| 1 | SCH 'A' Note: Please refer Schedule 'A' Notes given on serial page No.____ to ____ of tender documents. |
| 2 | Part-I (BUILDING WORKS):'Lump sum price to be worked out by the contractor brought forward from serial page No.31 |
| 3 | Part-II (INTERNAL ELECTRIFICATION):'Lump sum price to be worked out by the contractor brought forward from serial page No. 32&33 |
| 4 | Part-III (INTERNAL WATER SUPPLY):'Lump sum price to be worked out by the contractor brought forward from serial page No. 34 |
| 5 | Part-IV (HOT WATER SUPPLY):'Lump sum price to be worked out by the contractor brought forward from serial page No.35 |
| 6 | Part-V (REFRIGERATOR WATER COOLER):'Lump sum price to be worked out by the contractor brought forward from serial page No. 36 |
| 7 | Part-VI (FALSE CEILING WORK):'Lump sum price to be worked out by the contractor brought forward from serial page No. 37 |
| 8 | Part-VII (ROAD / PATH):'Lump sum price to be worked out by the contractor brought forward from serial page No. 38&39 |
| 9 | Part-VIII (EXTERNAL WATER SUPPLY):'Lump sum price to be worked out by the contractor brought forward from serial page No. 40 |
| 10 | Part-IX (EXTERNAL ELECTRIC SUPPLY):'Lump sum price to be worked out by the contractor brought forward from serial page No. 41,42 &43 |
| 11 | Part-X (SEWAGE DISPOSAL):'Lump sum price to be worked out by the contractor brought forward from serial page No.44 |
| 12 | Part-XI (AREA DRAINAGE):'Lump sum price to be worked out by the contractor brought forward from serial page No. 45 |
| 13 | Part-XII (FENCING AND GATE):'Lump sum price to be worked out by the contractor brought forward from serial page No. 46 |
| 14 | Part-XIII (DG SET):'Lump sum price to be worked out by the contractor brought forward from serial page No.47 |
| 15 | Part-XIV (LIGHTENING PROTECTION):'Lump sum price to be worked out by the contractor brought forward from serial page No. 48 |
| 16 | Part-XV (DEMOLITION AND DISMANTLING):'Lump sum price to be worked out by the contractor brought forward from serial page No. 49 |
| 17 | Part-XVI (SITE CLEARANCE):'Lump sum price to be worked out by the contractor brought forward from serial page No. 50 |
| 18 | SCH 'A' Part-XVII (MISCELLANEOUS ITEMS): Total amount of Sch A Part-XVII (Miscellaneous Items) is not prepriced by MES and the Pre priced rates indicates as ₹ '0.00' under Col 6 signifies this fact only. |
| 19 | Supply , Installation , commencing and testing of of Silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with foundation (as per OEM design), control panel with necessary meter and Weather proof outdoor type silent DG set , sound proof canopy as per CPCB norms of capacity 100 kVA. Technical Specification of DG Set - Electric Generating set placing the engine and A.C. Generator on M.S. frame duly bolted, coupled, aligned, tested and housed within the acoustic enclosure complete with the followings:Prime Power Rating kVA : 100, Voltage - 415, No. of phases : 3, Power Factor : 0.8, BHP not less than 138 BHP, water cooled, Aspiration Turbo charged after cooled, No. of Cylinders 4/6, RPM 1500, Fuel Diesel, Starting System 12V DC Battery.(a) Engine: 4/6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with A1 class mechanical governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 12 V DC battery.(b) Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength(c) ACCESSORIES: Base Frame : The Diesel Engine and the A. C. Generator will be mounted on a suitable base frame of sturdy to minimize vibration and ensure easy maintenance.Fuel Tank : Daily service fuel tank of sheet metal of suitable capacity complete with drain valve, air vents inlet and outlet connection as per OEM.Batteries : Battery (Dry and uncharged) of suitable Amp-Hr capacity along with leads for connection as per OEM Recommendation. |
