| 1 | Taking down carefully copper/aluminium point wiring complete alongwith switch board, casing patti/ PVC conduit removing materials to store and making good to disturb surfaces of wall/floors etc as specified & directed. |
| 2 | M&L for Point wiring with 1.5 Sqmm (22/0.30mm) PVC insulated and unsheathed multistranded copper conductor cable, 1100 Volts grade, ISI marked, FRLS type drawn through and including PVC concealed conduit (ISI marked) of adequate size and its accessories with sunk cast iron/pressed steel terminal boxes of size 1.2mm thick, with 3mm thick plastic laminated sheet cover of adequate size for one light or one fan point controlled by one switch incl 1.5 Sqmm (nominal area) copper conductor cable (multistrand), FRLS type, PVC insulated and unsheathed with colour code earth wire connected to common earth dolly at one end and metalic bodies of luminaires/ fan at other end complete all as specified and directed for One light point/ fan point controlled by one, one way swtich.Note:- Unit rate quoted inclusive for cutting chases for conduits and sinking for boxes and making good to wall, floors etc. |
| 3 | All as per ser item No. 2.00 herein before but One 5 Amp 5 pin socket outlet point on same board with other switches including earth wire as specified. |
| 4 | All as per ser item No. 2.00 herein before but with 4.0 Sqmm (36/0.30mm) PVC copper stranded cable FRLS type for one 15 Amp 6 pin socket outlet point including PVC cable 4 Sqmm FRLS type copper stranded conductor as earth wire as specified & connected to commen earth & earth terminals including boards for mounting purposes. |
| 5 | All as per ser item No. 2.00 herein before but on independent board. |
| 6 | All as per ser item No. 2.00 herein before but one light point controlled by 2 way switches. |
| 7 | All as per ser item No. 2.00 herein before but one bell/buzzer point controlled by one push button on independent roard. |
| 8 | M&L Point wiring with 1.5 Sqmm (22/0.30mm) PVC insulated and unsheathed multistranded copper conductor cable, 1100 Volts grade, ISI marked, FRLS type drawn through and including PVC casing and caping (ISI marked) of adequate size and its accessories with PVC boxes, frames for modular fixtures of adequate size, for one light or one fan point controlled by one switch incl 1.5 Sqmm (nominal area) copper conductor cable (multistrand), FRLS type, PVC insulated and unsheathed with colour code earth wire connected to common earth dolly at one end and metalic bodies of luminaires/ fan at other end complete all as specified and directed for One light point and one fan point controlled by one, one way swtich. |
| 9 | All as per ser item No. 8.00 herein before but One 5 Amp 5 pin socket outlet point on same board with other switches including earth wire as specified. |
| 10 | All as per ser item No. 8.00 here in before but on independent board. |
| 11 | All as per ser item No. 8.00 here in before but one light point controlled by 2 way switches. |
| 12 | All as per ser item No. 8.00 here in before but one bell/buzzer point controlled by one push button on independent board. |
| 13 | All as per item No. 8.00 here in before but with 2.5 Sqmm (36/0.30mm) PVC copper stranded cable FRLS type for one 15 Amp 6 pin socket outlet point including PVC cable 2.5 Sqmm FRLS type copper stranded conductor as earth wire as specified & connected to commen earth & earth terminals including fibre insulation boards, treated on one face only of adequate size for mounting purposes. |
| 14 | S&F switch modular type 6 Amps one way, 1 module, AC 230 Volts, shrouded terminal, ISI marked complete all as specified and directed. |
| 15 | S&F socket modular type 6 Amps, 3 pin round socket with child safety shutter (ISI marke), AC 230 Volts, shrouded terminals, smooth plug removal and insertion complete all as specified and directed. |
| 16 | S&F switch modular type 16 Amps one way, 1 module, AC 230 Volts, LED based indicator, shrouded terminal, ISI marked complete all as specified and directed. |
| 17 | S&F mini MCB modular type 20 Amp, SP C Curve, AC 230 Volts, laser marking, ISI marked complete all as specified and directed. . |
| 18 | S&F socket modular type 6 / 16 Amp, 3 pin socket with child safety shutter (ISI marke), AC 230 Volts, shrouded terminals, smooth plug removal and insertion complete all as specified and directed. |
| 19 | S&F bell push modular type 6 Amps, AC 230 Volts, LED based indicator, shrouded terminal, ISI marked complete all as specified and directed. |
| 20 | S&F switch modular 6 Amps two way, 1 module, AC 230 Volts, LED based indicator, shrouded terminal, ISI marked complete all as specified and directed. |
| 21 | S&F fan regulator modular type 8 step, 100 Watt, AC 230 Volts, 2 module, laser marking complete all as specified and directed. . |
| 22 | S&F telephone socket modular type RJ 11 with Shutter 1 module, laser marking complete all as specified and directed. . |
| 23 | S&F TV socket, modular type, 1 module complete all as specified and directed. |
| 24 | S&F in repair switch piano flush button 5 Amp single pole one way 230 Volts white finish all as specified & directed. |
