conductor single core cable etc. as required (P+N+E) for Normal and invertor points per room is to be provided seperately from switch board. The Job includes p/f of Lighting Junction deep /Fan deeps made of heavy guage sheet steel of standard make dully isi marked to be laid in slab complete job. |
| 2 | Wiring for lighti power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable of Polycab/Finolex/Anchor/RR Kabels /Salzer/ Apar/ Grandlay/ eq. make to be approved by EIC to be laid recessed medium class PVC conduit (25 mm dia PVC Conduits with allied accessories including 2 cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering/pop/paiting etc complete job including cost of conduits/Bends and allied accessories) including alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required of Polycab/Finolex /Anchor/RR Kabels/ Apar/ Grandlay/ eq. make to be approved by EIC |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable of Polycab/ Finolex/Anchor/RR Kabels /Salzer/ Apar/ Grandlay/ eq. make to be approved by EIC to be laid in recessed medium class PVC conduit (25 mm dia PVC Conduits 3 upto 4 Sq.mm wires and 32mm dia from 6 Sq.mm to 10 Sq.mm wires including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering/pop/paiting etc complete job including cost of conduits /Bends and allied accessories as reqd. |
| 4 | 2 X 1.5 sq. mm +1 X1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm +1 X 2.5 sq. mm earth wire |
| 6 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing of 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. (Schneider /ABB/L&T/Legrand / eq. make to be approved by EIC.) |
| 7 | Supplying and fixing suitable size Gi box with modular plate and cover in front on surface or in recess, including providing and fixing of 2 No's of 3 pin 5/6 A modular socket outlet and 2 No's of 5/6 A modular switch, connections etc. as required. (Schneider /ABB/L&T/Legrand / eq. make to be approved by EIC) |
| 8 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. (Schneider /ABB/L&T/Legrand / eq. make to be approved by EIC) |
| 9 | Supplying and fixing of 16 Amps Box type S-S Combine for invertor input and output |
| 10 | Supply and fixing of 16 Amps 3-pin top of SSK/ eq. / eq. make to be approved by EIC |
| 11 | Supply and fixing of 25 mm dia medium class PVC medium grade conduit to be recessed on walls/ floor complete with all allied accrues like bends, tees etc for paving way of laying of wires of heating points/ circuits, machine point/ circuits and sub mains. the job includes cutting of walls/ floors with required hydraulic cutter and refacing of walls with cement plaster of required ratio or with P.O.P after laying of conduits refacing to its original position by way of supply and applying of painting of required color to effectged areas complete matching with existing surface. Anchor/Polycab/Finolex/TMT Plus /paraflex/ eq. make to be approved by EIC. |
| 12 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safety rope, copper winding, Power Factornot less than 0.9, Service Value (CM/M/N) minimum 6.00, Air deliveryminimum 210 Cum/Min, 10 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, remote or electronic regulator unit for speedcontrol and all remaining accessories including safety pin, nut bolts, washers, temperature rise 75 degree C (ma><.), insulation resistancemore than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Usha/crompton/Halonix/Orient / eq. make to be approved by EIC. |
| 13 | Supply, Installation, Testing and Commissioning of 900 mm sweep, BEE 5 star rated, ceiling h Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm down rod, 2nos, canopies, shackle kit, safety rope, copper winding, Power Factornot s than 0.9, Service Value (CM/M/AN) minimum 6.00, Air deliveryminimum 210 Cum/Min, 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, remote or electronic regulator unit for speedcontrol and all remaining accessories including safety pin, nut bolts, washers, temperature rise 75 degree C (ma><.), insulation resistancemore than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Usha/crompton/Halonix/Orient / eq. make to be approved by EIC. |
| 14 | Supply, Installation testing and commissioning of 250 mm sweep Exhaust Fans of Usha /Crompton Greaves/Havel's incl making of necessary connections and making of necessary space in walls/Windows as per site. The Job includes providing and fixing of shutter of suitable size backlite hylum sheet for fixing of exhaust fan of Usha/Orient /Crompton/Helonix / eq. make to be approved by EIC. |
