| Sl. No. | Item Description |
| 1 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil 2.6.1 |
| 2 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.All kinds of soil l 2.26.1 (1.5m to 3.0m) |
| 3 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 4 | Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/ Lindane emulsifiable concentrate of 20% |
| 5 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 6 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 7 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 8 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 9 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) |
| 10 | FORM WORK Centring and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete. |
| 11 | Suspended floors, roots, landings, balcnies and access platform. |
| 12 | Lintels, beams, plinth bams, griders, bressumers and cantilevers. |
| 13 | Columns,Pillars, Piers, Abutments, Posts and Struts |
| 14 | Stairs,(excluding landings) except spiral-staircaces. |
| 15 | Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 16 | Cornices and mouldings |
| 17 | Weather shade,Chajjas, corbels etc. including edges |
| 18 | Extra for additional height in centring, shuttering where ever required with adequate bracing, propping etc. including cost of deshutering and de centring at all levels over a height of 3.5 m ,for every additional height of 1 metre or part thereof (Plan area to be measured) Suspended floors, roots, laning, beams and balconies (Plan area to be measured) |
| 19 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 20 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 21 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.Concrete of M25 grade with minimum cement contant of 330 kg/cum |
| 22 | Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 23 | All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 24 | Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 25 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 infoundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 26 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 insuperstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 27 | Half brick masonry with non modular fly ash bricks of class designation 10, conformingio IS :12894, in super structure above plinth upto floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 28 | Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. |
| 29 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Area of slab upto 0.50 sqm |
| 30 | Area of Slab over 0.50sqm |
| 31 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work. |
| 32 | Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 33 | Providing and fixing 12 mm toughened glass partition with neccessary fittings and Applying clear silicon on joints complete in all respect. |
| 34 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 35 | Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edge |
| 36 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square. |
| 37 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 38 | Providing & Fixing decorative high pressure laminated sheet of plain /wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. 1.0 mm thick |
| 39 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). |
| 40 | Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 41 | Providing and fixing approved brand and manufacture SS 304 grade SS 304 grade Mortice lock with key cylinder fixed fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 42 | Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 300 mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 43 | Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 150mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 44 | Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 45 | Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 46 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.. |
| 47 | Providing and fixing approved brand and manufacturer SS 304 grade hardware's for Glass Doors etc. Providing and fixing approved brand and manufacture SS 304 grade Top & Bottom Patch fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 48 | Providing and fixing approved brand and manufacture SS 304 grade H type 900mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 49 | Providing and fixing approved brand and manufacture SS 304 grade Center Patch Lock wih Cylinder complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 50 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness |
| 51 | Providing and fixing factory made ISI marked partially insulated metal fire rated doorset assembly, for staircase /exit pathway and refuge areas applications, consisting of galvanized iron steel frame and double leaf shutter including necessary hardware accessories, conforming to FD 120 PI classification of IS 3614 :2021 with fire rating of 120 minutes integrity and 30 minutes insulation. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS: 277. The entire fire rated doorset assembly shall be tested in latched condition as per IS 17518 (Part-1) 2022 Frame:The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joint (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS 4351. The smoke seal material shall be of EPDM tested in accordane with ASTM E-84 of minimum size 10 x 4mm. fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed to the three sides to masonary wall opening with CSK/Hex headed fastner of minimum 8 mm dia size and minimum 80mm long hot dip galvanized with 8mm dia Polyamide sleeves @ 5 number at each on vertical sides and 3 number on top side.Door shutter:The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories.Double leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etcAccessories Hardware |
| 52 | Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Clerestory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made. Frame size 65 x 125 mm |
| 53 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 54 | Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete Fastener with threaded dia 10 mm |
| 55 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. Using flats 30x6mm for diagonal braces and central cross piece |
| 56 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of requiredthickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 57 | Providing and fixing ball bearing for rolling shutters. |
| 58 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 59 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate |
| 60 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick |
| 61 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size Size of Tile 600 x 600 mm |
| 62 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm |
| 63 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/sqm including grouting the joint with white cement & matching pigments etc. complete Size of Tile 600x600 mm. |
| 64 | Providing and laying Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately) Size of Tile 600x600 mm |
| 65 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 66 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25 mm thick |
| 67 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete |
| 68 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab of colour Black, Cherry/Ruby Red or equivalent |
| 69 | Extra for pre finished nosing to treads of steps of Granite stone. |
| 70 | Extra for Granite stone flooring in treads of steps and risers using single length up to 2.00 metre . |
| 71 | Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per drawings and direction of Engineer-in-Charge. |
| 72 | Providing and laying 18 mm thick leather finish steel grey granite stone flooring in required design and patterns, in linear as well as curvilinear portions in building flooring, footpath etc. all complete as per the architectural drawings with over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. |
| 73 | Providing and fixing machine cut, mirror/ eggshell 18mm thick Plished granite stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. |
| 74 | 12mm cement plaster of mix : 1:6 (1 cement : 6 fine sand) |
| 75 | 15 mm cement plaster on the rough side of single or half brick wall of mix : 1:6 (1 cement : 6 fine sand) |
| 76 | 6 mm cement plaster to ceiling of mix : 1:3(1 cement: 3 coarse sand) |
| 77 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand). |
| 78 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 79 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 80 | Providing & fixing galvanized low carbon wire, anealed wire Chicken mesh formed by twisting two adjacent wires at least four times, forming a hexagonal shaped strong honeycomb mesh structure on joints of RCC & Brick work before plastering, of required gauge (not less than 21 gauge)and size with nails etc. complete as specified in drawing and as per the Direction of Engineer-in-charge. |
| 81 | Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. Two or more coats on new work |
| 82 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre |
| 83 | Finishing walls with ready mixed Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. |
| 84 | Painting with synthetic enamel paint of approved brand and manufacture to give an evenshade : Two or more coats on new work |
| 85 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge Glass Reinforced Gypsum (GRG) board conforming to IS: 2095- (Part 3):1996 (Boards with BIS certification marks) |
| 86 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main “T” runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross “T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main “T” at 600mm center to center to form a grid of 1200x600 mm and secondary cross “T” of length 600mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main “T” runners to be suspended from ceiling using GI slotted cleats of size 27 x 37x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GIadjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall bepre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge GI Metal Ceiling Lay in perforated Tegular edge global white colour tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. |
| 87 | Providing & fixing false ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/ partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling sectionand perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture’s specification and also including the cost of making openingfor light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specificaton and direction of the Engineer in charge but excluding the cost of painting with: 8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process. |
| 88 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Powder coated aluminum (minimum thickness of powder coating 50 micron) |
| 89 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminum (minimum thickness of powder coating 50 micron) |
| 90 | Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600 Upto 10 mm depth and 10 mm width |
