| 1 | WORK NAME |
| 2 | Supply & drawing Wiring for sub mains ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 4.0 sq.mm |
| 3 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 4 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 5 | Add Extra in Item no.62.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 6 | Add Extra for Laying of one number additional XLPE power cable of11/33 KV (Earthed) voltage grade direct in ground in the sametrench in one tier horizontal formation including excavation of trenchof size additional 20 cm in width, with procedure as per followingpoints:- (a) Make a river sand bed of height 125 mm along thetrench, (b) Lay another cable in middle of trench in such manner thatspacing between another cable is 20 cm, (c) Provide sand bed ofheight 125 mm on top of the cable. (d) Lay the protective Commonburnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabsof 50 mm thickness and 225 mm wide just above the sand bedvertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfillthe excavated soil leaving 300 mm from the Ground level. (f)Lay theCable warning tape and again back-fill the remaining portion of thetrench upto the ground level and compacting the earth |
| 7 | Add Extra in Item no. 62.5 if Excavation done in Hard Rock / CCroad / TAR Road and making Good the same |
| 8 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. 63 mm |
| 9 | 110 mm |
| 10 | Providing and Laying RCC Foundation for Octagonal / ConicalStreet Light poles, High mast Poles as per Drawing attach at TableP-4 with Following Procedure & All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR .A) Excavation of Pit for Foundation Size upto required depth fromGround levelB) Dressing of Pit and Dry stone pitching 200 mm thick includingsupply of stones and preparing surface complete.C) Providing and laying in position cement concrete of M-10 grade of75 mm thicknessD) Reinforcement for R.C.C. work with TMT bars includingstraightening, cutting, bending, placing in position and binding allcomplete.E) Centring and shuttering including strutting , propping etc. andremoval of form work for Footing and PedestalF) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe &Foundation Bolt with template as per OEM Recommendations.G) Providing and Laying Reinforce cement Concrete of M-25 gradein Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2no. 100 mm long, 10 mm dia. Lugs on each face. Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr |
| 11 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. Electrolytic grade Aluminium bus bar 6010 grade |
| 12 | Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . One day reserve (Analog type ) |
| 13 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2:2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR400 Amp , 35 kA, adjustable O/L & adjustable S/C setting |
| 14 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting |
| 15 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. 400 Amp |
| 16 | 250 Amp |
| 17 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in- charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Four pole MCB (With B/C curve tripping Characteristics) 50/63 A rating |
| 18 | P & Fixing Powder coated CRCA sheet enclosures on existing angle iron frame by means of nuts and bolts and making holes , Din rail etc. as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 1.6 mm thick |
| 19 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediatedLaboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 150.0 Sq. mm 3.5 core |
| 20 | 300.0 Sq. mm 3.5 core |
| 21 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 22 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 11 KV End Termination Kit Outdoor type 3 core 120/150/185 Sq.mm |
| 23 | 11 KV Straight Through Joint Kit 3 core 120/150/185 Sq.mm |
| 24 | 11 KV End Termination Kit Indoor type 3 core 120/150/185 Sq.mm |
| 25 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 26 | SITC of star rated Aluminium wound distribution Transformer offollowing rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as perIS 2026- 1977 & losses as defined as per 2014 (Fourth Revision)Level-1 . including standard accessories like conservator, silica gelbreather, radiator, fins, HT cable box & LT cable boxes, temperaturerise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree Cfor above 200 KVA, ISI marked drain valve, Dial type Temperaturegauge, first filling of transformer oil as per IS :335-1953, Epoxybased paint, including carrying of pre-commission Testing &Charging of Transformer complete in all respect .The Transformer shall be subjected to routine factory tests (as perIS:2026 and IS:1180) including testing from CTL of discom beforecharging of transformer & complete installaion must be certified fromElectrical Inspectorate office as per Indian Electricity rule, (CTLtesting charges and Electrical Inspection charges shall bereimbursed by the department to the contractor). All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR 250 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 27 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on die cast housing to allow traceability/ authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. High Power LED Flood Light Minimum lumen output 8700 lm |
| 28 | High Power LED Flood Light Minimum lumen output 14800 lm |
| 29 | Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705- 1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in-charge.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . Ring type tape wound CT C T Class 1, Ratio upto 150/5, Burden 5 VA |
| 30 | C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA |
| 31 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 6.4 mm thick |
| 32 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digitaltype (up to 500) V range Volt meter / Direct- Ammeter / CT oertatedammeter/ Frequency meter / KWH meter / Multi Function Meter /Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x96 mm including making connection by PVC insulated copperconductor with PVC sleeves / channel etc. as required. All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR . Three phase AMP + HZ + PF + KW + KVA + KVAR +KVARH+KWH+DUAL ENERGY+ ENERGY+THD-I, THD-V & RUNHRS |
| 33 | CPCB-IV complianced DG Sets CPCB-IV complianced125 kVA DG Set |
| 34 | SITC of PLC Based Auto main failure (AMF) Panel fabricated fromCRCA sheet steel 2 mmThick , Powder coated finish , Engine Start& Stop commands, control Relays , Ammeter & Voltmeter withselector switches, Control & 2 nos 4 pole Power Contactors with 2no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual& Alarm indication for faults, UPS, operator interface panel completein all respect suitable for following capacity DG sets: AppropriateTest Certificate/ report of product/accessories from OEM/PanelManufecturer shall be submitted. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR . 100 KVA to 140 KVA |
| 35 | Providing & Fixing of self healing IP20 MPP type shunt capacitor(banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitorshall be fitted with discharge resistors, pressure sensitivedisconnector ( PSD ) and shall have dissipation factor less than0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Minover current capacity 1.8 times rated current & peak inrush currentmin. 300 times of rated current, llife expectancy greater than100000hrs (temp class - 25 D) in 440 V/480 V Capacitor and for525 V should life expectancy minimum 1,65,000 hrs (temp class - 25D) including making connections, testing etc. as required.All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR . Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor(Bank) |
| 36 | Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3phase sensing compensation power factor correction relay Size139mm x 139 mm, Operating Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli ampsecondary current , self analysing auto c/k setting according totargeted power factor setting, the relay shall have digit display unitfor display of real power factor, targeted power factor, lag/leadcapacitor switching status, alarm output for under current, overcurrent, insufficient compensation, communication interface with RS485, indication of switching on units, auto/manual status, and shallhave over load protection, no volt release , having multi parameterlike KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5Cast Resin CT ( refer CT specs in this chapter )for sensing the relayincluding making coonection with 1.5 Sq.mm copper wire etc. asrequired. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR . 6 to 8 stage |
| 37 | Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % DetunedReactors conforming to IEC 61558-2-20 & IEC 60076-6 Aluminiumwound for harmonics filter with 180% to 200 % Linearity, H - ClassInsulation ( 180 degree C), high temp. Disconnection above 155 degC., ambient temperature: +60 deg C. with thermal cut off switch inexisting panel with following Capacitor ratings. including makingconnections, testing etc. as required. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR . 7 % (189 Hz) Aluminium wound Reactors 25 KVAR Please Enable Macros to View BoQ information |