| 1 | FIRE PUMP ROOM EQUIPMENTSupplying, installing, testing and commissioning of electrical motor driven Booster pump of Monoblock type capable to deliver 450 LPM at 35MWC.The pump shall be coupled to TEFC motor of suitable HP with speed of 2900RPM and complete set shall mounted on common base frame. Make willo/kilosker/ |
| 2 | Supplying, installing, testing and commissioning of 5000 litr Sintex water tank for fire porpose terace floor with RCC Base frame for seating of tank |
| 3 | Control panel for fire pumps for auto action :Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 125 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. Star Delta starter with O/L and Single Phasing Preventor suitable for 15HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge |
| 4 | SITC of FRLS,PVC outer sheateh, steel armoured, aluminium , 1100v grade power cables with glands etc.The minimum size of the cables shall as mentioned below,4 C x 16 Sq.mm |
| 5 | 2 C x 1.5 Sq.mm |
| 6 | G.I. Earthing strips of 50mm x 6mm thick, strip shall be run for PUMPS to Panel. |
| 7 | Supplying, Installing, Testing and commissioning of waffer type C.I. Non-return valves as per with required flanges, nuts, bolts and gaskets etc. complete of size 100 mm nominal dia.as per direction of engineer in charge.Make-Zoloto/Leader/Audco100 mm nominal dia |
| 8 | Supplying, Installing, Testing and commissioning of CI butterfly valves (PN 10) as per BS 5155 slim seal standard lever operated type with required flanges, nuts, bolts etc. complete of size 100 mm nominal dia.Make-Zoloto/Leader/Audco100mm nominal dia |
| 9 | SITC of Gun metal chrome finished Ball valves with fittings of screwed end type.Make. Kartar/newage/Safeguard15mm dia. |
| 10 | 25 mm dia |
| 11 | Supply and installaion of pressure switches of suitable range for pump sets.as per direction of engineer in chargeMake-Indfos/Grandfos. |
| 12 | Supply and installaion of pressure gauges of suitable range for pump sets.as per direction of engineer in chargeMake-H Guru/G Guru. |
| 13 | HYDRANT SYSTEMSupplying, installing, testing and commissioning of MS Pipes confirming to IS 1239 Pt - I Heavey grade with fittings such as Reducers,Tees, elbows, flanges. With painting of 1 coats of red oxide primer and 2 coats of PO red paint. Make Tata/Jindal100mm nominal dia |
| 14 | 80mm nominal dia |
| 15 | 25mm nominal dia |
| 16 | Supplying, erecting and commissioning of Landing Hydrants comprising of the following in the Fire duct;Providing and fixing Single headed hydrant having outlet of 63 mm dia (2.1/2inch) N.B. hydrant (IS:5290) landing valve in Stainless Steel Morris Pattern instanteous coupling type TAC / LFA approved & ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc.Make-Newage/Safex/Omex. |
| 17 | Providing & fixing 63mm dia RRL hose pipe a 15 mtr length per IS 636 TYPE A TAC/ LFA approved of standard length of approved pattern and size including gun metal male and female Coupling duly bound with copper wire etc. complete.Make-Newage/Safex/Omex. |
| 18 | Providing and fixing Stainless Steel standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:.Make-Newage/Safex/Omex. |
| 19 | Supplying & fixing first aid fire hose reel of thermoplast braided suitably reinforced 20 mm size & 30 m standard length with 5 mm tapering branch nozzle, 25mm dia. Pipe to connect to riser with cut off ball valve attachment. Hose to be swinging type wall mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts (Including drum and swivel arrangement) etc complete..Make-Newage/Safex/Omex. |
| 20 | Providing and fixing TAC approved fire hose cabinet to house fire hydrant & hose, including all other related accerrories fabricated from M.S. sheet (2mm thick) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 nos. hoses. The hose box size is 750 mm x 600 mm x 300 mm |
| 21 | Supplying and fixing 2 way fire brigade connection of cast iron body with 2 Nos. Gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for 100 mm dia MS pipe connection, conforming to IS904 as reqd. |
| 22 | Supplying and fixing of automatic air release valve with unions etc. complete.as per direction of engineer in charge |
| 23 | FIRE EXTINGUISHERSCarbon-di- oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge nozzle, bend & horn, wal mounting bracket etc. complete, confirming to IS: 15683.Make Minimax/Intime/Fire shield |
| 24 | ABC stroed pressure powder type fire extinguisher of 6 Kgs. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with control discharge hose, wall mounting bracket etc. complete, confirming to IS:15683. Minimax/Intime/Fire shield |
| 25 | MANUAL FIRE ALARM SYSTEMManual Fire AlarmSystem-:Supply, installation, testing and commissioning ofConventional type Main Fire Alarm Control Panel (FACP), the panel shall be conventional type fire detection and alarm system with capacity of 4 zone complete with all accessories and battery back up for 48 hours in standby mode and 15 minutes in alarm condition. The panel shall have minimum of 80 character display complete accessories.Make-System sensor by Honeywell/Bosch. |
| 26 | Supplying, installing, testing and commissioning of conventional type Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-System sensor by Honeywell/Bosch.. |
| 27 | Supplying, nstalling, testing and commissioning of Manual call points, break glass type made out of CRCA sheet with Hammer and chain. Please Enable Macros to View BoQ information |
| 28 | Supplying, nstalling, testing and commissioning of Manual call points, break glass type made out of CRCA sheet with Hammer and chain. Please Enable Macros to View BoQ information |