| 91 | Waterproof coating on RCC mother slab: Providing & applying 2 components, spray applied instant setting liquid hybrid polyurea polyurethane based waterproofing membrane, Dr. Fixit Superseal 4500 PUH using plural component airless spray equipment, to form a minimum system thickness of 1.5mm in two alternative coats with a total consumption of 1.6 kg/m2. The membrane shall be applied on horizontal surfaces and on verticals up to 300mm height above the FFL / Soil fill level as per respective project requirement. Surface preparation includes cleaning of concrete surface to remove loose dust, dirt, loose concrete flakes etc., carry out mechanical grinding to achieve CSP 4-CSP 5 profile, application of epoxy primer Dr. Fixit Cipoxy 16D by roller/ airless spray @ coverage of 4-6 m2/kg depends on porosity of concrete, broadcast anti slip grains of 200-300 micron (dried sand) on wet primer at coverage of 0.8-1.0 kg/m2 and allow the same to become to touch dry followed by spray application of Dr.Fixit Superseal 4500 PUH in min 1.5 mm thickness in 2 alternate passes. The membrane shall have 100% Solids, VOC Free, Tensile strength > 15 Mpa as per ASTM D 412, Elongation > 400% as per ASTM D 412, Bond strength > 2 MPa as per ASTM D 7234, Low temperature crack bridging up to 3.2mm as per ASTM C 836, Shore A Hardness 85 as per ASTM D 2240, Puncture Resistance > 1000 N as per ASTM E 154, Resistance to Hydrostatic Head > 7 Bar as per ASTM D 5385,Fire Resistance as per EN 13501-1,Class B, Root Resistance as per CEN/TS 14416. Separation Layer: Providing & Laying min 100 GSM Geotextile (non-woven polyester) membrane with a min of 100mm wide overlap loosely laid over Dr. Fixit Superseal 4500PUH membrane, etc., complete |
| 92 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 93 | Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : In 75x75 mm deep chase |
| 94 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying :(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours.(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours.The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry |
| 95 | Providing and laying broken AAC Block in sunken portion of W.C. & kitchen. These broken Block mixed with cement mortar 1:8 ( 1 cement : 8 coarse sand) laid and compacted properly including supply of labour, material, and tools and plant etc. as per instruction of Engineer-in-charge. |
| 96 | Earth work in excavation over areas ( exceeding 30 cm in depth. 1.5 m in width as well es 10 sqm on plan) including disposal of excavated earth , lead upto 50 m and lift upto 1.5 m; disposed earth to be levelled and neatly dressed. All kinds of soil |
| 97 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth: consolidating each deposited layer by ramming and watering lead |
| 98 | Providing and laying in position cement concrete of specified grade exluding the cost of centring and shuttering-all work upto plinth level. 1.4.8 (1 Cement :4 coarse sand :8 graded stone agregate 40mm nominal size) |
| 99 | Centring and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete. |
| 100 | Lintels, beams, plinth bams, griders, bressumers and contilevers. |
| 101 | Columns,Pillars, Piers, Abutments, Posts and Struts |
| 102 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 103 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth levelConcrete of M25 grade with minimum cement content of 330 kg /cum |
| 104 | All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 105 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement Mortar 1:6 (1 cement : 6 coarse sand). |
| 106 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 107 | 12mm cement plaster of mix : 1:6 (1 cement: 6 fine sand) |
| 108 | 15 mm cement plaster on rough side of single or half brick wall of mix. 1:6 (1 cement: 6 fine sand) |
| 109 | Finishing walls with ready mixed Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. |
| 110 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil |
| 111 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 112 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 113 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 114 | Centring and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete. |
| 115 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 infoundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 116 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 117 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 118 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50mm (base metal of minimum 0.45mm thickness with total coating thickness of 0.05mm) with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 119 | Providing and fixing precoated galvanised steel sheet roofing accessories of total coated thickness 0.50mm (base metal of minimum 0.45mm thickness with total coating thickness of 0.05mm) with Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete :Ridges plain (500 - 600mm) |
| 120 | 12mm cement plaster of mix : 1:6 (1 cement : 6 fine sand) |
| 121 | Earth work in excavation over areas ( exceeding 30 cm in depth. 1.5 m in width as well es 10 sqm on plan) including disposal of excavated earth , lead upto 50 m and lift upto 1.5 m; disposed earth to be levelled and neatly dressed. All kinds of soil |
| 122 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres. |
| 123 | Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density). |
| 124 | Supplying and stacking at site. 53 mm to 22.4 mm size stone aggregate |
| 125 | Stone screening 13.2 mm nominal size (Type A) |
| 126 | Moorum |
| 127 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement Mortar 1:6 (1 cement : 6 coarse sand). |
| 128 | Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25 |
| 129 | Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge. |
| 130 | Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by usingneedle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately).Cement concrete prepared with batch mixing machine |
| 131 | Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. |
| 132 | Providing, laying and making kerb channel 30 cm wide and 50 mm thick with cement concrete 1:3:6 (1 cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth etc. complete and as per direction of Engineerin- charge. |
| 133 | Painting road surface marking with adequate nos of coats to give uniform finish with ready mixed road marking paint conforming to IS : 164, on bituminous surface in white/yellow shade, including cleaning the surface of all dirt, scales, oil, grease and foreign material etc. complete. New work (Two or more coats) |
| 134 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in- Charge. 80 mm thick C.C. paver block of M-35 grade with approved colour design and pattern |
| 135 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured to calculate volume for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 136 | Earth work in excavation over areas ( exceeding 30 cm in depth. 1.5 m in width as well es 10 sqm on plan) including disposal of excavated earth , lead upto 50 m and lift upto 1.5 m; disposed earth to be levelled and neatly dressed. All kinds of soil |
| 137 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth: consolidating each deposited layer by ramming and watering lead |
| 138 | Extra for every additional lift of 1.5 m or part thereof in : All kinds of soil (From 1.5 to 3 m depth) |
| 139 | Supplying and Filling in plinth with local sand and under floors including, watering, ramming consolidating and dressing complete. |
| 140 | Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/Lindone emulsifiable concentrate of 20% |
| 141 | Diluting and injecting chemical emulsion for POSTCONSTRUCTIONAL anti-termites' treatrnent(including the cost of chemical emulsion) Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling and plugging 12 mm diameter holes with cement mortar 1:2 (1 cement: 2 coarse sand) to match the existing floor. |
| 142 | Providing and laying in position cement concrete of specified grade exluding the cost of centring and shuttering-all work upto plinth level. 1.4.8 (1 Cement :4 coarse sand :8 graded stone agregate 40mm nominal size) |
| 143 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone- III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 144 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing : 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) |
| 145 | Centring and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete. |
| 146 | Walls (any thickness) including attached pilasters. Butteresses, plinth and string courses etc. Suspended floors, roots, landings, balcnies and access platform. |
| 147 | Shelves (Cost in situ) |
| 148 | Lintels, beams, plinth bams, griders, bressumers and contilevers. |
| 149 | Columns,Pillars, Piers, Abutments, Posts and Struts |
| 150 | Edges of slabs and breaks in floors and walis- Under 20cms wide |
| 151 | Weather shade,Chajjas, corbels etc. including edges |
| 152 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 153 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 154 | All works above plinth level upto floor V level Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 155 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 156 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 infoundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 157 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 158 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1cement : 4coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups,including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade Area of slab upto 0.50 sqm |
| 159 | Area of Slab over 0.50sqm |
| 160 | Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work |
| 161 | Extra for fixing marble/granite stone over and above coresponding basic item, in facia and drops of width upto 150 mm with expoxy resin based (Araldite or equivalent) adhesive including cleaning etc. complete. |
| 162 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type,core of block board construction with frame of 1 st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 163 | Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of shutters (overall area of door shutter to be measured) |
| 164 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glas excluded) Rectangular or square. |
| 165 | Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. 1.0 mm thick. |
| 166 | Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete. |
| 167 | Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 168 | Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 300 mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 169 | Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 170 | Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. |
| 171 | Steel work welded in built up sections/framed worK including cutting hoisting, rixing in position and applying a priming coat of approved steel primer using structural steel, etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 172 | Providing and laying vitrifed floor tiles in different sizes {thickness to be specified by the manufactruer) with water absorption's less than 0.08 % and conforming to IS : 15622 of approved make in all colours and shades, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand ) including grouting the joint with white cement and matching pigments etc., complete. Size of Tile 600 x 600 mm. |
| 173 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600 x 600 mm |
| 174 | Providing and fixing machine cut, mirror/ eggshell 18mm thick granite stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. |
| 175 | 12mm cement plaster of mix : 1:6 (1 cement: 6 fine sand) |
| 176 | 15 mm cement plaster on rough side of single or half brick wall of mix. 1:6 (1 cement: 6 fine sand) |
| 177 | 6 mm cement plaster to ceiling of mix : 1:3 (1 cement : 3 fine sand) |
| 178 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 179 | Providing & fixing Chicken wire mesh on joints of RCC & Brick work before plastering complete in the direction of Engineer-in-charge. |
| 180 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats |
| 181 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work |
| 182 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / aneling,C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 183 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 184 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 185 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-incharge complete. Upto 5mm depth and 5 mm width |
| 186 | Surface preparation-Wash the surface and remove all loose concrete, grease, oil using wire brush or by surface grinder. All critical areas such as joints, junctions, movement zones, penetrations drainage points and cracks are to be correctly sealed and detailed prior to waterproofing. All hairline cracks < 1mm should be cut and open up to 5mm width to fill with Polymer modified mortar. Separation Layer: Providing & Laying min 100 GSM Geotextile (non-woven polyester) membrane with a min of 100mm wide overlap loosely laid over Dr. Fixit Superseal 4500PUH membrane, etc., complete |
| 187 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-incharge. All kinds of soil |
| 188 | Supplying and stacking of cow dung manure/cattle manure at site including cost and carriage with all lead and lifts, (manure measured in stacks will be reduced by 8% of payment) |
| 189 | Grassing with selection No. 1 doob grass including watering and maintenance of the lawn for 30 days or more till the grass forms a thick lawn, free from weeds and fit for mowing including supplying good earth, if needed (the grass and good earth shall be paid for separately). In rows 5 cm apart in both directions |
| 190 | Providing and applying anti termite treatment of infected trees i/c all branches/leaves by spraying chemical emulsion 0.5% (Chlorpyriphos 20% EC) concentration through power spray machine (@ 100 ml Chlorpyriphos per tree i/c cost of chemical) and as per direction of officer-in- harge.and as per direction of officer-in-charge. |
| 191 | Plantation of Trees, Shrubs, and Hedge at site i/c watering and removal of unserveiceable material’s as per direction of officer in charge (excluding cost of plant & water) Tree Plant |
| 192 | Providing and stacking of Erythrina indica of height 150-165 cm. in big polybag of size 25 cm as per direction of the officer-in-charge. |
| 193 | Providing and stacking of Plumeria alba of height 165-180 cm. with 3-4 branches and thick stem in big size HDPE bags as per direction of the officer-in-charge |
| 194 | Providing and stacking of Cassia fistula (Amaltash) of height 120-135 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. |
| 195 | Providing and stacking of Bauhinia blakeana (Kachnar) of height 120-150 cm. in big poly bags of size 25 cm as per direction of the officer-in-charg |
| 196 | Providing and stacking of Tecoma argentea of height 120-135 cm. in big poly bag of size 25 cm as per direction of the officer-in-charge. |
| 197 | Providing and stacking of Mimusops elengi (Maulsri) of height 150-165 cm. in big poly bag of size 25 cm as per direction of the officer-in-charge |
| 198 | Providing and stacking of Peltophorum species of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge |
| 199 | Providing and stacking of Albizzia lebbek of height 150-165 cm. in bag of size 25 cm as per direction of the officer-in-charge. |
| 200 | Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete. |
| 201 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests |
| 202 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:-a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 203 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. |
| 204 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.Granite Stone of approved shade as per Architect. |
| 205 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink without drain board Size 610x510 mm bowl depth 200 mm |
| 206 | Providing and Fixing central hole C.P. brass Sink Mixer including cutting and making good the walls wherever required complete in all respects as per direction of the Engineer-in-charge |
| 207 | Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. 15 mm nominal bore |
| 208 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighingnot less than 105 gms. |
| 209 | Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms. |
| 210 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:893115 mm nominal bore |
| 211 | Providing and fixing C.P. brass toilet paper holder. |
| 212 | Providing and fixing Health faucet with 1 metre long Flexible Tube and CP wall hook with PVC & SS Screws including cutting and making good the wall wherever required complete as directed by the Engineer-in-charge. |
| 213 | Providing and Fixing straight / offset type flexible single body push fit type WC pan connector with inlet ring and integral single mould sealing fins made of flexible EVA body to be fixed with manufacture supplied grease, including rubber bush / adaptor for use with C.I pipe as supplied with the pan connector complete as directed by Engineer-in-charge. |
| 214 | Providing and fixing C.P cast brass Double coat hook as approved with C.P. brass screws complete as per instructions of the engineer-in-charge. |
| 215 | Providing and fixing Electrically Operated Hand Drier to be operated with 220 volts single phase, with fully hygienic condition, with all accessories including cutting and making good the walls wherever required. |
| 216 | Providing and fixing testing and commissioning of storage type water heater (Geyser) (A. O. Smith make or equivalent) with automatic thermostatic control electric element, pressure release valve, M.S. nuts and bolts etc. conforming to IS: 2082, including cutting holes & making good the wall wherever required complete in all respects. 15 Litres Capacity |
| 217 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 218 | Providing and fixing automatic sensor faucet for cold water, for wash basin complete in all respect including basin mounted auto tap, with infrared sensors with solenoid valves for cold water with electronic circuit and necessary accessories including cutting and making good the walls and floors as per requirement. |
| 219 | Providing and fixing CP bath supply and shower fittings comprising of Wall Mixer with Provision for four/five way auto autodiverter, adjustable type over-head shower with CP shower arm , all with 115mm Long Bend Pipe and Wall Flange ,shower rose, adjustable shower with swivel joint with 6 LPM flow rate etc complete as per manufacturer specification & LEED Green building rating system. |
| 220 | Supplying, Installation, testing and commissioning of Inbuilt UV System with water cooler full SS body from front and rest PSS of minimum filteration capacity of 50 LPH production of RO system inbuilt / externally connected with water cooler with minimum 80 LPH cooling capacity and having 120 Ltrs water storage tank capacity with multiple function of cooling and removing hardness and maintaining TDS as per WHO recommendation by current advanced technology i/c pre filter bowl set of reqd. size, actual required length of GI pipe, nipple, elbow & gate valve of required size for connection & interconnection between the water cooler with RO system and Fabrication of mounting stand made out of 304 grade stainless steel of 650mm x 500mm x 150mm size with angle of size 25mm x 25mm x 3mm thick and stainless steel flat strip size of 25mm x 25mm x 3mm i/c brazing welding, grinding & finishing complete as reqd. |
| 221 | Providing and fixing Differecially abled toilets including Wash basin, Water closet,Cistern, grab bars & hand rails etc. The rate include cost of all material & labour involved in the item complete and all as per direction of engineer incharge.For physically handicap person consisting of; Waste Coupling |
| 222 | Providing and fixing soil, waste and vent pipes. 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 223 | 75 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 224 | Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc. : For 100 mm dia pipe |
| 225 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100 mm dia. Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 |
| 226 | Providing and fixing plain bend of required degree. 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 227 | Providing and fixing double equal plain junction of required degree. 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 228 | Providing and fixing single equal plain junction of required degree : 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 229 | Providing and fixing double unequal plain junction of required degree : 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 230 | Providing and fixing single unequal plain junction of required degree : 100 mm dia. Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 231 | Providing and fixing terminal guard :100 mm dia. Hubless centrifugally cast (spun) iron epoxycoated inside & outside as per IS:15905 |
| 232 | Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe.100 mm dia SS 304 grade coupling with EPDM rubber gasket |
| 233 | Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent pipes and fittings with two coats of synthetic enamel paint of any colour such as chocolate grey, or buff etc. over a coat of primer (of approved quality) for new work. 100 mm diameter pipe |
| 234 | 75 mm diameter pipe |
| 235 | Providing and Fixing 32 mm dia G.I. pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. |
| 236 | Providing and Fixing 40 mm dia G.I. pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. |
| 237 | Providing and Fixing 50 mm dia G.I. pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. |
| 238 | Painting of 32 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality. |
| 239 | Painting of 40 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality. |
| 240 | Painting of 50 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality. |
| 241 | Providing and fixing G.I. Inlet fittings with maximum 3 inlets 32,40 & 50 mm size fabricated from 100 mm dia G.I. pipes and welded G.I. sockets, fixed to C.I. Trap with lead caulked joints and set in cement concrete(1:2:4) complete as directed by Engineer-in-charge. |
| 242 | Providing, fixing, testing and commissioning of UPVC rain water pipes (IS : 4985-1983 class-III ) including injection moulded fittings (heavy duty) (plain or door) e.g. bends, junction, cowls, tees, offsets, access pieces etc. Clamps/Supports jointing with rubber ring/solvent cement joints including cutting chase or holes in walls and floors and making good as required at Site [ Terrace Rain Water Downtake Pipe]. 90 OD |
| 243 | 110 OD |
| 244 | Providing, fixing to the inlet mouth of rain water pipe PVC grating / Jali of following size including all fitting and accessories including civil work. 200 mm x 200 mm size (for Terrace Rain Water) |
| 245 | Providing and fixing in position stainless steel cockroch trap consisting of 0.45 mm thick inner and outer cup and 1.00 mm thick top grating (Jali) with ring to be fixed inside C.I. or uPVC ‘P’ traps with cement concrete. (For Kitchen ) |
| 246 | Providing & fixing 1 mm thick stainless steel grating with rim of approved design including setting in floor with cement mortar. (For Floor Drain)125 mm dia |
| 247 | Providing and fixing trap of self cleansing design with screwed down or hinged with or without vent arm complete, including cost of cutting and making good the walls and floors. 100 mm inlet and 100 mm outlet Hubless Centrifugally cast (spun) Iron pipes epoxi coated inside & outside S&S pipe IS: 15905 |
