| 1 | Annexure-A (Supply of following material as per UPCL Norms.) |
| 2 | Supply of cross arm holding clamps for PCC poles without nuts and bolts (w/o N&B), fabricated from suitable MS steel, complete as per approved drawings and UPCL specifications. |
| 3 | Supply of holding clamps for PCC poles, fabricated from suitable MS steel, complete with nuts, bolts, washers, and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 4 | Supply of F-Clamps for PCC poles, fabricated from suitable MS steel, complete with nuts, bolts, washers, and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 5 | Supply of LT clamps for PCC poles, fabricated from suitable MS steel, complete with nuts, bolts, washers, and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 6 | Supply of Suspension Clamp with Eye Hook suitable for LT/HT overhead lines/AB cable, made of suitable material (MS/Aluminium alloy as applicable), complete with eye hook, nuts, bolts, washers and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 7 | Supply of MS clamp suitable for SP-33 pole structure for fixing of suspension clamp, fabricated from suitable mild steel, complete with nuts, bolts, washers and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 8 | Supply of stay clamp for PCC poles, fabricated from suitable mild steel (MS), complete with nuts, bolts, washers and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 9 | Supply of Dead End Clamp with Eye Hook suitable for LT/HT overhead line/AB cable, made of suitable material (MS/Aluminium alloy as applicable), complete with eye hook, nuts, bolts, washers and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 10 | Supply of shackle insulator (porcelain/polymer) suitable for LT overhead lines, complete with GI strap, nuts, bolts, washers and all necessary accessories, conforming to relevant IS standards and UPCL specifications. |
| 11 | Supply of HT stay insulator (porcelain) suitable for 11 kV overhead line stay sets, conforming to relevant IS standards, complete with proper glazing, high mechanical strength, and compatible with stay wire arrangement as per approved drawings and UPCL specifications. |
| 12 | Supply of Shear Head Type Insulated Piercing Connector (IPC) suitable for 95 sq.mm AB cable, complete with shear head bolts, insulation piercing teeth, weatherproof body, and all necessary accessories, conforming to relevant IS/IEC standards and UPCL specifications. |
| 13 | Supply of MS bolts and nuts of required sizes (with washers), complete, conforming to relevant IS standards and UPCL specifications. |
| 14 | Supply of LT AB Cable 3x70+1x50sq.mm. |
| 15 | Supply of LT Distribution Box, Three Phase, made of SMC/FRP/metallic enclosure with inbuilt panel lock, complete with Aluminium (Al) bus bars (RYB), suitable for 415 V LT system, including all internal components, terminals, and accessories, conforming to approved drawings, relevant IS standards and UPCL specifications. |
| 16 | Supply of Aluminium Crimping Type Lugs suitable for 95 sq.mm conductor, complete with proper palm, barrel, and suitable for crimping connection, conforming to relevant IS standards and UPCL specifications. |
| 17 | Supply of Aluminium Crimping Type Lugs suitable for 25 sq.mm conductor, complete with proper palm and barrel, suitable for crimping connection, conforming to relevant IS standards and UPCL specifications. |
| 18 | Supply of LT PG (Parallel Groove) Clamp suitable for bare neutral conductor, made of aluminium alloy, complete with bolts, nuts, washers and all necessary accessories, suitable for proper electrical connection, conforming to relevant IS standards and UPCL specifications. |
| 19 | Supply of MS Half Clamp suitable for fixing of LT Distribution Box on PCC pole, fabricated from suitable mild steel, complete with nuts, bolts, washers and all necessary accessories, conforming to approved drawings and UPCL specifications. |
| 20 | Annexure-B (Following work as per UPCL norms) |
| 21 | Chemical Earthing – Earthing of distribution transformer including excavation of pit up to 2.5 m depth and boring of hole of 150 mm diameter. Placing of earthing electrode (to be supplied by the contractor) as per Drawing No. A/B, and connecting the same with G.I. strip (to be supplied by the contractor) of size 35×6 mm for a minimum length of 6 m as per Drawing C. Treatment of soil with highly conductive compound as per IS 30343, complete in all respects. The earth resistance shall be measured and recorded in the Measurement Book before and after installation of earthing. The earth resistance after installation shall be less than 1 Ohm. |