| 20 | (c) Control Panel: Manually operated Standard Alternator Control Panel fabricated out of sheet steel angle, iron, structure, acid treated for anti-corrosion, floor mounting, cubicle pattern, powder coated dust and, vermin proof, complete with internal wiring and with the followings as per OEM Recommendation:(i) Powder coated control panel manufactured with CRCA sheet provides:(ii) MCCB of suitable rating with short circuit protection(iii) Controller which displays voltage, current, KW, PF, Frequency, KWh.(iv) Indicating lamps for “Load On” and “Set Running”(v) Current transformers of suitable ratings(vi) Copper Cables of suitable capacity with incoming and Outgoing terminations(vii) Control fuses duly wired and ferruledTechnical Specification of Acoustic Enclosure(d) Salient Features:(i) Approved by ARAI, the nodal agency of CPCB (ii) Compact, modular construction and sleek design with low noise level 75 dBA, at a distance of 1 Meter from Canopy in free field conditions.(ii) Soundproof, weather-proof and environment friendly silent set.(ii) Ready-to-use silent DG Set, which eliminates need of foundation or grouting.(iv) Single bearing generator with Anti vibration mounting ensures minimal vibration(v) Steel outer construction with 1.6mm CRCA sheet with heavy-duty fabricated base frame and inbuilt fuel tank.(vi) Attenuators are placed in the hot air outlet and cooling air inlet.(vii) Residential type exhaust silencer is mounted on the enclosure.(viii) Illumination arrangement inside the canopy.(ix) Retrofit emission control device at exhaust of DG Set(x) Cold Start Kit |
| 21 | (e) Foundation: DG Set shall be installed on new foundation block as per manufaturers recommendations including excavation works PCC etc for foundations, provision of cable ducts, making good any demage to existing structure, fuel piping from tank to generator set with medium grade GI tubing and cold water piping system (medium grade GI tubing from nearest water point to radiator of engine with brass tap and stop cocks and fittings complete connecting the existing earth strips to control panel, DG st and generator. (f) Terms and Condition :- Warranty - (for DG Set) : warranty is for 2 years from the date of supply or the completion of 5000 Hrs. Which is earlier, subject to the use of genuine parts and recommended lube oil and coolant maintainance by authorised person / dealer only. |
| 22 | Design,Supply, installation, testing and commissioning of Cubical type floor mounted LT panel, minimum size 1.00x1.00x.30M depth, outdoor type factory fabricated made out of CRCA sheet of 3.15 mm thick ,fully enclosed and angle iron frame of size 40 x 40 x 6mm thick and T section with front openable double door shutter, dust and vermin proof and rear opening complete with locking arrangement, having a system of bus bars of aluminium of suitable size of 300 Amps duly insulated and mounted on Epoxy/porcelain insulators in totally enclosed chamber with three phase and neutral 415 volts, AC, system prewired with suitable copper wire PVC insulated with all control accessories, provn of suitable cable glands, duly powder coated of approved quality over a coat of red primer with sufficient free space complete to include the following accessories:- (a) 4 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 35 KA (Incommer)(b) 4 Pole MCCB 63 Amp, 50 Hz, 415 V with rupturing capacity 25 KA. (Outgoing)(c) 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 35 KA (Outgoing) = 2 nos (1 spare and 1 (outgoing)(d) Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 200 Amps(e) Digital volt meter 0 to 500 volts with selector switch-1 No (f) Digital Ammeter 0 to 350 Amps with CTs of suitable Amps and selector switch-1 No(g) Indicator lamp RYB- 01 Set |
| 23 | Design, supply, installation, testing & commissioning of Centralised AC Plan of capacity 60 TR or more based on final design (to be devided in 03 units, 02 Units as maint/working and one unit as standby) Complete in all respects including AHU’s, water pump set, Cooling towers, ducting, Humidity Control System, Electrical connections including panels suitable for 03 phase AC supply, chilled water system, Hot water system etc, to achieve temp 22°C ± 2°C and RH 65 % ± 5% for 24 hour operation and 25% fresh air requirement including Fire dampers and other parameter as specified in user data sheet.Fwg Planning Notes to be considered :-1.1. Above requirement of Air Conditionig is for a underground bldg (only 1m above NGL) PA of UG Bldg = 366.15 Sqm1.2. A Seprate AC Plant room (Plinth Area 98.60) shall be located near the Maint UG Bldg. AC Plant room is above ground. All connected accessories of centralized AC shall be housed in this AC Plant room.1.3. Design Part : (To be completed within 45 days date after finalization of order).1.3.1. We