| 248 | Providing & fixing rain water `Khurras' size 45 x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 Cement: 2 coarse: 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1 m x1m x400 micron, finished with 12 mm cement plaster 1:3 (1 Cement: 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 249 | Providing and Fixing G.I. Reducing elbow of 100 x 50 mm in cement concrete 1:2:4 at all levels for floor drains (exlcuding cost of grating) for connection to floor traps in sunken portions, complete as per drawings and as per approval of the engineer-in-charge. |
| 250 | Providing and fixing 100 mm dia cast brass cleanout plug / floor cleanout with suitable insert keys for opening, male threaded joint with G.I. socket caulked to spun soil pipe including cost of joint etc.complete as directed by Engineer-in-charge.. |
| 251 | WATER SUPPLY (INTERNAL AND EXTERNAL) Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. 20 mm nominal outer dia Pipes |
| 252 | 25 mm nominal outer dia Pipes |
| 253 | 32 mm nominal outer dia Pipes |
| 254 | 40 mm nominal outer dia Pipes |
| 255 | 50 mm nominal outer dia Pipes |
| 256 | 65 mm nominal outer dia Pipes |
| 257 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.15 mm nominal outer dia Pipes |
| 258 | 20 mm nominal outer dia Pipes |
| 259 | 25 mm nominal outer dia Pipes |
| 260 | 32 mm nominal outer dia Pipes |
| 261 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps,i/c cutting and making good the walls etc.(Riser pipe) 40 mm dia, nominal bore |
| 262 | 50 mm dia, nominal bore |
| 263 | Providing and fixing forged brass nickel plated lever operated ball valve of full flow with forged brass hard chrome plated ball with min. working pressure of 25 Kg/cm2. Lever should be anti rust coating, complete in all respects. 15 mm dia |
| 264 | 20 mm dia |
| 265 | 25 mm dia |
| 266 | 32 mm dia |
| 267 | 40 mm dia |
| 268 | Providing & fixing Auto Air vent for cold water supply risers, suitable for pressure not less than 15 Kg/Sq.cm. 15 mm nominal bore |
| 269 | Providing and fixing thermal insulation over water pipes exposed in Toilet, shaft & technical terrace with approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per manufacture's specifications and finishing mechanical protection with 2-3 coat of hardener paint complete. 15 mm dia (9 mm thickness) |
| 270 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.0 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 50 mm dia |
| 271 | 65 mm dia |
| 272 | Providing and Laying uPVC water pipes (I.S:4985) of 10 Kg/cm2 including all fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation including bed concrete (if required), sand bedding all around UPVC pipe & fittings and thrust blocks at bends as per standard design (For garden hydrants). 25 OD |
| 273 | 32 OD |
| 274 | 40 OD |
| 275 | 50 OD |
| 276 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 25 mm nominal bore |
| 277 | Construction brick masonry chamber (for Housing Lawn hydrant) Garden Hydrant with 75 class designation brick work in cement mortar 1:5 (1 cement : 5 find sand) for valve, with CI surface box 100 x 100 x 75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design. 300 x 300 x 500 mm deep With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 278 | Providing and fixing brass ferrule with C.I. mouth cover including boring and tapping the main. 25 mm nominal bore |
| 279 | Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately) : 80 mm dia nominal bore |
| 280 | Providing and placing on terrace polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 281 | Providing and laying High density Polythene (HDPE Pipes) material grade PE-80, working pressure rating PN 4 (0.4 maximum permissible working pressure) confirming IS - 14333 jointed by Butt welding method including testing of joints etc. complete 160 mm OD |
| 282 | 225 mm OD |
| 283 | 250 mm OD |
| 284 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round HDPE & RCC pipes including bed concrete as per standard design : 150 mm Dia. |
| 285 | 200 mm Dia. |
| 286 | 250 mm Dia. |
| 287 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. 150 mm dia. R.C.C. pipe |
| 288 | 250 mm dia. R.C.C. pipe |
| 289 | 300 mm dia. R.C.C. pipe |
| 290 | Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed within a lead of 50 m. All Kinds of Soil Pipes, cables etc., exceeding 80mm dia but not exceeding 300mm dia |
| 291 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mmthick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg.With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 292 | Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, totalweight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg).With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 293 | Extra for depth for manholes Size 90x80 cm With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 294 | Extra for depth for manholes Size 120 x90 cm With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 295 | Constructing Brick Masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 Coarse sand), inside cement plaster 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in Cement Concrete 1:2:4 (1 Cement : 2 Coarse Sand : 4 Graded Stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design. External surface shall be finished with 15mm thick cement plaster 1:6 (1 cement : 6 Coarse sand) as per side conditions.0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete.(Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 296 | Extra depth for circular type Manhole 0.91 internal dia with F.P.S. Bricks class designation 75, depth beyond 0.91 m to 1.67 m |
| 297 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steel bar conforming to IS: 1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specification and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 298 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design ::180 x 150 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 299 | Constructing brick masonry road gully chamber 45x45x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) with precast R.C.C. vertical grating complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 300 | Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete . For pipes 250 to 300 mm diameter |
| 301 | Supply, Installation, Testing & Commissioning of Vertical in line type pump set with SS-316 Casing, SS-316 impeller and SS-316 shaft, mechanical seal, CI based with CED coating, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with-55 protectionfor enclosure, horizontal foot mounted type with class-F insulation, conforming to IS-325 Electrical motor mounted on a common channel base plate with coupling guard, 150 mm dia. pressure gauge with gunmetal isolation cock, level controller, vibration eliminating pads as required, M.S fabricated base plate bolted to cement concrete foundations complete. Each set consists of 2 pumps (1Working +1Standby). At any given time, only one pump need operate. Both the pumps must operate alternatively in service. |
| 302 | Domestic Water OHT Filling Pump Each set consists of 2 pumps (1Working +1Standby). At any given time, only one pump need operate. Both the pumps must operate alternatively in service. |
| 303 | Flushing water OHT Filling Pump Each set consists of 2 pumps (1Working +1Standby). At any given time, only one pump need operate. Both the pumps must operate alternatively in service. |
| 304 | Providing and fixing lever operated gun metal ball valve with SS-316 ball. 25 mm nominal bore |
| 305 | 32 mm nominal bore |
| 306 | Providing and fixing gun metal non- return valve of approved quality (screwed end) : 25 mm nominal bore (Horizontal) |
| 307 | 32 mm nominal bore (Horizontal) |
| 308 | Providing and fixing of Pressure gauge (dial size minimum 6”) weather proof (IP-55) with a scale range from 0 to 10 Kg / cm² including stop cock. |
| 309 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps,i/c cutting and making good the walls etc. 25 mm dia, nominal bore |
| 310 | 32 mm dia, nominal bore |
| 311 | 40 mm dia, nominal bore |
| 312 | Pressure Sand FilterSupply, Installation, Testing and Commissioning of vertical Dual media Pressure Sand Filter (comprising of minimum 750mm media in four graded layer and minimum Height on Straight 1500mm) fabricated from high performance M.S plate of minimum 10mm thick for shell & 12mm thick for dished ends,(Quality of Steel as per IS:2062 Grade B),Tested to 5.0 Kg/m2 , internally treated with coal-tar epoxy, air scouring, collection system initial charge of media, M.S face piping with necessary flanges, gaskets, isolating valves, accessories, nuts & bolts, external painting with 2 coats of red oxide primer and enamel paint etc. with suitable foundation bolts & other accessories, mounting frame, complete as required & as per technical specifications of the following capacities: Discharge : 50 LPM /3 m3/Hour Each Filtration Rate : 15000 lit./m2/h Proposed Dia. : 500 mm Dia |
| 313 | Activated Carban FilterSupply, Installation, Testing and Commissioning of vertical self supporting Activated Carbon Filter (ACF) fabricated from high performance M.S plate of minimum 10mm thick for shell & 12mm thick for dished ends,(Quality of Steel as per IS:2062 Grade B),Tested to 5.0 Kg/m2 , internally treated with coal-tar epoxy, air scouring, collection system initial charge of media, M.S face piping with necessary flanges, gaskets, isolating valves, accessories, nuts & bolts, external painting with 2 coats of red oxide primer and enamel paint etc. with suitable foundation bolts & other accessories, mounting frame, complete as required & as per technical specifications of the following capacities: Discharge : 50 LPM /3 m3/Hour Each Filtration Rate : 15000 lit./m2/h Proposed Dia. : 500 mm Dia |
| 314 | Providing, fixing, testing & commissioning of metering pump type chemical doser with 100 lits. HDPE/ FRP solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 mph, complete in all respects for treated water tank. |
| 315 | Supply, installation, testing and commissioning compact monoblock dry motor sump pumps of suitable rating, with non-clog free flow open impeller, solid handling capacity at least 28mm suitable for operation on 415 volts +10% , 3 Phase, 50Hz, A.C supply, speed 2900 RPM including oil chamber, guide wire for lifting & lowering of pump, G.I. galvanized lifting chain, complete. The above pump sets must be supplied complete with following accessories. 1) GI Piping of 80mm dia for individual pump delivery line and 65 mm dia for common delivery line, to be terminated outside the sump. 2) 50 mm dia Butterfly valve.-2 Nos3) 50 mm dia reflux valve.- 2 Nos4) Electrical switch panel with DOL starter having all necessary accessories & safety devices of standard specifications. Automatic built-up water level controller with necessary length of cable upto control panel. No. of Pumps/set : 2nos. (1 W + 1 S)Discharge : 100 LPM Each Head : 10 Meters |
| 316 | Borewell Submersible pumpSupply installation testing and commissioning of borewell submersible pump for suitable rating, chrome steel shaft, suitable for operation on 415 volt ±10%, 3 phase, 50 Hz A.C. supply, speed 2900 RPM, including necessary submersible cable of 2Rx3x6 Sq. m. size, outdoor type M.S. control panel and all other accessories required to make it completely functional as per the technical specifications:Discharge: Approx. 10 m3/hrRecommended Head : 80 M min.Control Panel - 1 Nos, STAR DELTA starter of required rating (M.S. Fabricated in cubicle pattern). |
