| 1 | Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of following sizes in trenches/ poles/ passing through GI Pipe all as specified and directed by Engr-in-Charge.Note: Excavation, returning filling and removal required for the work shall be measured and paid separately. |
| 2 | (a) 185 Sqmm 3.5 core |
| 3 | (b) 150 Sqmm 3.5 Core |
| 4 | (c) 120 Sqmm 3.5 core |
| 5 | (d) 95 Sqmm 3.5 core |
| 6 | (b) 70 sqmm 3.5 core |
| 7 | (b) 50 sqmm 3.5 core |
| 8 | (c) 35 sqmm 3.5 core |
| 9 | (c) 25 sqmm 4 core |
| 10 | (c) 16 sqmm 4 core |
| 11 | (c) 10 sqmm 4 core |
| 12 | (c) 10 sqmm 2 core |
| 13 | M&L Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia (THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvanised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Crystalline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg Backfill compound to provide maximum contact between the electrode and Back Fill Compound. The earthing pit should be cover with PCC (1:2:4, B1) cover, of 450 x 450 mm complete all as specified and directed. Make ASHLOK / INDELEC/JMV /TERCEL/True Power. |
| 14 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 15 | (a) MCCB 4 Pole 250 Amps 25KA -01 No. Thermal Magnetic release (incomer)(b) MCCB 4 Pole 160 Amps 16KA -02 Nos. (Outgoing)(c) MCCB 4 Pole 100 Amps 16KA -03 Nos. (Outgoing)(d) MCCB 4 Pole 63 Amps 16KA -01 Nos. (Outgoing)(e) MCCB 4 Pole 40 Amps 16KA -01 Nos. (Outgoing)(f) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(g) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 16 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 17 | (a) MCCB 4 Pole 100 Amps 16KA -01 No. (incomer)(b) MCCB 4 Pole 63 Amps 16KA -01 Nos. (Outgoing)(c) MCCB 4 Pole 40 Amps 16KA -01 Nos. (Outgoing)(d) MCB DP 32 Amp C curve 10 KA - 03 Nos (Outgoing)(e) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(f) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 18 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 19 | (a) MCCB 4 Pole 200 Amps 16KA -01 No. (incomer)(b) MCCB 4 Pole 160 Amps 16KA -01 Nos. (Outgoing)(c) MCCB 4 pole 100 Amps 16 KA-01 Nos (Outgoing)(d) MCCB 4 pole 63 Amps 16 KA-01 Nos (Outgoing)(e) MCCB 4 Pole 40 Amps 16KA -01 Nos. (Outgoing)(f) MCB DP 32 Amp C curve 10 KA - 03 Nos (Outgoing)(g) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(h) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 20 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 21 | (a) MCCB 4 Pole 100 Amps 16KA -01 No. (incomer)(b) MCB 3 Pole 32 Amps 10KA C Curve -01 Nos. (Outgoing)(c) MCB 4 Pole 40 Amps 10KA C Curve -01 Nos. (Outgoing)(d) MCB 4 Pole 32 Amps 10KA C Curve -02 Nos. (Outgoing)(e) MCB 4 Pole 63 Amps 10KA C Curve -02 Nos. (Outgoing)(f) MCB DP 32 Amp C curve 10 KA - 03 Nos (Outgoing)(g) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(h) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a)All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item..(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 22 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 23 | (a) MCCB 4 Pole 200 Amps 16KA -01 No. (incomer)(b) MCCB 4 Pole 160 Amps 16KA -01 Nos. (Outgoing)(c) MCCB 4 pole 100 Amps 16 KA-01 Nos (Outgoing)(d) MCCB 4 pole 63 Amps 16 KA-01 Nos (Outgoing)(e) MCCB 4 Pole 40 Amps 16KA -03 Nos. (Outgoing)(f) MCB DP 32 Amp C curve 10 KA - 04 Nos (Outgoing)(g) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(h) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a)All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item..(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 24 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 25 | (a) MCCB 4 Pole 160 Amps 16KA -01 No. (incomer)(b) MCCB 4 Pole 100 Amps 16KA -01 Nos. (Outgoing)(c) MCCB 4 pole 63 Amps 16 KA-02 Nos (Outgoing)(d) MCCB 4 Pole 40 Amps 16KA -01 Nos. (Outgoing)(e) MCB DP 32 Amp C curve 10 KA - 02 Nos (Outgoing)(f) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(g) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 26 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 27 | (a) MCCB 4 Pole 100 Amps 16KA -01 No. (incomer)(b) MCCB 4 pole 63 Amps 16 KA-02 Nos (Outgoing)(c) MCCB 4 Pole 40 Amps 16KA -01 Nos. (Outgoing)(d) MCB DP 32 Amp C curve 10 KA - 02 Nos (Outgoing)(e) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(f) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 28 | Supply and install, testing and commissioning Out door LT feeder panel factory made cubicle type of suitable size and 3.15 mm thick CRCA sheet outdoor type vermin proof with Aluminium bus bar of suitable size as per rating of MCCB Al strip 3 phase and neutral connections with neutral colour coded with heat and shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, locking arrangements and painted with one coat of red oxide primer and two coats of powder coated paint with suitable size of panel control copper wiring, accessories are fitted on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands incl PCC foundation etc complete testing and commissioning complete and consisting the following :- |
| 29 | (a) MCCB 4 Pole 250 Amps 16KA -01 No. (incomer)(b) MCCB 4 pole 100 Amps 16 KA-01 Nos (Outgoing)(b) MCCB 4 pole 63 Amps 16 KA-05 Nos (Outgoing)(c) MCCB 4 Pole 40 Amps 16KA -03 Nos. (Outgoing)(d) MCB DP 32 Amp C curve 10 KA - 02 Nos (Outgoing)(e) Digital multimeter operated on 400/5A LT-CT operated complete - 01 No(f) Indicating type lamp for Red, Yellow and Blue phases - 01 SetNote : (a)All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item..(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces |
| 30 | Supply and fixing automatic street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off > 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor along with suitable power contactors incoming outgoing MCBS SP and automanual (sensor bypass selection option should be enclosed in a pole /wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 three phase load of 8 KW with circuit wiring min 6 sq mm, 3 nos contactor each of 20 amps, incoming outgoing MCB (3 nos) rating 20 amps of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt(4 nos) for fixing on pole / wall complete all as directed including taking down old one Model no Swadeep-02 EC 8KW 3P or equivalent from Havells/Legrand . |
| 31 | Cutting the existing PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil up to 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed. |
| 32 | S&F hot press moulded SMC junction/terminal box of size with internal dimensions of 200 x 140 x 95 mm with hinged door, incl provision of 4 way connector 415 Volts made out of polycarbonate or Bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/glands, fixed on pole by means of clamps made out of MS flat iron of size 25mm x 3 mm 2 Set including dismantling of old unserviceable all as specified and as directed. Make : Syntex/C&S/Havells. |
| 33 | S&F 1.5 sqmm 3 core copper conductor cable for street lights complete all as specified and directed. |
| 34 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure |
| 35 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/ dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed by Engr-in-Charge. |
| 36 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed. |
| 37 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. Please Enable Macros to View BoQ information |
| 38 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. Please Enable Macros to View BoQ information |