| 1 | Inspection, Testing & Maintenance of Fire Hydrant, HVWS & Sprinkler System as per technical specification & inventory list | Inspection, Testing & Maintenance of Fire Hydrant, HVWS & Sprinkler System as per technical specification & inventory list |
| 2 | Pressure testing of entire fire hydrant, sprinkler & HVWS system piping @14 kg/cm² water pressure including finding out leaks & rectification of leaks, if any | Pressure testing of entire fire hydrant, sprinkler & HVWS system piping @14 kg/cm² water pressure including finding out leaks & rectification of leaks, if any |
| 3 | Overhauling of pumps (As & when required) as per technical specification | Overhauling of pumps (As & when required) as per technical specification |
| 4 | Main Electric Pump (2283 lpm, 94 m, 75 kW) | Main Electric Pump (2283 lpm, 94 m, 75 kW) |
| 5 | Diesel Engine Driven Pump (2283 lpm, 94 m, 83 BHP) | Diesel Engine Driven Pump (2283 lpm, 94 m, 83 BHP) |
| 6 | Jockey Pump (250 lpm, 83 m, 5.5 kW) | Jockey Pump (250 lpm, 83 m, 5.5 kW) |
| 7 | Booster Pump (450 lpm, 35 m, 5.5 kW) including spare parts | Booster Pump (450 lpm, 35 m, 5.5 kW) including spare parts |
| 8 | Providing spare parts for overhauling of following pumps as per technical specification | Providing spare parts for overhauling of following pumps as per technical specification |
| 9 | Main electric fire pump, Make - Kirloskar, Model - SCT 100/30 (2283 lpm, 94 m, 75 kW) | Main electric fire pump, Make - Kirloskar, Model - SCT 100/30 (2283 lpm, 94 m, 75 kW) |
| 10 | Diesel engine fire pump, Make - Kirloskar, Model - DSM 100/36 (2283 lpm, 94 m, 83 BHP) | Diesel engine fire pump, Make - Kirloskar, Model - DSM 100/36 (2283 lpm, 94 m, 83 BHP) |
| 11 | Fire - Jockey pump, Make - Kirloskar, Model - KCIL 15-07 (250 lpm, 83 m, 5.5 kW) | Fire - Jockey pump, Make - Kirloskar, Model - KCIL 15-07 (250 lpm, 83 m, 5.5 kW) |
| 12 | Servicing/ Overhauling of valves as per technical specification | Servicing/ Overhauling of valves as per technical specification |
| 13 | Gate/ Sluice Valves (upto 150 mm dia.) | Gate/ Sluice Valves (upto 150 mm dia.) |
| 14 | Swing Check NRV (upto 150 mm dia.) | Swing Check NRV (upto 150 mm dia.) |
| 15 | Fire Brigade 4-way inlet valve | Fire Brigade 4-way inlet valve |
| 16 | Water flow alarm valve with gong | Water flow alarm valve with gong |
| 17 | Deluge valve with alarm gong | Deluge valve with alarm gong |
| 18 | Landing valves (each outlet) | Landing valves (each outlet) |
| 19 | Painting of fire pipeline/structure/valve/vessel of various sizes with two coats of primer & two coats of enamel paint after thorough cleaning of pipe as per technical specification | Painting of fire pipeline/structure/valve/vessel of various sizes with two coats of primer & two coats of enamel paint after thorough cleaning of pipe as per technical specification |
| 20 | Writing names/ numbers on Fire hydrant/ wet risers by painiting/ stenciling as per technical specification | Writing names/ numbers on Fire hydrant/ wet risers by painiting/ stenciling as per technical specification |
| 21 | Providing & replacing pressure transducer as per technical specification | Providing & replacing pressure transducer as per technical specification |
| 22 | Providing & installing of 63 mm (2.5 inch) dia dial type SS 316 glycerine filled pressure gauge of 1/4 inch BSP connector as per technical specification | Providing & installing of 63 mm (2.5 inch) dia dial type SS 316 glycerine filled pressure gauge of 1/4 inch BSP connector as per technical specification |
| 23 | Providing, installing & testing of acrylic tube water level indicator for fire hydrant air vessel as per technical specification | Providing, installing & testing of acrylic tube water level indicator for fire hydrant air vessel as per technical specification |
| 24 | Providing & installing PVC plastic cap with SS chain for landing type fire hydrant valves as per technical specification | Providing & installing PVC plastic cap with SS chain for landing type fire hydrant valves as per technical specification |
| 25 | Providing and installing 150 NB dual plate check valve as per technical specification | Providing and installing 150 NB dual plate check valve as per technical specification |
| 26 | Providing and installing 50 NB test & drain valve as per technical specification | Providing and installing 50 NB test & drain valve as per technical specification |
| 27 | Providing and installing 15/20/25 NB SS304 ball valve as per technical specification | Providing and installing 15/20/25 NB SS304 ball valve as per technical specification |
| 28 | Providing Anti Corrosive Spray in red colour for fire system piping as per technical specification | Providing Anti Corrosive Spray in red colour for fire system piping as per technical specification |
| 29 | Providing & replacing following sprinklers as & when required as per technical specification: | Providing & replacing following sprinklers as & when required as per technical specification: |
| 30 | 15 mm dia recessed gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, with rosette plate [Pendent type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respect | 15 mm dia recessed gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, with rosette plate [Pendent type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respect |
| 31 | 15 mm dia gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, (K-115) - Side Wall Type Sprinkler with jet of 3/6 m with all assembly complete in all respect | 15 mm dia gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, (K-115) - Side Wall Type Sprinkler with jet of 3/6 m with all assembly complete in all respect |
| 32 | 15 mm dia gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, [upright type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respect | 15 mm dia gun metal sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, [upright type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respect |