| 317 | Supply, Installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof Sub Distribution Board made out of 2.0 mm thick CRCA sheet complete with following equipments, including ammeter, ammeter selector switch, voltmeter, voltmeter selector switch, indicating lamps, CT's, internal wiring with suitable size wires/ cable, interconnection, painting etc as required. Panel describe as above |
| 318 | SEWAGE TREATMENT PLANT The Contractor shall carry out the complete investigation, analysis, review & design of Works, submission of as applicable all plans and documents to all relevant Authorities, secure all the necessary statutory approvals under the contract. The Contractor to factor cost associated in his tender for all such requirements. The Contractor shall be responsible for testing, commissioning & handing over of the completed works. Supply, installation, testing & commissioning of 40 KLD capacity Sewage Treatment Plant based on MEMBRANE BIO-REACTOR (MBBR) including Pressure Gauge, Pressure Transmitter, Air Rota meter, Level Switches, Ultra Sonic Level Transmitter, Magnetic Flow Meter, Flow Meter –Paddle Type, PLC etc.Motors will be as per IS 325, TEFC squirrel cage induction motors. Degree of protection will be IP55. Motors are suitable for supply voltage of 415 volts 10% and frequency of 50 Hz 5%, and combined variation 10%. Insulation Class ‘F’ considering temperature Rise as Class ‘B’. Efficiency Class IE3. |
| 319 | The above pump sets must be supplied complete with following accessories. 1) GI Piping of 80mm dia for individual pump delivery line and 65 mm dia for common delivery line, to be terminated outside the sump. 2) 50 mm dia Butterfly valve.-2 Nos3) 50 mm dia reflux valve.- 2 Nos4) Electrical switch panel with DOL starter having all necessary accessories & safety devices of standard specifications. Automatic built-up water level controller with necessary length of cable upto control panel.No. of Pumps/set : 2nos. (1 W + 1 S)Discharge : 100 LPM Each Head : 10 Meters |
| 320 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including geting out and disposal of excavated earth, lead upto 50m and lift upto 1.5m, as directed by Engineer-in-Charge. All kinds of soil |
| 321 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 322 | Extra for every additional lift of 1.5 m or part thereof in. All kinds of soil. |
| 323 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size). |
| 324 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves,chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing & reinforcement with1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) |
| 325 | Centring and shuttering including stutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and acees platform |
| 326 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of Grade Fe-500D or More. |
| 327 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 328 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12mm dia steel bar conforming to IS :1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and heaving manufactures permanent identification mark to be visible even after fixing \\" including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6: (1 cement :3 coarse sand :6 graded stone aggregate 20mm nominal size )complete as per design. |
| 329 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality.HD-20 circular shape 560 mm internal diameter. |
| 330 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer –in-charge, upto 90 metre depth below ground level. All types of soil 400 mm dia. |
| 331 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer –in-charge. 200 mm nominal size dia. |
| 332 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 200 mm nominal size dia. |
| 333 | Supplying, filling, spreading & levelling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 334 | Supplying, filling, spreading & levelling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 335 | Supplying, filling, spreading & levelling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer –in-charge. |
| 336 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 337 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 338 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 200 mm dia |
| 339 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 200 mm clamp. |
| 340 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer –in-charge, upto 90 metre depth below ground level. All types of soil 300 mm dia |
| 341 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 342 | Supplying, assembling, lowering and fixing in vertical position in bore well,unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 100 mm nominal size dia. |
| 343 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 344 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 345 | Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer –incharge. |
| 346 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 100 mm nominal size dia. |
| 347 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 348 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 100 mm dia |
| 349 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 100 mm dia |
| 350 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). 100 mm dia |
| 351 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: 450 lpn at 35 m Head |
| 352 | Supplying, Installation, testing & commissioning of dust & vermin proof double door with canopy type taperd roof wall / floor mounted compartmentlised feeder piller type cubical control Panel for fire fighting terrace pump of front area not less than 1.0 Sqmtr. and depth not less than 300 mm, made out of 2mm thick CRCA sheet with 100 Amp. 4 strip aluminium bus bars with front openable door & locking arrangement, interconnection, control wiring, intrigation with pressure switch i/c suppying & fixing following switchgears & control gears / starters etc. as required. with enclosure protection class IP 65 as required. Selector switch for local / remote, auto / manual / off operation ON / OFF indication etc. (2 Set) |
| 353 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm) |
| 354 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 355 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 356 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 357 | Supply of following sizes of ISI marked aluminium conductor XLPE insulated cable as per IS 7098, armoured, served, sheathed 1100 volts grade. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 16 sq.mm Upto 35 sq. mm |
| 358 | 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. ( For Underground ) 100 mm. Dia |
| 359 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (For Plant Room piping/Vertical Riser/Downcomer/Floor ) 80 mm. Dia |
| 360 | 100 mm. Dia |
| 361 | 150 mm. Dia |
| 362 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required :Single Headed steelness steel |
| 363 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 100 mm. Dia |
| 364 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 365 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required. 100 mm. Dia |
| 366 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 100 mm. Dia |
| 367 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : steelness steel (Grade-304) |
| 368 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 M |
| 369 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required. steelness steel (Grade-304) |
| 370 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required. 2 way-100 mm dia M.S. Pipe |
| 371 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 372 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 373 | Supply, installation and testing of cylindrical type flanged air cushion tank, 250 mm dia, 1200 mm long and of thickness 8 mm M.S., suitable supporting legs with MS plate of size 75x75x5 mm at the bottom and grouted in CC foundation. The air cushion tank shall be provided with air release valve, stop cock, safety valve, pressure gauge, 25 mm dia drain valve, tested to min 25 Kg/cm2 complete including painting with synthetic enamel paint of approved shade with all accessories as per direction of the Engineer-in-charge. (For Risers) |
| 374 | Providing & fixing air release valve with forged brass body full way ball valve type isolating valve, flanges / union, suitable for sprinkler / wet riser / down comer system with all necessary connections complete in all respects. 25 mm dia air release valve |
| 375 | Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete. |
| 376 | Providing & Fixing of MS door made up of 16 gauge MS Sheet capable of accommodating fire hose reel, landing valve, hose pipes, fittings, 1 No. CO2 & 1 No. Dry podwer type portable fire extinguishers & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with one coat of primer & two coat of finished stove enamelled post office red colour paint & \\"FIRE HOSE\\" written on front.(Approx. size of door: 2100 mm Height, Width of Door as per Shaft Size) |
| 377 | Supply, fixing, testing and commissioning of screwed type brass / bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 & spindle AISI 410) with setting & gland of superior quality having minimum working pressure of 16 kg/sqcm. 25 mm Dia |
| 378 | Providing, fixing water flow meter on test line complete with all accessories for flow indication , monitoring & testing of fire pumps with bypass arrangment including piping & bypass valves. 150 mm dia |
| 379 | Providing and Fixing of CO2 (Carbon Dioxide) based Portable Fire Extinguisher I.S.I. Marked, Valve shall be to IS 3224 Marked, PESO Approved Cylinder and shall be IS 7285 Marked on Body, fitted with High Pressure Wire Braided Hose & Flat Horn with Diffuser, fixed to wall with brackets including all necessary accessorises, IS 15683:2018 Marked as per the directions of Engineer-in-charge. Capacity 4.5 kg. (IS : 15683:2018) |
| 380 | Providing and Fixing of Dry Chemical Powder based Portable Fire Extinguisher, filled with DCP (ABC) MAP-90% (Mono-Ammonium Phosphate) Powder, Stored Pressure Type, UGTS Pressure Gauge, CE Marked Valve with NRV, fitted with EPDM Rubber Hose, fixed to wall with brackets including all necessary accessorises, Applicable on Class A,B & C and Electrically-Started-Fire, IS 15683:2018 Marked as per the directions of Engineer-in-charge. Capacity 6 Kg (IS : 15683:2018) |
| 381 | Providing and Fixing of Wet Chemical (K Type Kitchen) Portable Fire Extinguishers, Capacity 6 Litre, body made of SS 304-L, Squeeze Grip NRV Valve, UGTS Pressure Gauge EPDM Hose with Nozzle, Pressureized with Dry Nitroge and mainted as per IS 2190:2010 Revision Fourth as per the directions of Engineer-in-charge. |
| 382 | Providing and fixing Fire related signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. |
| 383 | INTERNAL ELECTRICAL WORKWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 384 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 385 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc .as required. |
| 386 | Wiring for light/ power plug with 2X4 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 387 | Wiring for light/ power plug with 4X4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit along with 2 Nos. 4 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required.. |
| 388 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed PVCconduit as required. 2x1.5 sq mm + 1x1.5 sq mm earth wire |
| 389 | 2x2.5 sq mm + 1x2.5 sq mm earth wire |
| 390 | 4x2.5 sq mm + 2x2.5 sq mm earth wire |
| 391 | 2x6 sq mm + 1x6 sq mm earth wire. |
| 392 | 2x10 sq. mm + 1x6 sq. mm earth wire |
| 393 | 2x16 sq. mm + 1x6 sq. mm earth wire |
| 394 | 4x6 sq mm + 2x6 sq mm earth wire |
| 395 | 4x10 sq mm + 2x6 sq mm earth wire |
| 396 | 4x16 sq mm + 2x6 sq mm earth wire |