| 25 | S&F in repair socket outlet flush type 3 pin 5 Amp multipurpose 230 Volts single pole one way suitable for 3 pin, 5 Amp plug top white/ivory finish all as specified & directed. |
| 26 | S&F in repair switch socket combination flush type 5 pin 5 Amp multipurpose 230 Volts single pole one way suitable for 3 pin/2pin 5 Amp plug top white/ivory finish all as specified & directed. |
| 27 | S&F in repair switch socket combination multipurpose flush type 2 in 1 type (3 and 3 pin) 5/15 Amps, 230V, AC. |
| 28 | S&F in repair bell push, flush type, 5 Amp single pole, 230 Volts white finish all as specified & directed. |
| 29 | S&F in repair switch piano flush button 5 Amp single pole 2 way 230 Volts white finish all as specified & directed. |
| 30 | M&L in repair fan regulator electronic dimmer type 230 Volts, 450 Watts on existing phenolic laminated sheet suitable for ceiling fan 1200/1400mm sweep. |
| 31 | S&F in repair lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings with invertor LED bulb 9 Watt complete all as specified and directed |
| 32 | S&F in repair ceiling rose surface PVC 50mm dia 3 terminals including PVC mounting block white/ivory finish. |
| 33 | S&F in repair buzzer, AC, 230 Volts, single phase complete all as specified and directed. |
| 34 | S&F in repair bell, AC, 230 Volts, single phase complete all as specified and directed. |
| 35 | S&F in repair LED 20 Watt inverter batten with rod complete with lithium ion battery with charging time 8-10 hours and backup time upto 4 hours connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 36 | S&F in repair LED 20 Watt plastic batten with white acrylic cover sleek design complete with connectors and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 37 | S&F in repair 30 Watt LED security light fitting luminaire, energy saving and environmental friendly long life LED light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having bottom opening seperate driver compartment with IP66 protection and impact resistance of IK08, including provision of 40 mm dia 1.2 rm GI pipe bracket with GI clamps, nut and bolt and connecting up with 2/3 core flexible coppper conductor cable complete all as specified and directed. |
| 38 | S&F in repair of LED luminaire 600x600mm, 36 Watt, 220 Volts AC recessed/ surface type fittings, IP 20 with epoxy powder coated CRCA sheet housing with electronic driver, connector block, etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 39 | S&F in repair of LED round shape 15 Watt 220 Volts AC recessed/surface type with high efficacy PMMA diffuser soft glare free light complete with drivers, clamps and suitable size as per ground requirement complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 40 | S&F in repair invertor LED bulkhead 10 Watt 220 Volts AC with high efficacy PMMA diffuser soft glare free light complete with drivers, clamps, accessories, internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 41 | S&F in repair LED table lamp 6 Watt 220 Volts AC with high efficacy PMMA diffuser soft glare free light complete with drivers, accessories, internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 42 | S&F Decorative wall light fitting made up of polycarbonate and aluminium body suitable for and including 10 Watt LED lamp complete all as specified and directed. |
| 43 | S&F in repair LED square shape 15 Watt, 220 Volts AC recessed/ surface type with high efficacy PMMA diffuser soft glare free light complete with drivers, clamps and suitable size as per ground requirement including all accessories internally pre-wired and connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 44 | Supply only Decorative LED post top lantern, high PF, 40 Watt, energy saving and environmental friendly long life versatile pressure die cast aluminium housing, 360 degree indirect light, optimum light output, IP 65 protection, glare-free and better uniformty, 240 Volts complete all as specified and directed. |
| 45 | S&F in repair sheet metal enclosures with plug socket single pole and neutral with two pin and earth plug and with one MCB of 20 Amps (SP) complete all as specified. |
| 46 | S&F in repair submain wiring with four single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts grade, FRLS type, cables 10 Sqmm drawn through in and including PVC heavy duty surface casing caping including 10 Sqmm 1100 Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. |
| 47 | S&F in repair submain wiring with four single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts, FRLS, 10 Sqmm drawn through in and including PVC heavy duty concealed conduit including 10 Sqmm 1100 Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. |
| 48 | S&F in repair submain wiring with four single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts, FRLS, 6 Sqmm, drawn through in and including PVC heavy duty surface casing caping 6 Sqmm 1100 Volts grade, FRLS, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note for item Sl No 46 to 48 :- (i) Four runs of cables and one run of earting cable will be measured as one length of sub main. (ii) PVC casing caping / PVC conduit and its accessories is deem to be included in the item rates quoted.(iii) Unit rate include for cutting, chases for sinking for boxes and making good to wall, floors etc. |
| 49 | S&F in repair of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts grade, FRLS, 6 Sqmm drawn through in and including PVC heavy duty surface casing caping including 6 Sqmm 1100 Volts, FRLS, PVC insulated unsheathed multi stranded flexible copper conductor as continuous earth wire and connecting to common earth terminals complete all as specified and directed. |
| 50 | S&F in repair of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts, FRLS, 4 Sqmm drawn through in and including PVC heavy duty surface casing caping including 4 Sqmm 1100 Volts, FRLS, PVC insulated unsheathed multi stranded flexible copper conductor as continuous earth wire and connecting to common earth terminals complete all as specified and directed. |
| 51 | S&F in repair submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts, FRLS, 4 Sqmm drawn through in and including PVC heavy duty concealed conduit including 4 Sqmm 1100 Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. |
| 52 | S&F in repair of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100 Volts, FRLS, 2.5 Sqmm drawn through in and including PVC heavy duty surface casing caping including 2.5 Sqmm 1100 Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note for Srl item No 49 to 52 :- (i) Two runs of cables and one run of continuous earting cable will be measured as one length of sub main. (ii) PVC casing caping and its accessories is deem to be included in the item rate quoted.(iii) Unit rate include for cutting chases for sinking for boxes and making good to wall, floors etc. |
| 53 | S&F in repair distribution Board, TPN Vertical (MCCB Incomer) IP43 protection Double Door, 4 way, mechanical impact strength IK 09, suitable for MCCB upto 125 Amps as incomer (frame 1) with 200 Amps rated busbar all as specified and directed. |
| 54 | S&F in repair distribution Board, TPN Vertical (MCCB Incomer) IP43 protection Double Door, 8 way, mechanical impact strength IK 09, suitable for MCCB upto 125 Amps as Incomer (frame 1) with 200 Amps rated busbar all as specified and directed. |
| 55 | S&F in repair distribution board sheet metal enlosure double door shutter type factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 415 Volts, 200 Amp rated bus bar with front openable cover suitable for TPN 4 ways all as specified & directed. |
| 56 | S&F in repair of sheet metal enclosures with plug socket triple pole and earth enclosure with three pin and earth plug with socket, 415 Volts complete with one MCB 63 Amps TP complete all as specified. |
| 57 | S&F in repair distribution board sheet metal enlosure double door shutter, factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 240 Volts, 200 Amp rated bus bar with front openable cover suitable for SPN 4 ways all as specified & directed. |
| 58 | S&F in repair distribution board sheet metal enlosure double door shutter, factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 240 Volts, 200 Amp rated bus bar with front openable cover suitable for SPN 8 ways all as specified & directed. |
| 59 | S&F in repair distribution board sheet metal enlosure double door shutter, factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 240 Volts, 200 Amp rated bus bar with front openable cover suitable for SPN 12 ways all as specified & directed. |
| 60 | S&F in repair 4 Pole MCCB 125 Amp, 50 Hz, 415 V, with adjustable thermal & adjustable magnetic setting, breaking capacity 25 kA. |
| 61 | S&F in repair MCCB 63 Amp TP, 415 Volts 16 kA complete all as specified & directed. |
| 62 | S&F in repair MCB FP 63 Amp, 415 Volts, 50 Hz with 10 kA complete all as specified & directed. |
| 63 | S&F in repair MCB TP 40 Amp, 415 Volts, 50 Hz with 10 kA complete all as specified & directed. |
| 64 | S&F in repair MCB DP/SPN 6-32 Amps, 230 Volts, 50 Hz with 10 kA complete all as specified & directed. |
| 65 | S&F in repair MCB SP 6-32 Amps, 230 Volts, 50 Hz with 10 kA complete all as specified & directed. |
| 66 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of earth plate not less than 1.5 m below normal ground level connected to and including galvanised earth lead wire of 4.00mm dia by means of nuts & bolts, check nuts and washers of galvanised incl PCC 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 kg/Sqm and 6mm dia bar handle, earth pit angle iron frame of size 25x 25mm, excavation and earth work in any type of soil, charcoal dust, salt, light grade GI watering pipe 20mm dia with funnel and wire -mesh and medium grade GI protection pipe of 15mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical Plate No 3 of MES Sch 2009 (Part I) connected main switch board all as specified and testing on completion. |
| 67 | NOTE :- AMOUNT OF SCHEDULE OF CREDIT Rs. 1,26,357.00 WILL BE DEDUCTED FROM TOTAL AMOUNT OF BOQ. Please Enable Macros to View BoQ information |