| 15 | Supply and fixing of 18 Watts LED surface mounted (Commercial type having aluminium Body and Housing) downlighter having following specficafications The luminaire should have a colour temperature of 6500°K, CRI≥80 and SDCMS5. The downlighter shall be back-lit & not side-lit. The driver shall have THD≤10% (@full Load) and PF ≥ 0.95 (@full load). Luminaire shall be designed to emit initial system lumen output of 1980 lumens with minimum system efficacy of 110 lumen/watt. The luminaire housing should made of pressure die-cast aluminium. The fixture should comply with the parameters as per IS10322. The luminaire shall have impact resistance of IK02 & ingress protection of IP20. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The luminary shall have average 13 life of 50000 hrs operating temperature-10 C to +45 C The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab & BIS certificate for LED Luminaire & Driver. Approved make Philips /Lighting techology/Trilux/wipro/Endo/Igguzini/Regent/Helonix/Bajaj / eq. make to be approved by EIC.. The Agency /firm must submit the Techanical data sheet (TDS) on OEM Letter head along with requisite certificates for approval by an officer from the department not below the rank of SDO prior to the supply of materials |
| 16 | Supply installation, Testing and Commissioning of 10-12 Watts, 2 ft long LED tube light fitting having PVC Body of standard make dully isi marked incl ceiling rose and 2-core transparent wire for connections complete job. The luminaire should have a LEDs with colour consistency SDCM ≤ 5, CRI ≥ 80 and CCT of 6500K. Luminaire shall be designed to emit initial system lumen output of 1400 lumens with minimum system efficacy of 120 lumen/watt. The luminaire shall comply to lifetime of 50000Hrs @ L70850 with design ambient temp 45°C. The electronic driver used shall have a power factor 20.95 and THD 14 ≤10%, suitable for an operating voltage range of 140-270V AC, THD≤10%, Current Ripple $5%, Internal surge protection should be minimum 4KV, electrical insulation class should be Class. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. of Philips /Lighting techology/ Trilux/ wipro/ Endo/ Igguzini / Regent / eq. make to be approved by EIC |
| 17 | Supply, Installation, Testing and Commissioning of 1P 66, 50 Watt LED Flood Luminaries having Aluminium body of standard make dully isi marked to be fitted on walls/poles with necessary cliffs /Clamps with nuts and bolts complete job. The system efficacy of the luminaire shall be ≥120lm/w. The LEDs used in the luminaire shall be from either Lumileds, Osram, Nichia, APT Electronics and CREE make, shall have CCT of 5700°K, CR≥70, SDCMs5, Life of 50000Hrs @ L70850. The luminaire shall have IP rating of IP66 & IK rating of IK07. The luminaire shall have lens made of polycarbonate & optical cover made of 15 toughened glass. The LED driver shall have operating voltage range of 140V to 270V, PF20.95 full load, THDs 10% @ full load, In-built surge protection of 4KV, HV Cut off @ 325V (±15V). The luminaire shall have 10KV SPD in-built inside the luminaire.. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver of Philips / Lighting techology/ Trilux/ wipro /Endo/ Igguzini / Regent / eq. make to be approved by EIC |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator of Legrend/L&T/ABB Simens/schinder / eq. make to be approved by EIC |
| 19 | 16 way, Double door |
| 20 | Supply and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit suitable for inductive load of following poles in the existing MCB DB complete with ctions, testing and commissioning etc. as required of legrand/ABB/Schneider (Acti-L&T/Simens / eq. make to be approved by EIC |
| 21 | Supplying and fixing of 32 Amps rating DP 240/415 volts (10KA) of Legrend /L&T/ABB Simens /Schinder make dully isi marked complete with connections of Legrand / ABB /Schneider (Acti-09) /L&T/Simens / eq. make to be approved by EIC (2 no's for Sub boards and Two Numbers for AC |
| 22 | Supplying and fixing of 40 Amps rating DP 240/415 volts (10KA) of Legrend /L&T/ABB /Simens /Schinder make dully isi marked complete with connections of Legrand / ABB /Schneider (Acti-09) /L&T/Simens / eq. make to be approved by EIC |
| 23 | Supplying and fixing of 100 Amps rating DP 240/415 volts (10KA) of Legrend/L&T/ABB 20 /Simens /Schinder Schneider (Acti-09) make dully isi marked complete with connections of Legrand / ABB /Schneider (Acti-09) /L&T/Simens / eq. make to be approved by EIC |
| 24 | Supply, Laying, Testing & Commissioning of 25 sq.mmm 2- core armored Al Cable XLPE/PVC Insulated and Steel sheathed of Havells/Eq. make, including cost thimbles on input aswell 21 as output sides dully crimped with hydraulic crimping tool incl making of necessary connections Including rolling of LT Colour coded types for main service line from LT pole |
| 25 | Supply and laying of DWC pipe (HDPE) having 40/32 mm (OD/ID)dia to be 22 laid partially under ground including execuation upto 2 ft deep and refilling back and disposal 160 Mtr 110 of surplus earth or surface mounted complete job complete job |
| 26 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoall coke and salt as required. The job includes providing and fixing of main hole 300mm x 300mm PVC Chamber with its cover complete job |
| 27 | Providing and fixing 25 mm X 5 mm G.1. strip on surface or in recess for connections etc. as required Please Enable Macros to View BoQ information |