| 397 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 398 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 399 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).. (For UPS Supply) |
| 400 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. TV anteena Socket Outlet |
| 401 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) - For Telephone,TV outlet & Data |
| 402 | 3 Module (100mmX75mm) - For Socket outlet. |
| 403 | 6 Module (200mmX75mm) - For Socket outlet. |
| 404 | 8 Module (125 mmX125 mm) |
| 405 | 12 Module (200 mmX150 mm) |
| 406 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 Way, Double Door |
| 407 | 16 Way, Double Door |
| 408 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 12 way (4 + 36), Double door |
| 409 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, C series Miniature Circuit Breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc,as required. Single pole |
| 410 | Supplying and fixing following rating, double pole, 240 volts, MCB complete with connections, testing and commissioning etc. as required. 40 Amp |
| 411 | 63 Amp |
| 412 | Supplying and fixing following rating, four pole, 415 volts, MCB complete with connections, testing and commissioning etc. as required. 63 Amp |
| 413 | Supplying and fixing of following rating double pole (Single phase and neutral) 240 volts, residual current circuit breaker (RCCB), having a current sensivity current 30 miliampere in the existing MCB DB complete with connections, testing & commissioning etc. as required. 40 Amp |
| 414 | 63 Amp |
| 415 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 416 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm |
| 417 | 25 mm |
| 418 | 32 mm |
| 419 | 40 mm dia |
| 420 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 421 | Supplying and fixing Cable End Box (Loose wire box) (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. For 10 way, Double door SPN MCBDB |
| 422 | For 14 way, Double door SPN MCBDB |
| 423 | Supplying and fixing Cable End Box (Loose wire box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415V, on surface/ recess, complete with testing and commissioning etc. as required. For 8way, Double door TPN MCBDB |
| 424 | Supply, erection, testing and commissioning of following sizes of splitter of aluminium die cast body in suitable size of G.I. Box. 8way |
| 425 | Supply & fixing of following size (GP RACEWAY- Fabricated from GP Sheet) race ways for electrical & LV wiring including neoprene gasket in joints, cutting the floor & jaming the race way / hanging in ceiling, supporting arrangement as approved by consultant / architect with all necssary hard ware (including civil work) as per site requirement. The thickness of raceway & cover shall be as per technical specification. 100 mm wide x 40 mm deep. |
| 426 | 150 mm wide x 40 mm deep. |
| 427 | 200 mm wide x 40 mm deep. |
| 428 | Supply & fixing of following size of Raceway Junction Box made out of GP Sheet for electrical & LV wiring including, cutting the floor & jaming the junction box / hanging in ceiling, supporting arrangement as approved by consultant / architect with all necssary hard ware (including civil work).(Junction box to be provided as per drawing/ as per site requirement & as per specification). The thickness of junction box shall be a as per thechnical specification. 150 mm wide x 50 mm deep. |
| 429 | 200mm wide x 50 mm deep |
| 430 | 250mm wide x 50 mm deep |
| 431 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single corecable etc. as required. |
| 432 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 433 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting/ LED fittings of all types, complete with all accessories and tube/lamp/ LED etc. directly on ceiling/ wall/ false ceiling with GI Chain included for fixing wherever required, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 434 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.2 x 1.5 sq mm |
| 435 | 3 x 1.5 sq mm |
| 436 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet (near equipment point) and 25 A modular SP MCB, “C” curve (at accessible point) including connections, painting etc. as required. |
| 437 | Supply of following sizes of ISI marked aluminium / copper conductor XLPE insulated cable as per IS 7098, armoured, served, sheathed 1100 volts grade. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 3.5 core, 185 sq.mm. |
| 438 | 3.5 core, 95 sq.mm. |
| 439 | 3.5 core, 70 sq.mm. |
| 440 | 3.5 core, 35 sq.mm. |
| 441 | 4 core, 16 sq.mm copper cable |
| 442 | 4 core, 10 sq.mm copper cable |
| 443 | 4 core, 6 sq.mm copper cable |
| 444 | 2 core, 16 sq.mm copper cable |
| 445 | 2 core, 10 sq.mm copper cable |
| 446 | 2 core, 6 sq.mm copper cable |
| 447 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as Upto 35 sq. mm |
| 448 | Above 35 sq. mm and upto 95 sq. mm |
| 449 | Above 95 sq. mm and upto 185 sq. mm |
| 450 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 451 | Above 35 sq. mm and upto 95 sq. mm |
| 452 | Above 95 sq. mm and upto 185 sq. mm |
| 453 | Above 185 sq. mm and upto 400 sq. mm |
| 454 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size on cable tray as required. Upto 35 sq. mm (clamped with cable tie) |
| 455 | Above 35 sq. mm and upto 95 sq. mm (clamped with cable tie) |
| 456 | Above 95 sq. mm and upto 185 sq. mm (clamped with cable tie) |
| 457 | Above 185 sq. mm and upto 400 sq. mm (clamped with cable tie) |
| 458 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 x 6 sq. mm (19mm) |
| 459 | 2 x 10 sq. mm (19mm) |
| 460 | 2 X 16 sq. mm (22mm) |
| 461 | 3½ X 35 sq. mm (32mm) |
| 462 | 3½ X 70 sq. mm (38mm) |
| 463 | 3½ X 95 sq. mm (45mm) |
| 464 | 3½ X 185 sq. mm (57mm) |
| 465 | 4 X 10 sq. mm (25mm) (The Termination including 4 x 6 sq. mm cable) |
| 466 | 4 X 16 sq. mm (28mm) |
| 467 | Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS insulated wire including termination complete as required in existing cable tray.1C x 16 sq.mm PVC Insulated cu wire including end termination. |
| 468 | Supply, Installation, Testing & Commissioning of Earthing Junction Box size - 400mm x 300mm x 80mm made out of 16 SWG CRCA sheet with seven tank process & powder coating, earthing link (32mmx6mm copper strip), front door with glass as complete as required. |
| 469 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 470 | 150 mm wide x 50 mm depth x 1.6 mm thickness. |
| 471 | 300 mm wide x 50 mm depth x 1.6 mm thickness. |
| 472 | 450 mm wide x 50 mm depth x 2.0 mm thickness. |
| 473 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 474 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 475 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 476 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 477 | 150 mm wide x 50 mm depth x 1.6 mm thickness. |
| 478 | 300 mm wide x 50 mm depth x 1.6 mm thickness. |
| 479 | 450 mm wide x 50 mm depth x 2.0 mm thickness. |
| 480 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 481 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 482 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 483 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 484 | 150 mm wide x 50 mm depth x 1.6 mm thickness. |
| 485 | 300 mm wide x 50 mm depth x 1.6 mm thickness. |
| 486 | 450 mm wide x 50 mm depth x 2.0 mm thickness. |
| 487 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 488 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 489 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 490 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 491 | 150 mm wide x 50 mm depth x 1.6 mm thickness. |
| 492 | 300 mm wide x 50 mm depth x 1.6 mm thickness. |
| 493 | 450 mm wide x 50 mm depth x 2.0 mm thickness. |
| 494 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 495 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 496 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 497 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 498 | 150 mm wide x 50 mm depth x 1.6 mm thickness. |
| 499 | 300 mm wide x 50 mm depth x 1.6 mm thickness. |
| 500 | 450 mm wide x 50 mm depth x 2.0 mm thickness. |
| 501 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 502 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 503 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 504 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 505 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 506 | Supplying, Installation, Testing and commissioning of Microwave technology based occupancy sensor having high performance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 3 meter and for 5m X 20m coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. |
| 507 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 508 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 509 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 510 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 511 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 512 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 513 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 514 | Providing and fixing earth bus of 50 mm X 5 mm GI strip on surface for connections etc. as required. |
| 515 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 516 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
| 517 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 518 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 519 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 520 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 521 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 522 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required 3C x 240 Sqmm, 11KV XLPE |
| 523 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required 3C x 240 Sqmm, 11KV XLPE |
| 524 | Supplying of 11 KV grade aluminium conductor, cross linked polyethylene (XLPE) insulated individual core screened, flat steel/strip armoured PVC sheathed cable complete as required. 3C x 240 Sqmm, 11 KV XLPE |
| 525 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required Above 120 sq. mm and upto 400 sq. mm |
| 526 | Supply of following sizes of 1.1KV grade Copper conductor XLPE insulated and FRLS PVC sheathed armoured control cable including termination conforming to relevant IS. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 2.5 sq.mm. |
| 527 | 10 core, 2.5 sq.mm. |
| 528 | 12 core, 2.5 sq.mm. |
| 529 | Supplying & Placing of First aid box as approved by St.John Ambulance Brigade /Indian Red Cross society conforming to IS : 2217 - 1963 etc as reqd. |
| 530 | Supplying & Installation of Shock treatment chart duly mounted on a wooden frame with glass on, as required in 2 languages (Hindi & English) etc. as reqd |
| 531 | Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 1.1 KV dielectric strength as per latest IS 15652-2006 etc. as reqd. |
| 532 | Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd. |
| 533 | Supply of LED indoor surface downlighter suitable for general lighting. Luminaire should have pressure die-cast Al housing with diffused optics. The luminaire should have CRI > 80 and CCT of 6500K. The luminaire shall be compliant with IP20, IK02 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 1700 lumens and maximum system wattage of 14 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 30k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. The fixture housing should be available in colors aluminium and grey. Luminaire manufacture shall provide LM79 report from NABL/UL accredited lab & LM80 report issued by LED manufacturer. Both the fixture and Driver should be of same make & must have separate BIS approval. (Make-Philips/Signify Cat Ref. No: SM296C LED15S or equivalent). |
