| 1 | Wiring for lighting points/fan points/ exhaust fan points/call bell points with 1.5 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit, with 240V 6A modular switch , modular plate and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable, etc. as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR/ Grandlay/ Apar or eq. make to be approved by EIC ) excl.cost of conduit. |
| 2 | Wiring for light/power plug points (15/16A heating points) with 2x4 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing, etc. as required. (Maximum two points shall be connected on one circuit).(Havells/ Polycab/ Anchor/ Finolex/KEI/RR / Grandlay/ Apar or eq. make to be approved by EIC) excl.cost of conduit |
| 3 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 6 pin 15/16 A modular socket outlet and 15/16A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent to be approved by EIC) |
| 4 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 2 no. 3 pin 5/6 A modular socket outlet and 2 no. 5/6A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or eq. to be approved by EIC) |
| 5 | Supplying and fixing of modular sockets/ indicators/switches on existing modular plate and switch box , incl. connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent to be approved by EIC) |
| 6 | i.3 pin 5A - 10A socket. |
| 7 | ii. indicator. |
| 8 | Point wiring for 5A -10A socket out lets (computer points) with 2x2.5 sq mm (P+N)FRLS PVC insulated 660/1100volt grade flexible stranded copper conductor wires in recessed or surface conduiting system and earthing the point with 1 x 2.5 sq. mm single core copper wire (loop earthing),(Maximum two points shall be connected on one circuit).(Havells/ Polycab/ Anchor/ Finolex/KEI/RR/ Grandlay/ Apar or eq. make to be approved by EIC) excl. cost of conduit |
| 9 | Supply, installation, testing and commissioning of 18 Watt LED recessed/ mounted (round or square) Down lighters having aluminum body, minimum 100lm/w, average life 50000 hours, LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India , Operating temperature -10`C to +45`C. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Halonix/Wipro/ eq. make to be approved by EIC). Commercial series. |
| 10 | Supply, installation, testing and commissioning of 200-250 mm sweep shutter type exhaust fans, incl. cost of ceiling rose and making of space in walls/ windows as per site and necessary connections. (Havells/ Philips/ Crompton/ eq. make to be approved by EIC). |
| 11 | Supply, installation, testing and commissioning of 400 mm sweep wall fans of Havells/ Crompton Greaves/Bajaj/ Usha/ eq. make. Sample to be got approved), incl. making of necessary connections. |
| 12 | Supply, installation, testing and commissioning of 1 star 1200 mm sweep ceiling fans of Havells / Crompton Greaves/Bajaj/ Anchor/ eq. make. (Sample to be got approved), incl. cost of extension of GI rod (if required) and making of necessary connections. |
| 13 | Supply and fixing of two module stepped electronic fan regulator on the existingmodular plate switch box, incl. connections but excluding modular plate etc. as reqd. |
| 14 | Supply, installation, testing and commissioning of 50 Watt LED Flood lighting luminaries having aluminum body, minimum 100 lm/w, the luminary housing should be aluminum and the luminary optics shall have a high efficiency with transmittance, average life 50000 hours, Operating temperature -10`C to +45`C. LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/Wipro/ eq. make to be approved by EIC). |
| 15 | Supplying and fixing of modular blanking plates on existing modular plate and switchbox ,excluding modular plate as required. |
| 16 | Wiring for sub mains along with earth wire in FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, excl. cost of conduits(Havells/ Polycab/ Finolex/ Anchor/KEI/RR / Grandlay/ Apar/ equivalent make to be approved by EIC). |
| 17 | 2 x 2.5 sq.mm + 1x 2.5 sq. mm earth wire (Lighting and inverter circuit) |
| 18 | 2 x 4 sq.mm + 1x 4 sq. mm earth wire |
| 19 | 2 x 6 sq.mm + 1x 6 sq. mm earth wire |
| 20 | 4 x 10 sq.mm + 1x 6 sq. mm earth wire |
| 21 | Supply and fixing of 6 way (4 + 18) Double door surface/ recess mounting , Horizontal type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBs and Incomer. . |
| 22 | Supply, installation, testing and commissioning of 5-32A single pole rating 240/415V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 23 | Supply, installation, testing and commissioning of 32 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 24 | Supply, installation, testing and commissioning of 63 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T / eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 25 | Supply, installation, testing and commissioning of 63A TP&N rating 240/ 415V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 26 | Providing / laying of shock proof rubber mat of 2mtr x1 mtr and 12 mm thick. |
| 27 | Providing of chemical earthing as per IS standards by way of digging 8 feet pit then embedding 2.5 mtr. Long GI earthing electrode, 60 mm dia. Connecting the plate with main control board by 10 SWG Copper wire with 1/2” dia. Full thread brass nut and bolts and washers, refilling the pit with chemical compound. |
| 28 | Supply, laying, connecting and commissioning of 70 sq. mm 3.5 core PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade Aluminum (armoured) LT cable , incl. cost of required al. thimbles duly crimped. (over head / under ground). |
| 29 | Supply and fixing of (25 mm dia./ flat batten) medium class PVC conduits along with accessories, surface/ recessed in walls, including cutting of walls and making good the same or fixed with nails/clips or as required. |
| 30 | SITC of wall/free standing floor mounted dust and vermin proof compartmentalized cubical panel for electrical Works, made out of CRCA sheet. Other parameters required as per point(a) Thickness of sheet shall not be less than 1.6 mm up to 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartment shaving bolted type doors with/without detachable extension type structure. (b) Panel shall be duly treated for derusting in 7 tank process with de phosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/Neoprene rubber gasket of not less than 3mm thickness, required hardware, separate detachable gland plate M.S. base channel (min 75mm), hinged door with locking arrangement for equipment/switchgearc) Interconnection between bus bar and switch gears/cable shall be rigidly supported and made out by flexible copper wires (upto 125 amp) and by solid bus bar (> 125).(d) Only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator, CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. |
| 31 | Providing and fixing following rating and breaking capacity and pole MCCB with thermo magnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Thermal Magnetic type, Adjustable type) |
| 32 | Normal Incoming |
| 33 | 250 Amp, 36 KA, FP MCCB |
| 34 | Aluminum Bus Bar 500 Amp set of 4 strips |
| 35 | ON Load Change Over Switch FP 160 amp. (Front operated) |
| 36 | Aluminum Bus Bar 300 Amp set of 4 strips |
| 37 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch,Indicating Lamp, etc. |
| 38 | Outgoing |
| 39 | 63 Amp, TPN MCB 10KA |
| 40 | 63 Amp, 10 KA, DP MCB |
| 41 | Space for 16 way MCBs |
| 42 | Supply, installation, testing and commissioning of 2000-2200VA Power Inverter having generator compatible & provided and fitted with 2 no. 12V, 200 Ah, tall tubular batteries of Exide/ Microtech/ Luminous make and PVC battery trolley for resting of batteries. The job also includes terminal connections of batteries, input/ output leads of required size and length, carriage and applicable taxes. |
| 43 | Supply, installation , testing and commissioning of 3 star rating 1.5 Ton Inverter type split Air Conditioners suitable for operation on AC supply single phase 50Hz 230V with hermetically sealed inverter compressor with air cooled condenser latest R410A/ R-32 refrigerant fan motor, start and run capacitors, relay and over load protector internal unit with one indoor and one outdoor unit. The indoor unit fitted on wall by employing suitable clamps and the outdoor unit will be placed on angle iron stand fitted with nut/bolts outside the room to avoid noise, including standard length of suitable size copper tubing covered with nitrilic foam, topping up with refrigerant for additional length of piping if required, PVC flexible drain pipe, suitable capacity 3 core sheathed/ PVC insulated copper cable and a battery operated wireless remote unit. The job includes repairs to walls wherever the same are cut and the AMC of AC for a period of one and a half year from date of successful commissioning. (Daikin/ Blue Star/ LG). |
| 44 | Supply, installation , testing and commissioning of relay type voltage stabilizer suitable for 2 Ton AC operating from input voltage 90-260Volt thereby producing output voltage of 230volts +_ 3%. (4 KVA) |
| 45 | Supply and installation of 32A modular plug/socket with 32A DP MCB for ACs Please Enable Macros to View BoQ information |