shall first submit a DPR of the centralized AC Plant complete in all respect of design & specification. DPR shall be duly vetted by IIT/NITand not by any individual Professor in personal capacity.Scope of DPR shall cover, but not limited to, fwg:-1.3.1.1 Heat load & ACH Calculation.1.3.1.2. AHU & air flow selection.1.3.1.3. Duct design & layout drawing.1.3.1.4. Chiller requirement & pipe sizing.1.3.1.5. Hot water generator requirement & pipe sizing.1.3.1.6. BoQ & Tech specification.1.3.1.7. Any other drg/ details required during execution of wk.1.4. Approval of DPR from Accepting officer:-1.4.1. Post submission of vetted DPR, same shall be approved by accepting officer.1.5. Execution Part :- (To be completed within completion date of Main Tender).1.5.1. Post approval of DPR, we shall supply & install the centralized AC Plant to full satisfaction of MES as per approved DPR.1.5.2. Testing & commissioning of centralized AC Plant shall be done as per your requirement. |
| 24 | Supply & fixing modular blank plate single module all as specified and directed. |
| 25 | Supply and fix LED bulb 9 watts, 240Volts,50Hz pin type and including removing old unserviceable item complete all as specified and directed. Make:- Havells or equivallent. |
| 26 | Supply and fix wall mounted fan 400 mm sweep along with speed control complete with all accessories incl mounting on wall with necessary arrangemets complete all as specified and directed. |
| 27 | Supply and fixing Vertical type sheet metal enclosure DB TPN 4 way double door made powder coated out of CRCA mild steel sheet 1.6 mm thick 415 volts 200 amps rated fitted bus bar dust and vermin proof suitable for incorporation of MCCB as incomer and MCBs as out going duly concealed on wall and making good the disturbed surface including MCCB, four pole, 100 Amps, 415 volts, 50 Hz,16KA complete all as specified and directed. |
| 28 | Supply and fix refrigerator, electric driven (single phase), capacity more than 195 ltrs upto 310 Litres, BEE 5 star rated complete all as specified and directed by Engr-in-Charge. |
| 29 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 1 KVA complete all as specified and directed by Engr-in-Charge. |
| 30 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2 KVA complete all as specified and directed by Engr-in-Charge. |
| 31 | M&L of valve pit chamber of size 600x600x600 mm (internal dimentions) including brick masonary, rendering in 15mm thick cement mortar 1:4 on internal and external surfaces and white washing with two coats of lime wash including paintig with two coats of black colour synthetic enamel paint to mild steel top cover surfaces and angle iron frame work with MS Sheet of thickness 3mm with hinges, handles and suitable locking arrangements, fastening arrangements, nuts, bolts and washers complete all as specified and directed |
| 32 | M&L for Construction of septic tank for 50 users, including inlet and outlet chamber, incl excavation in any type of soil, including plain cement concrete M-15(1:2:4) as in base/ foundation, type B-2 (using 40mm graded crushed stone aggregates), brick work with sub-class 'B' bricks, straight or curved on plan exc 6m mean radius built in cement mortar 1:4 and reinforced cement concrete cover slab in M-30 Design Mix,incl all form work, including RCC precast manhole covers steel fiber reinforced cover with angle iron frame and provision of vent shaft and sludge chamber etc., complete all as specified and as shown on drawing.Drawing No- CEUZ/TD-1585/2021 |
| 33 | M&L for construction of Soakage well of size 2.8 M dia X 4.0 M effective depth incl excavation in any type of soil, foundation in PCC 1:4:8, brick work with sub-class 'B' bricks, straight or curved on plan to any radius built in In cement mortar 1:4 and walls of honey combed masonry in CM 1:4 depth as per drawing including intercepting chamber and screen chamber made of Brick masonry in CM 1:4, RCC cover slab in M-30, complete filled with brick bats complete all as specified and shown on drawing.Drawing No- CEUZ/TD-1585/2021 |
| 34 | Note:- Deduction for Schedule of credit (Sch 'A' Part-II) to be made of ₹ 8370.00 from the total quoted amount of BOQ while accepting the bid. Details of schedule of credit is given in tender documents. Please Enable Macros to View BoQ information |