| 534 | Supply of LED indoor surface downlighter suitable for general lighting. Luminaire should have pressure die-cast Al housing with diffused optics. The luminaire should have CRI > 80 and CCT of 6500K. The luminaire shall be compliant with IP20, IK02 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 1700 lumens and maximum system wattage of 14 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 30k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. The fixture housing should be available in colors aluminium and grey. Luminaire manufacture shall provide LM79 report from NABL/UL accredited lab & LM80 report issued by LED manufacturer. Both the fixture and Driver should be of same make & must have separate BIS approval. (Make-Philips/Signify Cat Ref. No: SM296C LED15S or equivalent). |
| 535 | Supply of IP20 recessed LED Downlighter made of pressure die cast aluminum housing with PC diffuser, Fixture should have minimum efficacy at System level (Not Chip Level) >=110 lumens/watt with Minimum system Lumens 2000lm with maximum system wattage of 18W. Life of fixture (Including Driver) : 50000 burning Hrs. @ L70B50 Lumen maintenance, CCT of 4000K/6500K (SDCM<5), CRI >80, PF >0.95, THD<10% (At Full Load) working temp range - 0°C < Ta < 45°C, and operating Voltage Range of 130-320 VAC. It should has a Minimum Internal Surge Protection of 2.5KV. Electronic Switchable ballast. The Luminaire shall be Class B serviceable, it shall have cutout dia of 150mm and product height not more than 40mm. The driver shall be EMI/EMC(B1) compliant. The fixture should have BIS certification for LED Driver & Luminaire.Luminaire manufacture shall provide LM79report from NABL accredited lab & LM80 report issued by LED manufacturer. BIS approved. (Make-Philips/Signify Cat. Ref. No: . DN296B LED20S PSU WH or equivalent). |
| 536 | Supply of of recessed mounted 2X2 LED panel ,made of CRCA housing with high efficiency PS Diffuser. LED Used shall be SMD type and fixture should have minimum efficacy at System level >=120 lumens/watt with Minimum system Lumens 4300 & Max System wattage of 36W, Life of fixture : 50000 burning Hrs. @ L70B50 Lumen maintenance,CCT-6500K, (SDCM<=5), CRI Ra >=80, THD<10%, PF >0.95, an operating Voltage Range of 140 - 270 VAC.Minimum Internal Surge Protection 4.0KV & IP20/IK02 protection, Fixture should comply with to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, IEC 60598-2-2, CISPER 15 for EMC / EMI compliance with flicker free operations ripple <5%. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Both the fixture and Driver should have separate BIS approval. (Make-Philips/Signify Cat. Ref. No: RC380B LED42S or equivalent). |
| 537 | Supply of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 120 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.95.The Batten should be flicker free(Ripple<5%),with high cut-off Voltage at 320V and auto restart. It should have a surge protection of 4kV. The luminaire housing should made of CRCA with a PC UV shielding diffuser. The total power consumption should not exceed 16W (including driver). All test should be done as per IS:10322 (Part 5/Sec 3) & IEC 60598-1,IEC 60529 & Complies IEC 62384, Certification Required: LM 79 & LM 80 . Vendor should provide seperate BIS certifications for luminaire and Driver Seperately, (Make- Signify/Philips Cat No. BN308C LED20S L120 PSU WH or equivalent). |
| 538 | Supply of LED Mirror Supply of Integral LED 2 ft IP20 Batten with PC housing and PC cover. The luminaire should have CCT of 5700K. Luminaire shall be designed to emit at least 1000 nominal lumens at a system efficacy of greater than 100 lumen/watt with maximum input power of 9± 1 Watt. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.9 The fixture should comply with the parameters as per IS10322. The LED driver should comply to IS 15885 sec 13 for Harmonics, IS 10322 for Electrical Safety. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Make-Orient LBLN-10-C- SQ or Equivalenlt. |
| 539 | Supply of Industry grade Bulkhead made of pressure die cast aluminum housing with High quality opal Diffuser with 120 deg light distribution. LED Used shall be SMD type and fixture should have minimum efficacy >=100lumens/watt, Life ofluminaire : 50K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500, CRI >70, PF >0.90. Lumainire should be equipped with built-in driver. The fixture should comply with the parameters as per IS10322. The LED driver should comply to IS 15885 sec 13 for Harmonics, IS 10322 for Electrical Safety. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Make-Orient LIBHP-10-C or Equivalenlt. |
| 540 | Supply of linear receesed/suspended 4 ft luminaire made of extruded aluminium. Fixture should have minimum efficacy>100lumens/watt and a minimum system lumen output of 2800(downlight) lumens and maximum system wattage of 28W. Luminaire should have Life of 50000hrs@L70B50 Lumen maintenance, CCT up to 4000/6500K, CRI >80, PF >0.95, THD<10% and Internal Surge Protection 2.5KV. Fixture is available in 4 ft module with 50-55mm width options. The fixture should comply with the parameters as per IS10322. The LED driver should comply to IS 15885 sec 13 for Harmonics, IS 10322 for Electrical Safety. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Make-Orient LCRDL-28-C-50C or Equivalenlt. |
| 541 | Supply of 20W LED Wall mounted Bracket light fixture, These wall lights are inspired from eclectic sources and draw design inspiration from things that are common place yet inspire us and make every day a special day, one that is to be looked forward to. Pair these wall lights with our Hue bulbs and get that added zing to everyday activities whether that be entertainment or getting you more productive at things which matter - read, relax, concentrate, and energize. Key features are: Clean contemporary design, Fits perfectly into any home, Premium material, Beautiful glass & glossy finish, Dimension (in mm): 100x125x200, Max wattage: 1x 20W with Lamp Base E27. (Make-Philips/Signify Cat. Ref. No: 31455 Chiffe Wall Light 1H or equivalent). |
| 542 | Supply fo IP20 grade flexible LED Strip lights with driver. Drivber should have short circuit protection and should be equipped with 2.5kV inbuilt surge protection. Maximum wattage of luminaire 24± 1W. Approbation & Report: CB report, LM79, IP test, thermal test, CRI≥80, CCT: 2700K, Make-Orient LSTRIP-24-C or Equivalenlt. |
| 543 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 544 | Supply, Installation, Testing and Commissioning of 250 mm sweep decorative Fresh air fan with all accessories suitable for operation single phase 230 volt 50 cycle per second per sec. AC supply etc. as required. in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning earthing etc. as required. (Make : Havells Thrill Air DX or equivalent ) |
| 545 | Supply, Installation, Testing & Commissioning of 35W LED Postop made up of aluminium pressure die-cast aluminum with integrated pole top with polyester powder coating in addition to a specific weathering resistance treatment, color RAL7011.Non-yellowing transparent and textured Polycarbonate UV-protected round symmetrical diffuser 1.5 mm thick with circular radial pattern for glare-free and even light distribution. The fixture should have provision of simplified extraordinary maintence by an easy to remove top openable driver compartment. High Efficiency long life LED module with SMD LED package mounted on MCPCB. Lumen Efficacy of LED>114Lm/W@ 5700K color temperature and CRI >70. Powered by Built In electronic. LED driver with THD<10%, 4kV inbuilt surge protection, high cut off at 325V, auto-restart etc. Suitable for pole mounting having OD of 60 mm and height of 6 meters. Fixture Lumen>3900 Lm, IP 66(no glue), IK 10, PF>0.95, Operating voltage range: 120 V - 277 V Average life L70B50: 50000 hours. Luminaire manufacture shall provide LM79 report from NABL/UL accredited lab & LM80 report issued by LED manufacturer. Both the fixture and Driver should be of same make & must have separate BIS approval. (Make-Philips/Signify Cat. Ref. No: BGP300 LED40 or equivalent ) |
| 546 | Supply, Installation, Testing & commissioning of bollard LED 3000K 230-240Vac 50-60Hz CRI > 80 Input power: 10W Electronic driver, IP rating IP65, impact resistance IK07. MATERIAL CHARACTERISTICS : Extruded aluminium bottom pipe Ø76 x H750mm with polycarbonate diffuser. Lumen output 800 lm, Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted. (Make-Philips/Signify Cat. Ref. No: BCP100 or equivalent) |
| 547 | Supply, Installation, Testing & Commissioning of Aesthetically designed decorative 4.0 Meter hot dipped galvanised mild steel step pole with grey powder finish. Compatible for all post top range. Window - Plasma cut & duly chamfered opening window of 300x110 mm for terminal connections & mounting accessories. Window cover is fitted with allen screws to the pole. with 4 Nos M20 x 700 mmlong \\" J type \\" foundation bolts, suitable RCC foundation etc as complete as required. (Make- Havells-DECO POLE 4M TOP Ø 76 MM or equivalent) |
| 548 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with allaccessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. Two Loop Panel |
| 549 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
| 550 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required |
| 551 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. |
| 552 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 553 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. (75 DBA @3 mtr. & 75CD flashing) |
| 554 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 555 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 556 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 557 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required |
| 558 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
| 559 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 560 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 561 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 562 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required speaker cable Single pair, 2-core, 1.5 sqmm |
| 563 | Supply, Installation, Testing & Commissioning of Patch Panel Cat 6 U/FTP 24 Port- Loaded as per technical specification. |
| 564 | Supply, Installation, Testing & Commissioning of Patch Cord Cat 6 U/FTP 3 feet as per technical specification. |
| 565 | Supply, Installation, Testing & Commissioning of Patch Cord Cat 6 U/FTP 7 feet as per technical specification. |
| 566 | Supply, Installation, Testing, Commissioning of Cat 6, 10G, U/FTP, Information Outlet including G.I. Box and modular cover plate as per technical specification. |
| 567 | Supply , Installtion , Testing and comissioning of 15U wall mount rack with fans , 2 cable managers, satationary shelf , 2 Nos of hardware pkts as per technical specification. |
| 568 | Supply, Installation, Testing & Commissioning of 24 port 10/100/1000Mbps, 4SFP module, L-2 Switch, POE as per technical specifications. |
| 569 | Supply, Installation, Testing & Commissioning of IP Based voice Communication System with 04 Port Voicemail ,04 Port FXS ,04 Port FXO ,1 PRI Trunk lines (30 Ch) Circuit with CLIP Facility , 800 IP users License ,01 Nos. IP Operator Console, 30 Party Conference ,Speed Dial, Music on Hold , Internal/ External ring difference ,Call Barring, Call Pickup, - Redundant server in active-Active mode as per technical specification. |
