| 1 | Making trench less under ground hole across the roads/cement concrete pathway at a depth of about 1 mtr. by means of manual augor and connecting pipes to suit the pipe/cable of size up to 150 mm/300 mm dia. i/c making excavation on both side of road/pathway for making trenchless hole and refilling the same with excavated soil after laying pipe & cable through trenchless hole. watering. dressing complete as required as per instruction of Engineer-incharge. (Cost of laying of cable & pipe is not included in this item) |
| 2 | Supply of heavy duty 1100 V grade, XLPE insulated, PVC sheathed armoured cable with aluminium conductor for the following size with ISI mark confirming to IS : 7098 part-1 amended up to date as required. 3.5 x 300 sqmm Aluminium conductor cable |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required Above 185 sq. mm and upto 400 sq. mm |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. Above 185 sq. mm and upto 400 sq. mm |
| 5 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 6 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 8 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 9 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 10 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 11 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 12 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 300 sq. mm (70mm) |
| 13 | Supplying, installation, testing and commissioning of cubical panel/box on the existing bus bar panel, size should be not less than 800mm x 800mm x 400mm (nominal) duly powder coated fabricated out of 2mm thick CRCA sheet , having equally sized three phase and neutral aluminium conductor Bus Bar to carry 1000 Amp, current and suitably insulated with colour coded Heat Shrink Sleeve etc complete including drilling holes in existing cubical panel making connections from existing bus bar with required accessories like nut bolts etc as required. The cubical panel should having provision for entry of 2 no. 3.5 x 300 sq mm XLPE cable, should be duly powder coated in required colour shade, earth studs etc., as required |
| 14 | Supplying, installation, testing and commissioning of wall mounted panel, size should be not less than 1700mm x 600mm x 400mm (nominal) duly powder coated fabricated out of 2mm thick CRCA sheet as tetailed below in the suitable size to accommodate all the required mounting with lockable arrangement should be duly powder coated in required colour shade, earth studs etc., as required4 pole 800amp 50KA MCCB = 1 No3 Phase Indication lamps LED type with suitable protections = 1 set Digital Voltmetre (0-500) volt, 96 mm X 96mm size = 1 No Digital Ampere Meter (0-800) Amp, 96 mm X 96 mm size =1 NosCTs 800/5 Amp Class-I = 3 Nos.6 Amp SP MCB=3 NosASS Rotary selector switch= 1 NosVSS Rotary selector switch= 1 NosBus Bar :- Equally sized three phase and neutral aluminium conductor Bus Bar to carry 1000 Amp, current and suitably insulated with colour coded Heat Shrink Sleeve |
| 15 | Supplying, installation, testing and commissioning of the following out door feeder pillar of adequate depth, size should be not less than 1700mm x2800mm x700mm (nominal) duly floor mounted, weather proof IP-54 fabricated out of 2 mm thick CRCA sheet as detailed below in the suitable size to accommodate all the required mountings, with double door lockable arrangement, feeder pillar should be in sloping roof, as per the approved drawing, the entire feeder pillar should be mounted on 50 mm x 50mm x 6mm angle iron with minimum 600 mm long legs to be grouted in ground in suitable size CC foundation the feeder pillar should be duly powder coated in required colour shade, earth studs etc., as required (The feeder pillar should be interlock for both suuply)In Coming 4 pole 800amp 50KA MCCB = 2 No 3 Phase Indication lamps LED type with suitable protections = 2 setDigital Voltmetre (0-500) volt, 96 mm X 96mm size = 2 No Digital Ampere Meter (0-800) Amp, 96 mm X 96 mm size =2 NosCTs 800/5 Amp Class-I = 6 Nos.6 Amp SP MCB=6 NosASS Rotary selector switch= 2 NosVSS Rotary selector switch= 2 NosBus Bar :- Equally sized three phase and neutral aluminium conductor Bus Bar to carry 1000 Amp, current and suitably insulated with colour coded Heat Shrink SleeveOut Goings 400 amp 50KA FPMCCB = 2 No.250 amp 50KA FPMCCB = 2 No.200 amp 36KA FPMCCB = 2 No.125 amp 36KA FPMCCB = 2 No.100 amp 30KA/36KA FPMCCB = 2 No. 63 amp 10 KA C Curve TP&NMCB = 1 No.63 amp 10 KA C Curve DPMCB = 2 No.32 amp 10 KA C Curve DPMCB = 1 No. Please Enable Macros to View BoQ information |