| 1 | Wiring for light point / ceiling fan point /wall fan point including 6 amp 3 pin socket/call bell point / exhaust fan point with 1.5 sq mm FRLS /HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable size GI box and earthing the point with 1.5 sq mm,1.1 kV, FRLS/HFFR PVC insulated copper conductor single core cable etc as required.Preferred Make ( Wire,1.1 kV ):-Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approvedby Engineer-in ChargePreferred Make (Switch,Socket,Blank plate etc):-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in ChargePreferred Make ( MMS Pipe):-Prestoplast/Precision/AKG/ Anchor/Equivalent approved by Engineer-in Charge |
| 2 | Upto 6 metres.( Group A ) |
| 3 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required .Preferred Make ( Wire,1.1 kV):- Finolex/RR Kabel/Polycab/Havells/KEIPreferred Make ( MMS Pipe):- Presto plast/Precision/AKG/ Anchor/Equivalent approved by Engineer-in Charge |
| 4 | 2 X 1.5 sq mm + 1 X 1.5 sq mm for earth wire |
| 5 | 2 X 2.5 sq mm + 1 X 2.5 sq mm for earth wire |
| 6 | 2 X 4 sq mm + 1 X 4 sq mm for earth wire |
| 7 | 2 X 6 sq mm + 1 X 6 sq mm for earth wire |
| 8 | 4 X 2.5 sq mm + 2 X 2.5 sq mm for earth wire |
| 9 | 4 X 4 sq mm + 2 X 4 sq mm for earth wire |
| 10 | 4 X 6 sq mm + 2 X 6 sq mm for earth wire |
| 11 | 4 X 10 sq mm + 2 X 6 sq mm for earth wire |
| 12 | 4 X 16 sq mm + 2 X 6 sq mm for earth wire |
| 13 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required.Preferred Make (MMS Pipe):-Presto plast/Precision/AKG/Anchor/Equivalent approved by Engineer-in Charge |
| 14 | 20 mm |
| 15 | 25 mm |
| 16 | Supplying and drawing following sizes of FRLS/ PVC insulated 1.1 kV grade copper conductorsingle core cable in the existing surface /recessed steel / PVC conduit as required.Preferred Make (Wire):- Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approved by Engineer-in Charge |
| 17 | 2 X 1.5 sq mm +1 X 1.5 sq mm for E.C.C |
| 18 | 2 X 2.5 sq mm +1 X 2.5 sq mm for E.C.C |
| 19 | 2 X 4 sq mm +1 X 4.0 sq mm for E.C.C |
| 20 | Supplying and fixing following sizes / modules ,GI box along with modular base & cover plate for modular switches in recess etc as required.Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge. |
| 21 | 1 or 2 Module (75 mm X 75 mm ) |
| 22 | 3 Module (100 mm X 75 mm ) |
| 23 | 4 Module (125 mm X 75 mm ) |
| 24 | 6 Module (200 mm X 77 mm ) |
| 25 | 12 Module (200 mm X 150 mm ) |
| 26 | Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge. |
| 27 | 5 /6 Amps Switch |
| 28 | 15 /16 Amps Switch |
| 29 | 3 pin 5 /6 Amps Socket Outlet |
| 30 | 6 pin 15 / 16 Amps Socket Outlet |
| 31 | Supplying and fixing Two Module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.Preferred Make:-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge |
| 32 | Supplying & Fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 25 Amps modular socket outlet and 25 Amps modular SP MCB, \\"C\\" curve including connections,painting etc.as required.Preferred Make:-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge |
| 33 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required Preferred Make:- Crabtree/Hager Insysta/Legrand Myline range/MK/Equivalent approved by Engineer-in Charge. |
| 34 | Installation , testing and commissioning of pre- wired, fluorescent fitting /compact fluorescent fitting/LED fittings of all types complete with all accessories and tube etc. directly on false ceiling / wall including connection with 3 X1.5 sq mm FRLS PVC insulated copper conductor single core cable and earthing etc as required. |
| 35 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Wall Surface as required incl. S+F of 1 X 10 SWG rust free GI wire for E.C.C making holes and manding good the damages to original finish incl painting.( Cable Dept supply) |
| 36 | Upto 35 sq mm (rust free clamped with 1 mm thick rust free saddle) |
| 37 | Above 35 sq mm and upto 95 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 38 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Cable Tray along with S+F of 10 SWG GI wire as earth wire as required. |
| 39 | Upto 35 sq. mm (clamped with 1mm thick saddle @ 3 sets per metre.) |
| 40 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25 X 3mm MS flat clamp @ 3 sets per metre.) |
| 41 | Supplying and making End Termination with brass compression gland and lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 kV grade as required.Preferred Make:-ARUN/Dowells/3M /Equivalent approved by Engineer-in Charge |
| 42 | 2 X 10 sq mm (19 mm ) |
| 43 | 2 X 16 sq mm ( 22 mm ) |
| 44 | 4 X 10 sq mm (25 mm ) |
| 45 | 4 X 16 sq mm (28 mm ) |
| 46 | 3.5 X 25 sq mm (28 mm ) |
| 47 | 3.5 X 35 sq mm (32 mm ) |
| 48 | Supplying and Fixing DP/4P Sheet Steel Enclosure on surface/recess complete with connection,testing and commissioning etc.as required with out MCB/MCCB Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 49 | Two Pole Enclosure for MCB |
| 50 | Four Pole Enclosure for MCB |
| 51 | Supplying and fixing following way, Single Pole and Neutral, IP- 43, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Preferred Make:-Legrand/Hager/L&T/ABB/Equivalent approved by Engineer-in Charge |
| 52 | 8 Way , Double door |
| 53 | 12 Way Double door |
| 54 | Supplying and fixing of following ways surface/ recess mounting, Horizontal type, IP-43,415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. Preferred Make:-Legrand/Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge |
| 55 | 8 Way (4 + 24), Double door |
| 56 | Supplying and fixing of following ways surface/ recess mounting, Vertical Type,IP-43, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TP DB is normally used where 3 phase outlets are required.) Preferred Make:-Legrand/L&T/Hager/Siemens/Equivalent approved by Engineer-in Charge |
| 57 | 4 Way (4 + 12), Double door |
| 58 | Supplying and fixing 5 Amps to 32 Amps rating, 240/415 V,10 kA,“C” curve,miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Preferred Make:- Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 59 | Single Pole |
| 60 | Double Pole |
| 61 | Triple Pole |
| 62 | Triple Pole and Neutral |
| 63 | Supplying and fixing 40 Amps to 63Amps rating, 240/415 V,10 kA,“C”curve, MiniatureCircuit breaker suitable for inductive load of following poles in the existing MCB DB or inenclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABBEquivalent approved by Engineer-in Charge |
| 64 | Single Pole |
| 65 | Double Pole |
| 66 | Triple Pole |
| 67 | Four Pole |
| 68 | Supplying and fixing 100 Amps rating, 240/415 V, 10 kA, “C” curve, Miniature Circuit Breaker suitable for inductive load of following poles in the existing MCB DB or in enclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalentapproved by Engineer-in Charge |
| 69 | Four Pole |
| 70 | Supplying and fixing of Molded Case Circuit Breaker,415 Volt, of Breaking capacity 25 kA/35kAwith Icu = Ics (for 1 sec),adjustable overload setting (Thermal Magnetic) with two sets copper spreader terminals suitable for inductive load of following poles in the existing MCB/MCCB DB/SMDB or in enclosure complete with connections, testing and commissioning etc. as required.Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABBEquivalent approved by Engineer-in Charge |
| 71 | 125 Amps, Four Pole Please Enable Macros to View BoQ information |