| 22 | Erection of M.S. Earthing Rod of size 20 mm dia × 2500 mm length for earthing of supports as per RESPO Drawing No. RES-12, including driving the earth rod 2.5 m deep below ground level, and connecting the same to the support with G.I. earthing strip/wire complete with nuts, bolts, washers, and all associated works, as per specifications and direction of Engineer-in-Charge. |
| 23 | Fabrication and fixing of structural steel work for Double Pole structure using channel of size 125 × 65 mm, including cutting, drilling of holes, welding, and fabrication as required, complete with supply and fixing of clamps, nuts, bolts, washers, and all associated materials. The work includes proper alignment, erection, and fixing on pole as per approved drawings and specifications and direction of Engineer-in-Charge. |
| 24 | Providing and laying cement concrete for grouting of stay block of size 0.60 m × 0.60 m × 0.30 m in CC (1:4:8) using 20 mm nominal size graded stone aggregate and coarse sand, including cost of cement, sand, stone ballast, mixing, placing, compacting, curing, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 25 | Charges for erection of PCC pole 8.5 m long (180 kg working load) for reducing span of LT/ABC line, including excavation of pit of size 0.60 m × 0.90 m × 2.15 m, erection and proper alignment of pole, fixing of all accessories, backfilling with suitable soil and boulders, ramming and dressing of pit, and providing earthing, complete in all respects as per RESPO specifications and direction of Engineer-in-Charge. |
| 26 | Erection of STP SP-33 Single Pole including digging of pit size 0.6X0.6X1.8 M , grouting, stone pad and making kiciking block in E&B ,fixing of all accessories upto energisation.. |
| 27 | Erection of STP SP-55 Single Pole including excavation of pit of size 0.60 m × 0.60 m × 1.80 m, grouting, providing and placing of stone pad, construction of kicking block in earth & boulder (E&B), erection and proper alignment of pole, fixing of all accessories, and completion of all works up to energisation, as per RESPO specifications and direction of Engineer-in-Charge. |
| 28 | Erection of STP SP-33 Double Pole structure including excavation of pits of size 0.60 m × 0.60 m × 1.80 m for each pole, grouting, providing and placing of stone pads, construction of kicking blocks in earth & boulder (E&B), erection and proper alignment of both poles, fixing of all accessories including cross-arms, bracings, clamps, nuts and bolts, and completion of all works up to energisation, as per RESPO specifications and direction of Engineer-in-Charge. |
| 29 | Grouting and erection of pole including excavation of pit of size 0.60 m × 0.60 m × 1.80 m, providing and placing of stone pad, construction of kicking block in earth & boulder (E&B), proper alignment and erection of pole, grouting, fixing of all accessories, backfilling with suitable soil/boulders, ramming and dressing of pit, and completion of all works up to energisation, as per RESPO specifications and direction of Engineer-in-Charge. |
| 30 | Providing and laying cement concrete muffing around pole of size 0.45 m × 0.60 m (average radius/section) up to 0.45 m height above ground level, in CC (1:3:6) using 10 mm nominal size graded stone aggregate and coarse sand, including cost of cement, sand and stone aggregate, centering (if required), mixing, placing, compaction, curing, finishing, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 31 | Painting of poles STP SP 33 with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of Aluminum Paint and two strip of fluorescent alternate Red and White paint 30 Cm wide upto 1.5 Mtrs. from ground level. |
| 32 | Installation of 63 kVA Distribution Transformer (DTR) on pole mounted structure, including erection of transformer on double pole structure, fixing of all accessories such as mounting channels/clamps, LT distribution box, HT/LT insulators, jumpers, connections, earthing, and all associated works complete up to commissioning/energisation, as per RESPO specifications and direction of Engineer-in-Charge. |
| 33 | Laying, stringing and sagging of Weasel conductor for HT overhead line, including binding on insulators, jointing, tightening, proper sagging as per standard charts, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 34 | Lopping and chopping of tree branches for maintaining required ground/root clearance along LT/HT overhead lines, including cutting, trimming, removal and safe disposal of branches, ensuring statutory electrical safety clearances, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 35 | T-Off Connection Complete 11 KV Line as per Direction of Engineer Incharge |
| 36 | Cartage of PCC Pole 8.5 mtr long from store center to nearest road side with loading unloading at both points. Loading unloading plus carriage per pole 21-50km |
| 37 | Cartage for SP-33 Pole 8.5 mtr long from store center to nearest road side with loading unloading at both points. Loading unloading plus carriage per pole 21-50km |
| 38 | Cartage for SP55 Pole 8.5 mtr long from store center to nearest road side with loading unloading at both points. Loading unloading plus carriage per pole 21-50km |
| 39 | Cartage of petty material by vehicle from store center to nearest road side including loading and unloading at both ends 21-50km |
| 40 | Cartage/transportation of 63 kVA Distribution Transformer (DTR) from store/workshop to site for a lead distance of 21 km to 50 km, including loading, unloading, handling, stacking at site, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 41 | Charges of Head Load Cartage (PCC Pole 8.5 Mtr Long) from Road site To work Site as per RESP Specification of Engineer incharge distance 01-03 KM |
| 42 | Charges of Head Load Cartage STP SP-33 Pole) from Road site To work Site as per RESP Specification of Engineer incharge distance 01-03 KM |
| 43 | Charges of Head Load Cartage STP SP-55 Pole) from Road site To work Site as per RESP Specification of Engineer incharge distance 01-03 KM |
| 44 | Headload cartage/transportation of 63 kVA Distribution Transformer (DTR) from nearest motorable point to site for a lead distance of 1 km to 3 km, including manual handling, loading, unloading, shifting, stacking at site, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 45 | Charges of Laying, Stringing, sagging of AB Cable3x95+1x70 mm2 including fixing of Insulated, Piercing Connector in all complete work. as per direction of Engineer in charge |
| 46 | Straightening of tilted STP poles including excavation around pole base, adjustment of alignment, re-erection/positioning, refilling with suitable earth/stone ballast, ramming, dressing of pit, and making the pole vertical and stable, complete in all respects as per specifications and direction of Engineer-in-Charge. |
| 47 | Erection of 11 kV stay set including excavation of pit, fixing of stay rod, stay wire, turnbuckle, stay insulator, anchor plate, thimble, clamps, and all necessary accessories, followed by proper tightening, alignment, backfilling with soil/stone ballast, ramming and dressing, complete in all respects as per RESPO specifications and direction of Engineer-in-Charge. |
| 48 | Resagging of loose 11 kV overhead line, including adjustment of conductor tension, re-stringing where required, tightening of jumpers, checking and correction of sag as per standard sag-tension chart, and all associated works complete as per specifications and direction of Engineer-in-Charge. |
| 49 | Installation of LT Distribution Box including fixing on PCC pole/wall mounted structure, proper alignment and tightening, making of all incoming and outgoing cable connections, fixing of internal bus bars and accessories, provision of earthing connection, and all associated works complete in all respects up to commissioning, as per approved drawings, UPCL specifications and direction of Engineer-in-Charge. |
| 50 | Painting of STP SP-55 pole structure including angles, channels and all steel parts, with one coat of red oxide primer followed by two coats of aluminium paint. The work also includes painting of two fluorescent strips of alternate red and white colour, each 30 cm wide, up to 1.5 m height from ground level, complete in all respects as per specifications and direction of Engineer-in-Charge. |
| 51 | Charges for laying, stringing and sagging of LT Aerial Bunched (AB) Cable of size 3 × 70 + 1 × 50 +1X16 sq.mm, including fixing of insulated piercing connectors (IPC), binding, tensioning, and all associated works complete in all respects as per specifications and direction of Engineer-in-Charge. Please Enable Macros to View BoQ information |