Tender For Providing Additional Fire Detector, Mcp, Hooters Etc. & Integrated With Existing System In The Various Offices/Rooms In Punjab & Haryana High Court Sector 1, Chandigarh Where Detection System Not Installed., Chandigarh-Chandigarh
TDR : 55380693
Tender Notice
BOQ
Expired
Chandigarh
Chandigarh
Tender For Providing Additional Fire Detector, Mcp, Hooters Etc. & Integrated With Existing System In The Various Offices/Rooms In Punjab & Haryana High Court Sector 1, Chandigarh Where Detection System Not Installed.
Name of Work:- PROVIDING ADDITIONAL FIRE DETECTOR, MCP, HOOTERS ETC. & INTEGRATED WITH EXISTING SYSTEM IN THE VARIOUS OFFICES/ROOMS IN PUNJAB & HARYANA HIGH COURT SECTOR 1, CHANDIGARH WHERE DETECTION SYSTEM NOT INSTALLED.
Sl. No.
Item Description
1
DSR Item No.17.2.1 Supplying, installation, testing and commissioning of microprocessor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.
2
Two Loop Panel.
3
DSR 17.2.14 Supplying, installation, testing & commissioning of addressable manual call point complete as required.
4
DSR 17.2.15 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
5
DSR 17.2.4 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required
6
Supply & erection of loop card compatible with existing system. The card should be of Edwards/Honeywell make and match able with the existing panel. The card operating voltage 24 Volt DC and current 139 mili amp. The cost of other petty items required to set right the panels are also included to complete the job to the entire satisfaction of the Engineer-in-Charge.
7
DSR 17.5.2 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
8
DSR 17.2.10. Supplying, installation, testing & commissioning of addressable fire control module complete as required.
9
Supply installation testing & commissioning of LED exit signage: the signage should be made of laser etched acrylic sheet of approx. size 350 x170mm to suit 30m or as per standards, viewing with reflective LED light source of minimum 2 W having battery backup (minimum 2 hours) with battery charger. The assembly should have suitable surface /hanging arrangement including connectors with the help of clutch wire / studs/ Chain etc. for hanging the same. The size of text/ symbol and location for the signage to be approved by the engineer in charge before installation. The job includes all labour & petty material required to complete the job in entire satisfaction of EIC.Make Glowline/ Powertech/Agni make only.
10
Double side Please Enable Macros to View BoQ information