| 570 | Supply, Installation, Testing & Commissioning of Type 1 IP Phone . Graphic LCD display with backlight 3 user accounts with multi-line appearance keys Local and company-wide phone directories. |
| 571 | Supply, Installation, Testing & Commissioning of Type Basic Phone account , Full duplex speaker phone, . |
| 572 | Supply, Installation, Testing & Commissioning of SFP+ 10GBASE-SR 10 Gigabit Ethernet Optics, 850 nm for up to 300 m,transmission on multimode fiber (MMF). |
| 573 | Supply, Installation, Testing & Commissioning of 6 Core OM4 Multimode Fiber Cable as per technical specification. |
| 574 | Supply, Installation, Testing & Commissioning of 24 Port LC multimode loaded LIU. |
| 575 | Supply, Installation, Testing & Commissioning of LC - LC Fiber patch cord OM4, 3 Mtrs. |
| 576 | Supply, Installation, Testing & Commissioning of 6 Core, Single Mode, OS2 as complete as required. |
| 577 | Supply, Installation, Testing & Commissioning of wifi Access point as complete as required. |
| 578 | Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable |
| 579 | 2 run of cable |
| 580 | 3 run of cable |
| 581 | Supply, Installation, Testing & Commissioning of 4MP IP Network TDN Low-Light IR Rugged Indoor Dome Camera, 1/2.8\\" CMOS or better, 4MP (2304 x 1296) @ 25fps or better, triple stream at various resolution up to 25fps, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, Field of View FoV H:88°-24°, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Motion Detection, Tampering, 4 Privacy Mask, 8 Region Of Intreset, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 256GB SD card support, PoE (802.3 af) and 12V DC, Max 6W, IP 66/67, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T compliant, UL/CSA 62368-1, CE (EN 50130-4), FCC Part 15, EN 55032 & RoHS (EN63000) compliant |
| 582 | Supply, Installation, Testing & Commissioning of 4MP IP Network TDN Low-Light IR Rugged indoor/ outdoor Bullet Camera, 1/2.8\\" CMOS or better, 4MP (2304 x 1296) @ 25fps or better, triple stream at various resolution up to 25fps, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 60m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, Field of View FoV H:85°-24°, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Motion Detection, Tampering, 4 Privacy Mask, 8 Region Of Intreset, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 256GB SD card support, PoE (802.3 af) and 12V DC, Max 6W, IP 66/67, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T compliant, UL/CSA 62368-1, CE (EN 50130-4), FCC Part 15, EN 55032 & RoHS (EN63000) compliant. |
| 583 | Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light 2MP 40 X IP IR PTZ Camera, 1/2.8\\" CMOS, 2MP@ 50fps, H.265, H.264, Min. Illumination required 0.1 lux (color), 0 Lux B/W IR on, 120dB True WDR, HLC, BLC, triple stream, Lens wide 4 to 5mm - Tele 160 to 200mm, 40X motorized focus & zoom lens, Inbuilt/Externla IR uo to 200 Meters, Built in Video Analytics such as Video Motion Detection, Camera Tampering & Auto Tracking, 3DNR, Defog, Electronic Image Stabilization, 24 Privacy Mask, shutter speed 1/1 to 1/10,000 second, PAN Speed upto 400°/s, PAN Range 360° Endless, Tilt Speed upto 400°/s, Tilt Range -20° to +90° (Auto Flip ), 256 Presets, Dual channel Audio G.711a/G.711u/G726, 256GB SD card support, Alarm: 2 In, 1out, High-PoE (UPOE) and 24VAC, IP 66, IK 10 vandal proof, Inbuilt Heater, Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S & G compliant, UL, CE, EN, FCC, NDAA Section 889 & RoHS compliant. |
| 584 | Supply , Installation , Testing and commissioning of 16 Channel NVR (Network Vedio Recorder), for recording upto 64CH @ 1080P with 08 nos. SATA HDDs minimum 64TB storage or more (recording requirement all cameras recording at 4MP, 25fps for 30 days),H.265/H.264/MJPEG/MPEG4 codec decoding, Front Control Pannel with LEDs Indication, 3 nos. USB, iPhone; iPad; Android based Mobile clients, Video Export feature on USB, Search Mode: Time/Date; Alarm; Motion Detection (MD); Exact Search (accurate to a second); Smart Search, Dual HDMI Output, Alarm Input (16 nos.), Alarm Output (6 nos.), 16 POE Ports, eSATA Device, 320Mbps each Incoiming & Outgping throughput, Operating Temperature –10°C to 55°CCertification : CE, FCC & UL including fixing accessories and cable termination with required connectors/Jack, complete in all respect as per instruction of engineer in-charge |
| 585 | Supply, Installation, Testing and commissioning of Managable 24 port Switch with Power on Ethernet (PoE) enabled, 10/100, RJ45 Access ports with PoE complete as required. |
| 586 | Supply, Installation, Testing and Commissioning of pecial Surveillance 6TB SATA HDD internal( For Servers). etc. all complete. |
| 587 | Supply, Installation, Testing and Commissioning of 55\\" LCD for Monitoring for each server etc. all complete. |
| 588 | Supplying installation testing and commissioning of Grid interactive roof top solar photo voltaic power generation system including all the required accessories like Solar PV module, Grid Tie invertor, arrey junction box, cabling & wiring, earthing, surge protection device, FRLSame structure for mounting of solar panel. The cell shall be poly crystaline silicon cells of 6 inch each and module efficiency shall be more than 17%. Solar module shall have linear output warranty with degradation not exceeding 0.7% FRLSom 2nd Year onwards. Minimum 80% power output must be assured at end of 25 years. The FRLSont glass of solar module shall be low iron tempered glass ARC type. Termination box shall be Thermo-plastic, IP 67 or better, UV resistant with built-in-bypass. The nominal power of a single PV module shall be minimum 545 Wp or higher. Positive power tolerance modules only to be used. RF identification tag for each solar module shall be provided inside the module and must be able to withstand environmental conditions. The solar panel shall be complience of IEC 61215, IEC 61730 certified by TUV Rheinland / UL. The solar panel shall be installed as per BOQ & detailed technical specification. |
| 589 | 4.0 KG UL Listed Cylinder Automatic Pre-Engineered System filled with Clean Agent FK 5-1-12, Fitted with DLP Valve mounted on Cylinder Push-In-Connector for Tube, Mounting Bracket, End of Line Adopter and UL Listed Low Pressure Switch for Monitoring System Activation. |
| 590 | 6.0 KG UL Listed Cylinder Automatic Pre-Engineered System filled with Clean Agent FK 5-1-12, Fitted with DLP Valve mounted on Cylinder Push-In-Connector for Tube, Mounting Bracket, End of Line Adopter and UL Listed Low Pressure Switch for Monitoring System Activation. |
| 591 | UL Listed Linear Pneumatic Heat Detection Tube with all necessary fittings & supports, HR Grade,UV Protected, MultiLayered, Made of Special Modified Polyamide Material, Inner diameter 4mm, Outer Diameter 6MM, Operating Pressure 15 8Bar, Maximum Pressure 30 Bar at maximum Temperature of +65 Degree C, Pressurized. |
| 592 | Master Control Unit with Audio Visual Alarm with wiring to make complete system operational. The Control Panel should have provision for integration with Fire Alarm/SCADA/BMS System (Supply to be provide by the end client at 220 Volt AC). |
| 593 | Supply, Installation, Testing & Commissioing of 10 KVA UPS in paralleling mode at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, Inbuilt Isolation transformer as per specification given in the document with following broad features. UPS described as above |
| 594 | Supply, testing and Commissioning of Silent type Diesel Generating Set at 0.8 PF, 415 Volts, 50 cycles per second, 1500 rpm, 3 phase, suitable for parallel operation / PLC based synchronization, 0.85 load factor including circuit breaker for isolation, sound proof acoustic and weather proof enclosure, residential type silencer (as per latest CPCB norms) fabricated out of CRCA sheet of 16 SWG thickness with 9 tank pretreated before powder coating with ventillation system complete in all respects comprising of the following. 320 KVA |
| 595 | Supply, Fixing, testing and Commissioning of Exhaust gas piping system of Class `B' MS pipe as per IS:1239 for upto 150 mm dia and for 200 mm dia & above MS pipe as per IS:3589 with welded joints, cut to required lengths with necessary bends, fittings, flanges, painting over primer coat, with mineral wool / rock wool insulation of minimum 75 mm thick of 150 Kg per cu M density on all sides of exhaust pipe, with chicken mesh wrapping and 26 SWG aluminium sheet cladding complete as required. The aluminum foil should be tightly cladded to insulation surface of pipe. The aluminum cladding shall be locked with sheet metal screws with other sections of aluminium foil. The measurement shall be done on the basis of centre line. (Stack height should be in accordance with emission regulations of CPCB, which will go well above the top most terrace) The exhaust piping system should be suitable for upto 550oC temperature, the surface temperature of exhaust pipe shall not exceed more than 60oC. (The rates are exclusive of support structure) (Note - Final size of exhaust pipe will be confirmed by the DG vendor after calculating the actual back pressure and submit the same to client / consultant for approval) 200 mm dia (wall thickness - 4.85 mm) |
| 596 | Supply & fixing of SS Bellow of following diameter 200 mm dia |
| 597 | Supply & fabrication of D G exhaust pipe supports by M.S angle iron of size not less than 100 x 50 mm x 6/8 mm duly grouted in the wall through minimum 8 mm thick plate and with suitable MS angle / channel iron structure. The entire MS support structure should be painted by 2 coats of anti corrosive paint over primer coat of approved shade and make. The design of support to be duly approved by the Structural Consultant / Architect before fabrication and installation. |
| 598 | H.T. Panel described as above |
| 599 | Design, manufacture, supply, installation, testing and commissioning of 315 KVA, 11 KV /0.415 KV, 3 phase, 4.5 % impedance, 50 Hz delta/star-11 connected, outdoor type, copper wound transformer, oil immersed ONAN cooled, complete with all fittings such as oil conservator, silica gel breather, thermometer, explosion vent with on Load Tap changing (OLTC) arrangement on HV side with Tapping for variations of high voltage from (+) 5% to (-) 15% in steps of 1.25% each with integrated microprocessor based RTCC Panel, bi-directional roller, diagrams & rating plate, Oil temperature indicator, & Winding temperature indicator, Buchholz relay, weather proof Marshalling Box, lifting lugs, first filling of oil, weather proof H.T/L.T cable box etc. complete as per specification. All relays, contacts & CT terminals to be wired upto marshalling box. The Transformer losses should confirm to IS - 1180 Part-1 (2014) with energy efficiency level-1 as per amendment-4 [1.025 KW at 50% load & 3.100 KW at 100% load shall not exceeds by 5.0% (@ 11 KV) of the maximum total loss values. |
| 600 | All outgoing feeder shall be provide with ON / OFF / Trip indication lamp with protection MCB's, Dual Source energy Meter. Main L.T. Panel Described as Above. |
| 601 | 1 no. of 16 AMPS TPN MCCB (25 KA) and 20 amps AC3 duty contactor with 5 KVAR, MPP resin filled, super heavy duty ,525 V capacitor bank, with copper coil 14 % detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete. Capacitor Panel as described above |
| 602 | OUTGOING Panel described as above |
| 603 | OUTGOING 02 Nos. 40 Amp DP MCB (10 KA) |
| 604 | OUTGOING Panel described as above |
| 605 | OUTGOING 04 Nos. 40 Amp DP MCB (10 KA) |
| 606 | Less 5% as per GO Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail